FEEDER PROTECTION UNIT
FPU-16 FEEDER PROTECTION UNIT
2
THE FPU-16 FEEDER PROTECTION UNIT
The FPU-16 is a microprocessor-based feeder protection unit with programmable trip-and-alarm set points for phase protection, ground-fault protection, and current unbalance. Features of the FPU-16 include an operation counter, front-panel programming, independent trip-and-alarm relays, and an isolated analog output.
3
FPU-16 FEEDER PROTECTION UNIT
Compact design-1/4 DIN size Temperature rating of -40°C to 60°C Panel or surface mount Supply voltage range of 85 to 135 Vac Program-change lockout
4
FPU-16 FEEDER PROTECTION UNIT
Separate trip and alarm contacts - Fused - Form “C” - Fail-safe or non-fail- safe operation Plug-in terminal blocks
5
WHAT PROTECTION DOES AN FPU-16 OFFER?
THERMAL OVERLOAD SHORT-TIME OVERCURRENT INSTANTANEOUS OVERCURRENT CURRENT UNBALANCE EARTH-FAULT RAMP MODE RESET ENTER SET POINT MOD STATUS MODES FPU-16 FEEDER PROTECTION UNIT
6
OPTIONAL ELECTROLUMINESCENT BACKLIT DISPLAY
FPU-16 FACE PLATE LIQUID CRYSTAL DISPLAY MODE digit identifies mode VALUE digits Display set points, trip and alarm codes, and meter readings TRIP/ALARM, Red LED On: Trip or alarm Flashing: Program-change lockout defeated PROCESSOR, Green LED Indicator On: Processor functional OPTIONAL ELECTROLUMINESCENT BACKLIT DISPLAY MODE LIST MEMBRANE SWITCH KEYPAD RAMP switch Adjusts value digits ENTER switch Enters values, accesses alarm set points and values at trip MODE switch Selects modes “0” through “F” RESET switch Resets trips and alarms
7
FPU-16 BACK PLATE - + 13 14 15 16 A B C O M 17 18 19 20 P E 21 22 23
24 F - + CNTR ICT SHIELD 12 11 10 9 8 7 6 5 4 3 2 1 L1 L2 F2 8A F1 ANALOG NC I 26 25 RS 485 TRIP ALARM L1 and L2 - are for control power. Units can be ordered with optional 120 Vac or 240 Vac and 50 or 60 Hz. There is also an optional DC power supply. are the form “C” trip relay. It is 10 A rated and fused at 8 A. Relays can be configured to operate in the fail-safe or non-fail-safe mode. 8 - System ground 9 - Key Pin. High voltage lower block cannot be plugged into low voltage upper terminals. Form “C” alarm relay. isolated analog output or RS-485. Input for Earth-fault CT. Program enable. These pins must be connected to allow program changes. Input for RTD or Thermistor. ICT-2 Interface CT input. ICT-2 shown on the next slide.
8
ICT-2 INTERFACE CT Provides mounting flexibility Mounting ICT-2 close
to CT’s provides: - Less signal loss Eliminates open CT hazard
9
FPU-16 TYPICAL APPLICATION
EARTH-FAULT CT PHASE CT'S SUPPLY LOAD 12 11 10 9 8 1 5 S R 7 6 4 3 2 ICT-2 13 14 15 16 A B C O M E F 18 19 17 Y X 20 21 22 23 24 25 26 27 MPU PHASE C CT PHASE A CT PHASE B CT EARTH FAULT ANALOG OR RS-485 OUTPUT 13 14 15 16 17 18 19 20 21 22 23 24 A B C C N C P E - + M O C E CNTR ANALOG/RS-485 OUTPUT F ICT SHIELD FPU-16 ALARM TRIP F2 N F1 L2 L1 C 12 11 10 9 8 7 6 5 4 3 2 1 N L TO TRIP COIL OR LOCKOUT RELAY ALARM A
10
I2t THERMAL PROTECTION CURVE
10000 8000 PERCENT I2t 6000 DYNAMIC LIMIT 5000 100 4000 3000 PERCENT I2 t 2000 50 1000 800 600 500 0.5 1.0 400 MULTIPLES OF RATED CURRENT 300 200 CLASS 20 SECONDS 100 80 60 50 40 30 CLASS RANGE 1 s TO 45 s AT 600% 0% I2t 20 25% I2t 50% I2t 10 8 6 5 4 75% I2t 3 2 1 1 2 3 4 5 6 7 8 9 10 11 12 MULTIPLES OF RATED CURRENT
11
SHORT-TIME OVERCURRENT SETTINGS
MAXIMUM 9x PHASE CT PRIMARY RATING FEEDER CURRENT TRIP SET POINT TRIP TIME = 3, 6, 12, OR 24 CYCLES ALARM SET POINT ALARM TIME = 3, 6, 12, OR 24 CYCLES 1x PHASE CT PRIMARY RATING MINIMUM
12
INSTANTANEOUS OVERCURRENT SET-POINT RANGE
MAXIMUM 9x PHASE CT PRIMARY RATING TRIP SET POINT TRIP TIME =0.25 TO 3 CYCLES FEEDER CURRENT ALARM SET POINT ALARM TIME = 0.25 TO 3 CYCLES 1x PHASE CT PRIMARY RATING MINIMUM
13
CURRENT UNBALANCE SET-POINT RANGE
75% MAXIMUM PERCENT CURRENT UNBALANCE TRIP SET POINT TRIP TIME =5 SECONDS ALARM SET POINT ALARM TIME = 1 SECOND 5% MINIMUM
14
EARTH-FAULT CURRENT SET-POINT RANGE
100% of CT-primary rating MAXIMUM EARTH-FAULT CURRENT TRIP SET POINT TRIP TIME=3, 6, 12, OR 24 CYCLES ALARM SET POINT ALARM TIME = 12 CYCLES 1% of CT-primary rating MINIMUM
15
FPU-16 SETUP MODES MODE 6: EARTH-FAULT-CT-PRIMARY RATING (Ie)
Range: 5 A to 2000 A MODE 7: PHASE-CT-PRIMARY RATING (Ip) Range: 20 A to 1200 A MODE 8: RATED CURRENT (In) Range: 9 A to 800 A
16
MODE 5-PROGRAMMABLE OPTIONS
SHORT-CIRCUIT TRIP TIME: 3, 6, 12, or 24 cycles EARTH-FAULT TRIP TIME: 3, 6, 12, or 24 cycles I2t IMMEDIATE RESET: on / off ALARM LATCH: on / off AUTORESET (MODE 0): on / off RELAY OPERATING MODE: TRIP RELAY: fail safe / non fail safe ALARM RELAY: fail safe / non fail safe ANALOG OUTPUT PARAMETER: current, I2t, earth leakage
17
METERING MODES MODES A, b, AND C: AMMETERS
<ENTER> displays pre-trip value MODE d: PERCENT I2t, TIME-TO-RESET, EMERGENCY THERMAL RESET MODE 9: PERCENT UNBALANCE <ENTER> displays pre-trip value MODE E: EARTH LEAKAGE <ENTER> displays pre-trip value MODE F: OPERATION COUNTER
18
OPTIONS AVAILABLE FOR THE FPU-16
MOUNTING: Panel or surface POWER SUPPLY: AC: 120 Vac, 240 Vac, or 120/240 Vac switch selectable DC: 12 Vdc, 24 Vdc, or 48 Vdc FREQUENCY: 50 or 60 Hz SIGNAL OUTPUT CONFIGURATION: ANALOG: 4-20 mA, 0-5 Vdc, 0-10 Vdc COMMUNICATIONS: RS-485 A-B or Modicon protocols (data logging available) DUAL OUTPUT: Analog and RS-485 available ELECTROLUMINESCENT BACKLIT DISPLAY REMOTE-KEYPAD INPUT
19
RS-232 TO RS-485 CONVERTER (485CSP2)
FPU-16 COMMUNICATIONS 23 24 RAMP MODE RESET ENTER FEEDER PROTECTION UNIT SET POINT MODES STATUS MODES STARTCO FPU-16 SE-485 T(A) T(B) R(A) R(B) SE-TA485 FR. GND TD(B) TD(A) RD(A) RD(B) +12VDC GND WHT BLK RTS SD ON OFF CONTROL ECHO TD ENABLE RD RS-232 TO RS-485 CONVERTER (485CSP2) RS-485 RS-232 DC POWER SUPPLY SHIELD 23 24 FEEDER PROTECTION UNIT 1 TO 63 FPU-16’s or MPU-16A’s SET POINT MODES STATUS MODES RAMP MODE RESET ENTER STARTCO FPU-16 23 24 FEEDER PROTECTION UNIT SE-485 SET POINT MODES STATUS MODES RAMP MODE RESET ENTER STARTCO FPU-16 23 24 FEEDER PROTECTION UNIT SE-TA485 SET POINT MODES STATUS MODES RS 232 RAMP MODE RESET ENTER STARTCO FPU-16