Smitty’s Two Minute Drill Overcurrent Protection

Similar presentations


Presentation on theme: "Smitty’s Two Minute Drill Overcurrent Protection"— Presentation transcript:

1 Smitty’s Two Minute Drill 2017-8 Overcurrent Protection
A drill to help you improve your code skills and your ability to find answers in the code book. © Ted “Smitty” Smith 2016, 2017

2 Directions Left click on the presentation ICON located at the bottom of the slide directory to the left of the this slide. Each slide will transition to the correct answer automatically in 2:00 minutes. The correct answer will transition in 5 seconds. Do not worry about writing down the correct answer for now. You will have the opportunity to do that at the end of the two minute drill Good luck

3 Question 1 An electric arc welder is fed with a THHN 1/0 aluminum conductor. What is the maximum sized over current protective device that can be used to protect these conductors? A. 135 B. 150 C. 270 D. 300 Copyright 2017 Ted "Smitty" Smith

4 Question 1 Answer D. 300 T301.15(B16) determines the ampacity of a THHN 1/0 Aluminum to be 135A . 630.12(B) states that the OCPD can be no larger than 200% of the conductor ampacity. 2 x 135= 270 states that if the calculation results in a size that is not listed as a standard size in we can go up to the next standard size. 270 is not listed in 240.6, the next highest up from there is 300A. Copyright 2005 Ted "Smitty" Smith

5 Question 2 An overcurrent device shall be provided in each ungrounded conductor for each capacitor bank. The rating or setting of the overcurrent device shall be: A. 100% of the rated current of the capacitor bank B. 125% of the rated current of the capacitor bank C. 135% if the rated current of the capacitor bank D. As low as practicable Copyright 2016 Ted "Smitty" Smith

6 Question 2 Answer 460.8(B) D. as low as practicable
Copyright 2005 Ted "Smitty" Smith

7 Question 3 The overcurrent protection for Instrumentation Tray Cable conductor size 20 AWG shall not exceed: A. 3A B. 5A C. 7A D. 10A Copyright 2005 Ted "Smitty" Smith

8 Question 3 answer B. 5A 727.9 Copyright 2005 Ted "Smitty" Smith

9 Question 4 What is the maximum sized overcurrent protective device that can be used to protect non-power limited fire alarm circuit conductors which are size 16 AWG. A. 10 B. 8 C. 6 D. 4 Copyright 2017 Ted "Smitty" Smith

10 Question 4 Answer 760.43 A. 10 amperes
Copyright 2017 Ted "Smitty" Smith

11 Question 5 Household type appliances with surface heating elements having a maximum demand of more than 60 amperes, calculated in accordance with T shall have their power supply subdivided into a minimum of ________ circuits, each of which shall be provided with overcurrent protection rated at not over ________ amperes. 3/30 2/50 3/40 2/40 Copyright 2005 Ted "Smitty" Smith

12 Question 5 B. 2/50 422.11(B) Copyright 2005 Ted "Smitty" Smith

13 Question 6 What is maximum sized overcurrent protective device which can be used for a single load of 28 amperes which is fed with a 10 AWG copper conductor? A. 20A B. 25A C. 30A D. 40A Copyright 2005 Ted "Smitty" Smith

14 Question 6 answer 240.4(D)(7) C. 30 A
Copyright 2005 Ted "Smitty" Smith

15 Question 7 The 1/0 THWN copper secondary conductors of a Delta/Wye three phase 480V/208V transformer may be protected with the overcurrent protection of the primary of the transformer even though the secondary conductors leave the enclosure of the transformer, as long as the primary overcurrent protection is not larger than __________________ amperes. A. 150 A B A C. 650 A D. 350 A Copyright 2005 Ted "Smitty" Smith

16 Question 7 answer C. 650A 240.21(C)(2)
The primary must not be larger than 10 times the ampacity of the secondary conductor if you multiply the OCPD rating times the primary to secondary voltage ratio. In this case the voltage ratio is: 480/208= 2.3 The ampacity of the secondary conductor is 150 amperes. 10 times the ampacity of the secondary is 1500 amperes. 1500/2.3 is 650A approx. Copyright 2005 Ted "Smitty" Smith

17 Question 8 What is the maximum rating allowed for a plug type, Edison based fuse? A. 10A B. 30 A C. 50A D. 100 A Copyright 2005 Ted "Smitty" Smith

18 Question 8 answer B. 30 240.51(A) Copyright 2005 Ted "Smitty" Smith

19 Question 9 The ampere rating of an overcurrent protective device located ahead of a motor control center that has a rating of 300 Amperes for the common power bus and is fed with 250 KCML THWN copper conductors shall not exceed _________________ amperes. A. 255 A B. 250 A C. 300 A D. 200 A Copyright 2005 Ted "Smitty" Smith

20 Question 9 answer C. 300 A requires the OCPD to be rated no higher than the common power bus which is 300 A (B) requires the OCPD to be rated no higher than the conductors ampacity which is 255A, however, if the conductors ampacity is not a standard size and it does not feed multiple receptacle loads and it is rated less than 800 A we can go up to the next standard size, which is 300 A according to Copyright 2005 Ted "Smitty" Smith

21 Question 10 A phase convertor has a single phase input full load ampere rating of 100A. The loads supplied by the phase convertor will be varied. What is the maximum rating of an inverse time circuit breaker that is will be used for overcurrent protection of the phase convertor. A. 100A B. 115A C. 110A D. 125A Copyright 2005 Ted "Smitty" Smith

22 Question 10 Answer D. 125A 455.7(A) Copyright 2005 Ted "Smitty" Smith

23 Question 11 What is the maximum sized overcurrent protection that can be used for a Class 1, power limited circuit that is fed with 18 AWG copper conductors? A. 5A B. 7A C. 10A D. 15A Copyright 2017 Ted "Smitty" Smith

24 Question 11 Answer B. 7A 725.43 Copyright 2005 Ted "Smitty" Smith

25 Question 12 What is the maximum allowed overcurrent protection and circuit rating for low voltage fixed electric space heating equipment? A. 10A B. 15A C. 20A D. 30A Copyright 2016 Ted "Smitty" Smith

26 Question 12 Answer D. 30A Copyright 2005 Ted "Smitty" Smith

27 Question 13 Overcurrent protection is NOT required for circuits of an electrolytic cell dc power process. A. True B. False Copyright 2005 Ted "Smitty" Smith

28 Question 13 answer A. True 668.3(C)(2)
Copyright 2005 Ted "Smitty" Smith

29 Question 14 What is the minimum rating of the overcurrent protection device for an industrial, non-medical use X-ray machine that has a momentary rating of 80A and a long time rating of 50A? A. 80 A B. 50 A C. 40 A D. 25 A Copyright 2017 Ted "Smitty" Smith

30 Question 14 Answer B 50 A 660.6(A) Copyright 2017 Ted "Smitty" Smith

31 Question 15 Which of the following is allowed for use as overcurrent protection for sensitive electronic equipment? A. Inverse time, single pole , 120V circuit breaker B. Inverse time, two pole, 208V circuit breaker C. Common trip, two pole, 60V/120V circuit breaker D. Instantaneous Trip, single pole, 120V circuit breaker Copyright 2005 Ted "Smitty" Smith

32 Question 15 C. Common trip, 2 pole, 60V/120V circuit breaker 647.4(A)
Copyright 2005 Ted "Smitty" Smith

33 Question 16 A resistance welder is fed with a 8 AWG copper feeder conductor, THHN. What is the maximum sized inverse time circuit breaker that can be used for overcurrent protection of the feeder conductors? A. 60 A B. 165 A C. 175 A D. 300 A Copyright 2005 Ted "Smitty" Smith

34 Question 16 answer C 175 A 630.32(B) allows for a maximum of 300% of the conductors ampacity T310.15(B16) lists the conductors ampacity as 55A. 3 x 55= 165 A states that if the values does not match a standard size listed in 240.6, then we go up to the next higher value listed which is 175A Copyright 2005 Ted "Smitty" Smith

35 Question 17 Which of the following is NOT one of the approved methods to reduce clearing time for Arc Energy Reduction for a circuit breaker with the highest continuous current trip rating setting is 1200 Amperes. A. An instantaneous trip setting that is less than the available arcing current B. Zone-selective interlocking C. Universal metering adjustment D. Energy-reducing active arc flash mitigation system Copyright 2005 Ted "Smitty" Smith

36 Question 17 answer C. Universal Metering System
This is made up. There is no system with that name in the electrical industry. 240.87(B) Copyright 2005 Ted "Smitty" Smith

37 Question 18 A circuit breaker that is NOT marked with an Interrupting Rating, has an interrupting rating of ____________________ amperes. A A B A C A D A Copyright 2005 Ted "Smitty" Smith

38 Question 18 answer C. 5000 Amperes 240.83(C)
Copyright 2005 Ted "Smitty" Smith

39 Question 19 Fuse holders for current-limiting fuses shall permit insertion of fuses that are not current-limiting if the manufacturer instructions do not prohibit this practice. A. True B. False Copyright 2005 Ted "Smitty" Smith

40 Question 19 answer B. False 240.60(B)
Copyright 2005 Ted "Smitty" Smith

41 Question 20 A three phase, 480V to 208V transformer will have secondary conductors which will be protected from overcurrent by the primary conductor’s overcurrent device. The secondary conductors will be 13 feet in length. The primary conductors are protected by a 50 Ampere inverse time circuit breaker. If nothing else is know, what is the minimum ampacity required for the secondary conductors? A. 50 A B A C A D A Copyright 2005 Ted "Smitty" Smith

42 Question 10 Answer D A 25’ Foot Tap rule for other than industrial locations 240.21(C)(6) The minimum ampacity of the secondary conductos must be the transformer voltage ratio ( 480/208=2.3) multiplied by 1/3 of the primary OCPD rating. (50/3=16.6) 16.6x2.3= A Copyright 2005 Ted "Smitty" Smith

43 End of Drill Click on this slide to continue to the repeat of the questions. The timer will not operate in this section. Click on each slide to advance. Review the questions and look up the answers. Copyright 2005 Ted "Smitty" Smith

44 Question 1 An electric arc welder is fed with a THHN 1/0 aluminum conductor. What is the maximum sized over current protective device that can be used to protect these conductors? A. 135 B. 150 C. 270 D. 300 Copyright 2017 Ted "Smitty" Smith

45 Question 1 Answer D. 300 T301.15(B16) determines the ampacity of a THHN 1/0 Aluminum to be 135A . 630.12(B) states that the OCPD can be no larger than 200% of the conductor ampacity. 2 x 135= 270 states that if the calculation results in a size that is not listed as a standard size in we can go up to the next standard size. 270 is not listed in 240.6, the next highest up from there is 300A. Copyright 2005 Ted "Smitty" Smith

46 Question 2 An overcurrent device shall be provided in each ungrounded conductor for each capacitor bank. The rating or setting of the overcurrent device shall be: A. 100% of the rated current of the capacitor bank B. 125% of the rated current of the capacitor bank C. 135% if the rated current of the capacitor bank D. As low as practicable Copyright 2016 Ted "Smitty" Smith

47 Question 2 Answer 460.8(B) D. as low as practicable
Copyright 2005 Ted "Smitty" Smith

48 Question 3 The overcurrent protection for Instrumentation Tray Cable conductor size 20 AWG shall not exceed: A. 3A B. 5A C. 7A D. 10A Copyright 2005 Ted "Smitty" Smith

49 Question 3 answer B. 5A 727.9 Copyright 2005 Ted "Smitty" Smith

50 Question 4 What is the maximum sized overcurrent protective device that can be used to protect non-power limited fire alarm circuit conductors which are size 16 AWG. A. 10 B. 8 C. 6 D. 4 Copyright 2017 Ted "Smitty" Smith

51 Question 4 Answer 760.43 A. 10 amperes
Copyright 2017 Ted "Smitty" Smith

52 Question 5 Household type appliances with surface heating elements having a maximum demand of more than 60 amperes, calculated in accordance with T shall have their power supply subdivided into a minimum of ________ circuits, each of which shall be provided with overcurrent protection rated at not over ________ amperes. 3/30 2/50 3/40 2/40 Copyright 2005 Ted "Smitty" Smith

53 Question 5 B. 2/50 422.11(B) Copyright 2005 Ted "Smitty" Smith

54 Question 6 What is maximum sized overcurrent protective device which can be used for a single load of 28 amperes which is fed with a 10 AWG copper conductor? A. 20A B. 25A C. 30A D. 40A Copyright 2005 Ted "Smitty" Smith

55 Question 6 answer 240.4(D)(7) C. 30 A
Copyright 2005 Ted "Smitty" Smith

56 Question 7 The 1/0 THWN copper secondary conductors of a Delta/Wye three phase 480V/208V transformer may be protected with the overcurrent protection of the primary of the transformer even though the secondary conductors leave the enclosure of the transformer, as long as the primary overcurrent protection is not larger than __________________ amperes. A. 150 A B A C. 650 A D. 350 A Copyright 2005 Ted "Smitty" Smith

57 Question 7 answer C. 650A 240.21(C)(2)
The primary must not be larger than 10 times the ampacity of the secondary conductor if you multiply the OCPD rating times the primary to secondary voltage ratio. In this case the voltage ratio is: 480/208= 2.3 The ampacity of the secondary conductor is 150 amperes. 10 times the ampacity of the secondary is 1500 amperes. 1500/2.3 is 650A approx. Copyright 2005 Ted "Smitty" Smith

58 Question 8 What is the maximum rating allowed for a plug type, Edison based fuse? A. 10A B. 30 A C. 50A D. 100 A Copyright 2005 Ted "Smitty" Smith

59 Question 8 answer B. 30 240.51(A) Copyright 2005 Ted "Smitty" Smith

60 Question 9 The ampere rating of an overcurrent protective device located ahead of a motor control center that has a rating of 300 Amperes for the common power bus and is fed with 250 KCML THWN copper conductors shall not exceed _________________ amperes. A. 255 A B. 250 A C. 300 A D. 200 A Copyright 2005 Ted "Smitty" Smith

61 Question 9 answer C. 300 A requires the OCPD to be rated no higher than the common power bus which is 300 A (B) requires the OCPD to be rated no higher than the conductors ampacity which is 255A, however, if the conductors ampacity is not a standard size and it does not feed multiple receptacle loads and it is rated less than 800 A we can go up to the next standard size, which is 300 A according to Copyright 2005 Ted "Smitty" Smith

62 Question 10 A phase convertor has a single phase input full load ampere rating of 100A. The loads supplied by the phase convertor will be varied. What is the maximum rating of an inverse time circuit breaker that is will be used for overcurrent protection of the phase convertor. A. 100A B. 115A C. 110A D. 125A Copyright 2005 Ted "Smitty" Smith

63 Question 10 Answer D. 125A 455.7(A) Copyright 2005 Ted "Smitty" Smith

64 Question 11 What is the maximum sized overcurrent protection that can be used for a Class 1, power limited circuit that is fed with 18 AWG copper conductors? A. 5A B. 7A C. 10A D. 15A Copyright 2017 Ted "Smitty" Smith

65 Question 11 Answer B. 7A 725.43 Copyright 2005 Ted "Smitty" Smith

66 Question 12 What is the maximum allowed overcurrent protection and circuit rating for low voltage fixed electric space heating equipment? A. 10A B. 15A C. 20A D. 30A Copyright 2016 Ted "Smitty" Smith

67 Question 12 Answer D. 30A Copyright 2005 Ted "Smitty" Smith

68 Question 13 Overcurrent protection is NOT required for circuits of an electrolytic cell dc power process. A. True B. False Copyright 2005 Ted "Smitty" Smith

69 Question 13 answer A. True 668.3(C)(2)
Copyright 2005 Ted "Smitty" Smith

70 Question 14 What is the minimum rating of the overcurrent protection device for an industrial, non-medical use X-ray machine that has a momentary rating of 80A and a long time rating of 50A? A. 80 A B. 50 A C. 40 A D. 25 A Copyright 2017 Ted "Smitty" Smith

71 Question 14 Answer B 50 A 660.6(A) Copyright 2017 Ted "Smitty" Smith

72 Question 15 Which of the following is allowed for use as overcurrent protection for sensitive electronic equipment? A. Inverse time, single pole , 120V circuit breaker B. Inverse time, two pole, 208V circuit breaker C. Common trip, two pole, 60V/120V circuit breaker D. Instantaneous Trip, single pole, 120V circuit breaker Copyright 2005 Ted "Smitty" Smith

73 Question 15 C. Common trip, 2 pole, 60V/120V circuit breaker 647.4(A)
Copyright 2005 Ted "Smitty" Smith

74 Question 16 A resistance welder is fed with a 8 AWG copper feeder conductor, THHN. What is the maximum sized inverse time circuit breaker that can be used for overcurrent protection of the feeder conductors? A. 60 A B. 165 A C. 175 A D. 300 A Copyright 2005 Ted "Smitty" Smith

75 Question 16 answer C 175 A 630.32(B) allows for a maximum of 300% of the conductors ampacity T310.15(B16) lists the conductors ampacity as 55A. 3 x 55= 165 A states that if the values does not match a standard size listed in 240.6, then we go up to the next higher value listed which is 175A Copyright 2005 Ted "Smitty" Smith

76 Question 17 Which of the following is NOT one of the approved methods to reduce clearing time for Arc Energy Reduction for a circuit breaker with the highest continuous current trip rating setting is 1200 Amperes. A. An instantaneous trip setting that is less than the available arcing current B. Zone-selective interlocking C. Universal metering adjustment D. Energy-reducing active arc flash mitigation system Copyright 2005 Ted "Smitty" Smith

77 Question 17 answer C. Universal Metering System
This is made up. There is no system with that name in the electrical industry. 240.87(B) Copyright 2005 Ted "Smitty" Smith

78 Question 18 A circuit breaker that is NOT marked with an Interrupting Rating, has an interrupting rating of ____________________ amperes. A A B A C A D A Copyright 2005 Ted "Smitty" Smith

79 Question 18 answer C. 5000 Amperes 240.83(C)
Copyright 2005 Ted "Smitty" Smith

80 Question 19 Fuse holders for current-limiting fuses shall permit insertion of fuses that are not current-limiting if the manufacturer instructions do not prohibit this practice. A. True B. False Copyright 2005 Ted "Smitty" Smith

81 Question 19 answer B. False 240.60(B)
Copyright 2005 Ted "Smitty" Smith

82 Question 20 A three phase, 480V to 208V transformer will have secondary conductors which will be protected from overcurrent by the primary conductor’s overcurrent device. The secondary conductors will be 13 feet in length. The primary conductors are protected by a 50 Ampere inverse time circuit breaker. If nothing else is know, what is the minimum ampacity required for the secondary conductors? A. 50 A B A C A D A Copyright 2005 Ted "Smitty" Smith

83 Question 10 Answer D A 25’ Foot Tap rule for other than industrial locations 240.21(C)(6) The minimum ampacity of the secondary conductos must be the transformer voltage ratio ( 480/208=2.3) multiplied by 1/3 of the primary OCPD rating. (50/3=16.6) 16.6x2.3= A Copyright 2005 Ted "Smitty" Smith