Download presentation
Presentation is loading. Please wait.
1
Energy Code Program Manager – SPEER
Third Party Energy Inspections & Overview of a Third Party Inspection Program CATEE Jason Vandever Energy Code Program Manager – SPEER
2
SPEER REEO – Regional Energy Efficiency Organization
Member-based, non-profit 501(c)3 organization 50+ members from wide cross section of E.E. industries
3
Approved Inspection Agencies
104.4 Approved inspection agencies. The code official is authorized to accept reports of third-party inspection agencies not affiliated with the building design or construction, provided such agencies are approved as to qualifications and reliability relevant to the building components and systems they are inspecting. Remember state law requires ICC Certifications Applies to duct and envelope testing
4
3rd Party Energy Services
Plan Review Inspections Testing Commissioning
5
Registering Contractors
Insulation contractors – standard contractor registration form 3rd party inspectors 3rd party testers FORMS?
6
Approved?
7
Approved?
8
Approved?
9
Examination of documents.
The code official shall examine or cause to be examined… OR the code official is authorized to utilize a registered design professional, or other approved entity…
10
C103.2 Information on Construction Documents
Details shall include, but are not limited to, the following as applicable: 1. Insulation materials and their R-values. 2. Fenestration U-factors and solar heat gain coefficients (SHGCs). 3. Area-weighted U-factor and solar heat gain coefficient (SHGC) calculations. 4. Mechanical system design criteria. 5. Mechanical and service water heating system and equipment types, sizes and efficiencies. 6. Economizer description. 7. Equipment and system controls. 8. Fan motor horsepower (hp) and controls. 9. Duct sealing, duct and pipe insulation and location. 10. Lighting fixture schedule with wattage and control narrative. 11. Location of daylight zones on floor plans. & 12. Air sealing details.
11
Required Inspections Footings and foundation
Framing and Plumbing, mechanical & electrical rough in Final - …(for commercial) - verifying activities associated with required building commissioning…
12
Quality Control Seal boots to drywall or other finished surface
13
Quality Control R403.5.3 Hot water piping Insulation
Minimum R-3 shall be applied: Pipes ¾” diameter or larger Serving more than 1 unit Located outside conditioned space From water heater to manifold Located under floor slab Buried in piping
14
Quality Control Cut and split insulation around blocking, plumbing, HVAC and electrical components. This is an animated slide. Please be sure to note the order of the animation. Narrative: The batt on the left was incorrectly run behind the wire instead of being split around the wire. Animate red text box and arrows. As a result the batt is compressed and will not be touching the drywall. The batt on the right is how a batt should be installed around wiring. Animate green text box and arrows. They carefully split the batt from the bottom, and place one half at the back of the cavity – behind the wiring – and they can then lay the other half down and over the wire. Point of Slide: Cut and split insulation around blocking, plumbing, HVAC and electrical components as required by IECC Tables and Compression Behind Wiring Batt split around wiring
15
Lighting Equipment (MANDATORY)
Quality Control 2009 IECC 404.1 2012/15 IECC R404.1 Lighting Equipment (MANDATORY) A minimum of 50 percent of the lamps in permanently installed lighting fixtures shall be high-efficacy lamps A minimum of 75 percent of the lamps in permanently installed lighting fixtures shall be high-efficacy lamps or a minimum of 75 percent of the permanently installed lighting fixtures shall contain only high-efficacy lamps. This is not hard, mostly a matter of specifying the right bulbs or fixtures. There have been issues with dimming, but the current generation of lamps is much better than just two years ago. I’m all for helping the builder comply and a little wrinkle here can certainly help. 60 lumens per watt for lamps over 40 watts 50 lumens per watt for lamps over 15 up to 40 watts 40 lumens per watt for lamps 15 watts or less Best halogen I could find was 24 lumens per watt for a 40 watt bulb
16
Quality Control Required: ACCA Manual J & Manual S & Manual D or other approved method
19
Third Party Inspections – Trade offs
Pros Can rapidly increase the enforcement of energy code compliance and reduce workload for the city staff Potential for shortening wait times for builders Can add emphasis on the energy code that may not be a priority to city code inspectors Ask the audience for more
20
Third Party Inspections – Trade offs
Cons Oversight can be time consuming; checks and balances can deplete code officials’ resources Trust Potential construction cost increases Inherent conflict of interest potential Lack of control Ask the audience for more
21
Key items to keep in mind when creating a third party program:
Procedure Qualifications Documentation
22
108.1 Authority Where the code official finds any work
regulated by this code being performed in a manner either contrary to the provisions of this code or dangerous or unsafe, the code official is authorized to issue a stop work order.
23
Energy Code Program Manager – SPEER
Thank you! Questions? Jason Vandever Energy Code Program Manager – SPEER
Similar presentations
© 2025 SlidePlayer.com. Inc.
All rights reserved.