1 N F G C r e v I s I o n s

2 Relocate Pressure limitations
Scope Section 5.5 (B) The maximum operating pressure shall be This code shall apply to natural gas systems operating at a pressure of 125 psi (862 kPa) or less. Exception No. 1: Piping systems for gas-air mixtures within the flammable range are limited to a maximum pressure of 10 psi (69 kPa). Exception No. 2: LP-Gas piping systems are limited to 20 psi (140 kPa), except as provided in (6). (C) This code shall apply to LP-Gas systems operating at a pressure of 50 psi (345 kPa) or less. (D) This code shall apply to gas-air mixture systems operating within the flammable range at a pressure of 10 psi (69 kPa) or less. 5.5 Piping System Operating Pressure Limitations Piping System Operating Pressure Limitations. The maximum operating pressure for any piping system shall not exceed 125 psi Flammable Gas-Air Mixtures. The maximum operating pressure for piping systems for gas-air- mixtures within the flammable range shall be 10 psi (69 kPa) LP-Gas Piping Systems. The maximum operating pressure for LP-Gas piping systems shall be 20 psi (140 kPa), except as provided in (6) Relocate Pressure limitations

3 Update All Reference Standards
… ASTM International Publications. American Society for Testing and Materials International, 100 Barr Harbor Drive, West Conshohocken, PA , , ASTM A53, Standard Specification for Pipe, Steel, Black and Hot- Dipped, Zinc Coated Welded and Seamless, ASTM A106, Standard Specification for Seamless Carbon Steel Pipe for High-Temperature Service, ASTM A254, Standard Specification for Copper-Brazed Steel Tubing, 1997 (Reaffirmed 2007)2012. ASTM A268, Standard Specification for Seamless and Welded Ferritic and Martensitic Stainless Steel Tubing for General Service, [FR No. 94-NFPA 54/Z ] ASTM A269, Standard Specification for Seamless and Welded Austenitic Stainless Steel Tubing for General Service, 2015. Update All Reference Standards

4 Allow Stainless Steel Pipe; Allow minimum Schedule 10 pipe
Steel, Stainless Steel, and Wrought-Iron. Steel, Stainless Steel, and wrought-iron pipe shall be at least of standard weight (Schedule 4010) and shall comply with one of the following dimensional standards of ANSI/ASME B36.10M, Welded and Seamless Wrought Steel Pipe, and one of the following: (1) ANSI/ASME B36.10M, Welded and Seamless Wrought Steel Pipe (21) ASTM A53, Standard Specification for Pipe, Steel, Black and Hot- Dipped, Zinc-Coated Welded and Seamless (32) ASTM A106, Standard Specification for Seamless Carbon Steel Pipe for High-Temperature Service (43) ASTM A312, Standard Specification for Seamless, Welded, and Heavily Cold Worked Austenitic Stainless Steel Pipes. Allow Stainless Steel Pipe; Allow minimum Schedule 10 pipe

5 Add Press-Connect Joints; No Threaded joints for Schedule 10 pipe
* Pipe Joints. Schedule 40 and heavier pipe Pipe joints shall be threaded, flanged, brazed, or welded, or assembled with press-connect fittings listed to ANSI LC 4/CSA 6.32, Press-Connect Metallic Fitting for Use in Fuel Gas Distribution Systems. (A) Pipe lighter than Schedule 40 shall be connected using press- connect fittings, flanges, brazing, or welding. (B) Where nonferrous pipe is brazed, the brazing materials shall have a melting point in excess of 1,000°F (538°C). (C) Brazing alloys shall not contain more than 0.05 percent phosphorus. Add Press-Connect Joints; No Threaded joints for Schedule 10 pipe

6 Allow Stainless Steel Tubing
5.6.3 Metallic Tubing. Seamless copper, aluminum alloy, or steel tubing Tubing shall not be used with gases corrosive to such the tubing material. Stainless Steel. Stainless steel tubing shall comply with one of the following: (1) ASTM A268, Standard Specification for Seamless and Welded Ferritic and Martensitic Stainless Steel Tubing for General Service. (2) ASTM A269, Standard Specification for Seamless and Welded Austenitic Stainless Steel Tubing for General Service. Allow Stainless Steel Tubing

7 Relocate protective coating
Section 5.6.6 Section 7.2.2 7.2.2 Protective Coating. Where piping is in contact with a material or an atmosphere corrosive to the piping system, the piping and fittings shall be coated with a corrosion- resistant material. Any such coating used on piping or components shall not be considered as adding strength to the system. 5.6.6 Protective Coating. Where in contact with material or atmosphere exerting a corrosive action, metallic piping and fittings coated with a corrosion-resistant material shall be used. External or internal coatings or linings used on piping or components shall not be considered as adding strength. Relocate protective coating

8 5. 6. 8. 3 Stainless Steel Tubing Joints
Stainless Steel Tubing Joints. Stainless steel joints shall be welded, assembled with approved tubing fittings, brazed with a material having a melting point in excess of 1,000°F (538°C), or assembled with press-connect fittings listed to ANSI LC 4/CSA 6.32, Press-Connect Metallic Fittings for Use in Fuel Gas Distribution Systems. Brazing alloys and fluxes shall be recommended by the manufacturer for use on stainless steel alloys. Add SS Joining methods

9 Add Polyamide plastic pipe standard
Plastic Polyamide pipe, tubing and fittings, other than polyethylene, shall be identified and conform to the edition of ASTM D2513F2945, Standards Specification for ThermoplasticPolyamide 11 Gas Pressure Pipe Tubing and Fittings. Pipe to be used shall be marked “gas” and “ASTM D2513F2945”. Add Polyamide plastic pipe standard

10 Clarify when pressure regulator is required
5.8.1 Where Required. A line pressure regulator shall be installed where the gas supply pressure is higher than that at which appliances are designed to operate or vary beyond design pressure limits exceeds the maximum allowable inlet pressure of the appliance served Listing. Line pressure regulators shall be listed in accordance with ANSI Z21.80/CSA 6.22, Line Pressure Regulators, where the outlet pressure is set to 2 psi or less Clarify when pressure regulator is required

11 Rename pressure relieving & limiting devices
5.9.3 Overpressure Protection Devices Pressure relieving or pressure limiting Overpressure protection devices shall be one of the following: … The devices in shall be installed either as an integral part of the line pressure regulator or as separate units. Where separate pressure relieving or pressure limiting overpressure protection devices are installed, they shall comply with through Construction and Installation. All pressure relieving or pressure limiting overpressure protection devices shall meet the following requirements: Rename pressure relieving & limiting devices

12 Add 39 EHD to Two NG CSST Tables

13 Deleted same size outlet requirement
7.8 Branch Pipe Connection. When a branch outlet is placed on a main supply line before it is known what size pipe will be connected to it, the outlet shall be of the same size as the line that supplies it. Deleted same size outlet requirement

14 Clarify and delete AHJ Approval
7.10 Prohibited Devices. No device Devices shall not be placed inside within the interior of gas piping or fittings that where such devices will reduce the cross-sectional area or otherwise obstructs the free flow of gas, except where proper allowance in the piping system design has been made for such a devices and where approved by the authority having jurisdiction. Clarify and delete AHJ Approval

15 Clarify grounding electrode bond
* The length of the jumper between the connection to the gas piping system and the grounding electrode system shall not exceed 75 ft (22 m). Any additional grounding electrodes installed to meet this requirement shall be bonded to the electrical service grounding electrode system or where provided, lightning protection grounding electrode system. Clarify grounding electrode bond

16 Add Arc resistant jacketed csst bonding
Arc Resistant Jacketed CSST. CSST listed with an arc resistant jacket or coating system in accordance with ANSI LC 1/CSA 6.26, Fuel Gas Piping Systems Using Corrugated Stainless Steel Tubing (CSST), shall be electrically continuous and bonded to an effective ground fault current path. Where any CSST component of a piping system does not have an arc resistant jacket or coating system, the bonding requirements of shall apply. Arc resistant jacketed CSST shall be considered to be bonded when it is connected to appliances that are connected to the appliance grounding conductor of the circuit that supplies that appliance. Add Arc resistant jacketed csst bonding

17 Revise existing appliance inspections
9.1.24* Existing Appliances. Existing appliance installations shall be inspected to verify compliance with the provisions of Section 9.3 and Chapter 12 where a component of the building envelope is modified as described by one or more of (1) through (6). Where the appliance installation does not comply with Section 9.3 and Chapter 12, the installation shall be altered as necessary to be in compliance with 9.3 and Chapter 12. (1) The building is modified under a weatherization program. (2) A building permit is issued for a building addition or exterior building modification. (3) Three or more window assemblies are replaced. (4) Three or more storm windows re installed over existing windows. (5) One or more exterior door and frame assemblies are replaced. (6) A building air barrier is installed or replaced. Revise existing appliance inspections

18 Add UL Standard Requirement
Exhaust ducts shall be constructed of rigid metallic material. Transition ducts used to connect the dryer to the exhaust duct shall be listed and labeled in accordance with ANSI/UL 2158A, Clothes Dryer Transition Ducts, for that application or and installed in accordance with the clothes dryer manufacturer's installation instructions. Add UL Standard Requirement

19 Delete Floor Mounted Unit Heater
Floor-Mounted-Type Unit Heaters. Floor-mounted-type unit heaters shall comply with the following requirements: (1) A listed unit heater shall be installed with clearances from combustible material at the back and one side only of not less than 6 in. (150 mm). Where the flue gases are vented horizontally, the 6 in. (150 mm) clearance shall be measured from the draft hood or vent instead of the rear wall of the unit heater. A unit heater listed for reduced clearances shall be installed in accordance with the manufacturer’s installation instructions. (2) Floor-mounted-type unit heaters installed on combustible floors shall be listed for such installation. (3) Combustible floors under unlisted floor-mounted unit heaters shall be protected in an approved manner. (4) Clearances for servicing shall be in accordance with the manufacturers’ recommendations contained in the installation instructions. Delete Floor Mounted Unit Heater

20 Add General ducting requirement for all air handling equipment
Locations with Air-Handlers. Where a draft hood equipped water heater is installed in a space containing a furnace or other air-handler, the ducts serving the furnace or air-handler shall comply with Section Add General ducting requirement for all air handling equipment

21 10. 28 Compressed Natural Gas (CNG) Vehicular Fuel Systems
10.28 Compressed Natural Gas (CNG) Vehicular Fuel Systems. The installation of compressed natural gas (CNG) fueling (dispensing) systems shall conform with NFPA 52, Vehicular Fuel Systems Code. Residential CNG fueling appliances shall be listed in accordance with ANSI/CSA NGV 5.1, Residential Fueling Appliances, and installed in accordance to the appliance manufacturer’s installation instructions. Add CSA NGV Standard

22 Mechanical draft systems shall be listed in accordance with UL 378, Draft Equipment, and shall be installed in accordance with both the appliance and the mechanical draft system manufacturer’s installation instructions. Add UL Standard

23 Clarify and Delete Duplicate text
12.3.3* Ventilating Hoods. Ventilating The use of ventilating hoods and exhaust systems to vent appliances shall be permitted to be used to vent appliances limited to industrial appliances and appliances installed in commercial applications and to vent industrial appliances, particularly where the process itself requires fume disposal. Ventilating hoods and exhaust systems shall be permitted to be used to vent appliances installed in commercial applications. Clarify and Delete Duplicate text

24 Plastic Piping. Where plastic piping is used to vent an appliance, the appliance shall be listed for use with such venting materials and the appliance manufacturer’s installation instructions shall identify the specific plastic piping material. The plastic pipe venting materials shall be labeled in accordance with the product standards specified by the appliance manufacturer or shall be listed and labeled in accordance with ANSI/UL 1738, Venting Systems for Gas-Burning Appliances, Categories II, III, and IV Plastic Vent Joints. Plastic pipe and fittings used to vent appliances shall be installed in accordance with the appliance manufacturer's installation instructions. Plastic pipe venting materials listed and labeled in accordance with ANSI/UL 1738, Venting Systems for Gas-Burning Appliances, Categories II, III, and IV, shall be installed in accordance with the vent manufacturer’s installation instructions. Where primer is required, it shall be of a contrasting color. Add UL 1738 Standard

25 Special Gas Vent. Special gas vent shall be listed and labeled in accordance with ANSI/UL 1738, Venting Systems for Gas-Burning Appliances, Categories II, III, and IV, and installed in accordance with the special gas vent manufacturer’s installation instructions. Add UL 1738 Standard

26 Factory-built chimneys shall be listed in accordance with ANSI/UL 103, Chimneys, Factory-Built, Residential Type and Building Heating Appliances, ANSI/UL 959, Medium Heat Appliance Factory-Built Chimneys, or ANSI/UL 2561, Degree Fahrenheit Factory-Built Chimneys. Factory-built chimneys shall be installed in accordance with the manufacturer’s installation instructions. Factory-built chimneys used to vent appliances that operate at positive vent pressure shall be listed for such application. Add UL Standards

27 * Masonry chimneys shall be built and installed in accordance with NFPA 211, Standard for Chimneys, Fireplaces, Vents, and Solid Fuel-Burning Appliances, and lined with one of the following: (1) Aapproved clay flue lining, (2) Aa listed chimney lining system listed and labeled in accordance with ANSI/UL 1777, Chimney Liners, (3) or Oother approved material that will resist corrosion, erosion, softening, or cracking from vent gases at temperatures up to 1800°F (982°C). Add UL Standard

28 Add installation shield requirements
Installation Shield. Where a factory-built chimney passes through insulated assemblies, an insulation shield constructed of steel having a minimum thickness of inch ( mm) (nominal 26 gage) shall be installed to provide clearance between the chimney and the insulation material. The clearance shall not be less than the clearance to combustibles specified by the chimney manufacturer’s installation instructions. Where chimneys pass through attic space, the shield shall terminate not less than 2 inches (51 mm) above the installation materials and shall be secured in place to prevent displacement. Insulation shields provided as part of a listed chimney system shall be installed in accordance with the manufacturer’s installation instructions. Add installation shield requirements

29 12.7 Gas Vents Materials. Type B and Type BW gas vents shall be listed in accordance with ANSI/UL 441, Gas Vents. Vents for listed combination gas- and oil-burning appliances shall be listed in accordance with ANSI/UL 641, Type L Low Temperature Venting Systems. Add ul standards

30 Add Table instead of text
The vent terminal of a direct-vent appliance with an input of 10,000 Btu/hr (3 kW) or less shall be located at least 6 in. (150 mm) from any air opening into a building, and such an appliance with an input over 10,000 Btu/hr (3 kW) but not over 50,000 Btu/hr (14.7 kW) shall be installed with a 9 in. (230 mm) vent termination clearance, and an appliance with an input over 50,000 Btu/hr (14.7 kW) shall be at least a 12 in. (300 mm) vent termination clearance. The clearances for through-the-wall direct vent terminals shall be in accordance with Table The bottom of the vent terminal and the air intake shall be located at least not less than 12 in. (300 mm) above finished ground level. Add Table instead of text

31 Add new requirement over 150,000 Btu