Maintenance masterdrive siemens
2
Equipment and materials
Scoop fluke Testbox siemens multimeter fluke screwdrivers torque wrench 0-10 Nm torque wrench Nm socket spanner/wrench small and big brakleen fine steel wool 2X grease filter cloths cleaning duds rubber pads tyraps powersupply bridge plug
3
Safety instruction before maintenance
4
Safety instruction before maintenance
Push the emergency stop Turn off all three main switches on the AFE to zero and turn off the UPS in AFE Check DC voltage on the DC bus. How: push ‘P’ (parameter) on display push arrow ‘up’ till you see r 006 push again ‘P’ the number on screen = voltage on DC bus. this has to be under 12V
5
Safety instruction before maintenance
Remove plastic cover of the DC fuses Measure DC voltage on DC fuses
6
Disassemble of the drive
Remove main fan of drive Disconnect the power plug of the main fan Remove the fan (caution: very heavy!)
7
Disassemble of the drive
Remove the three capacitors banks Disconnect the power plug of all capacitor banks Number each bank Remove the 4 bolts that keep the bank in place
8
Disassemble of the drive
Remove the capacitor bank from drive Turn the bank 90 deg to the right Lift the bank up Pull the bank out its pivot point Place it on the ground 2. 1. 3.
9
Removing master drive circuit boards
Removing the connections First take out the connector –X9 out. This to make sure there is no power on panel Remove the display panel and unplug it from the print board
10
Removing master drive circuit boards
Remove al the connectors on all 3 pcb’s Make sure that you remember where to put them back
11
Removing master drive circuit boards
By-pass the safety relay Remove the X533 connector Put the bridge plug on the X533 connector
12
Removing master drive circuit boards
Remove the pcb’s Remove the 6 screws Take out all 3 boards without touching the printed circuit Place the boards on an isolated table or plate Make sure that you know the right position of each board
13
Cleaning the masterdrive
Main fan With the use of brakleen you clean the entire fan Open the front cover and clean the inside of the cover Check for loose connections and burn marks
14
Cleaning the masterdrive
Cleaning the capacitor banks Clean all dust and dirt from the capacitor with brakleen Remove the old grease on the copperplates Cleaning of copperplates with fine steel wool
15
Cleaning the masterdrive
Check all the screws with a torque wrench at 8 Nm Cleaning the inside of the masterdrive Remove al the dust and dirt on the IGBT boards Clean the isolation panel Remove the old crease between the copper slidingplates
16
Cleaning the masterdrive
If everything is clean you check the bolts on IGBT boards at 9Nm Check the bolts (M8) on the copper plates at 12Nm and the bolts (M10) at 18Nm
17
Cleaning the masterdrive
Check the connection bolts (M12) on the copper plates at 70Nm Check if there are rubber pads between the wires and metal guiders
18
Cleaning the masterdrive
substitute the filter cloths by new ones Clean the outer side of the electrical cabinet
19
Checking for loose contacts
20
Testing of the masterdrive
placing the parts necessary for testing place the mainfan and connect the powerplug Mount the capacity banks in the corresponding slot (don’t shut them) Put grease (SGB 2X contact treatment) on the copper bars. Not on the isolation material
21
Testing of the masterdrive
testbox Place now the test board on the most left side Connect the testbox on the test board Reconnect the plug on the –X09 connection
22
Testing of the masterdrive
Powersupply Connect the + and – wires on the DC-bus Short circuit the copper connection bars of the motor with a wire Adjust the powersupply up to 24V DC and max 2A current
23
Testing of the masterdrive
Testing with testbox Check if all leds light up Measure the voltage on the testbox with a scoop 5V 4.9 and 5.3V (-)15V and 15.75V 24V 20 and 27V
24
Testing of the masterdrive
Testing the IGBT,s Pull the first switch up when the led lights up it means that the testbox receives the feedback from the IGBT Pull the third switch down and check if the lower led lights up Check the power supply if the voltage drops down and the current rise
25
Testing of the masterdrive
Put all switches in neutral position ‘0’ Check if power supply is at 24 volts Now do the same for all combination: 1 2 3 ok up down
26
Testing of the masterdrive
Testing the current coils of masterdrive Measure with scoop between ground and IRN / ISN / ITN Measurement has to be between -50mV and +50mV
27
Testing of the masterdrive
Measure the temperature probe of radiator box Connect the scoop between ground and TWRN Measuring of the voltage should be between 4.53V and 5.29V at ambient temperature of 20dgr
28
Testing of the masterdrive
Measuring the differential DC voltage Turn of the power supply on the DC bus DC bus must be approximately 0 Volt Measure with scoop between ground and UZKN Voltage should be between - 50mV and +50mV
29
Testing of the masterdrive
Testing the main contactor and contactor of fan Turn on the main contactor switch and listen if fan works normal Turn on the pre-load contactor and listen if the contactor is activated If test is ok bring both switches to zero position
30
Testing of the masterdrive
Ending the testing fase Turn of the powersupply and remove all testing equipment of the masterdrive
31
Testing of the masterdrive
Disconnect the plug from –X9 to make sure there is no voltage present on the drive Remove the testbox and connection board
32
Assembly of the masterdrive
Remove brigeplug from X533 connector Plug back the correct plug in to X533 connector Place back the boards in the right order
33
Assembly of the masterdrive
Reconnector all the connector on the electronic boards if it’s a master slave configuration please check the fiber optic link
34
Assembly of the masterdrive
Close the 3 capacitor banks of the masterdrive fasten the bolds of the banks (12 pieces)
35
Assembly of the masterdrive
Reconnect the plugs of capacitor banks Reconnect the display panel Place all plastic covers on there original position Connect the powerplug on the –X9
36
Updating drivemonitor
Accessing the drive Open the S7 simatic manager Go to the right masterdrive. For example: ‘h1inv/masterdrives’ Right click ‘PLC/drive/parameterization’ Click ‘ok’ when warnings shown Open ‘direct to parameter list’
37
Updating drivemonitor
Cleaning the history faults Double click on ‘P952’ Change the value in the right side to ‘0’ and press ‘OK’ Repeat step 1 till 4 of page 36
38
Updating drivemonitor
Uploading parameters from the drive Open ‘save drive parameters to a file’ make sure ‘basic device complete…’ is the only one who is active Press OK
39
Updating drivemonitor
choose an object name according to the drive If file name allready exists,overwrite it Check if upload starts
40
Updating drivemonitor
Wait a few minutes till it is uploaded When done press ‘OK’ and close ‘DriveMon’
41
Testing the quay crane Put the power back on Undo the emergency stop
Turn the UPS back on of all 3 AFE’s Put the switch of the AFE back on
42
Testing the quay crane Resetting Push the ‘fault reset’ button
check fault list all faults that prevent starting the crane are reset
43
Testing the quay crane starting up crane Push the ‘control on’ button
check if crane is on Check if there are fault generated