Objectives Finish with Exchangers - Start Air Distribution Systems
- Diffuser selection
2
Fin Efficiency Assume entire fin is at fin base temperature
Maximum possible heat transfer Perfect fin Efficiency is ratio of actual heat transfer to perfect case Non-dimensional parameter
5
Heat Transfer From the pipe and fins we will find t tP,o tF,m
6
Resistance model Q = U0A0Δtm
Often neglect conduction through tube walls Often add fouling coefficients
7
Heat exchanger performance (Book section 11.3)
NTU – absolute sizing (# of transfer units) ε – relative sizing (effectiveness) Criteria NTU ε P RP cr
9
Summary Calculate efficiency of extended surface
Add thermal resistances in series If you know temperatures Calculate R and P to get F, ε, NTU Might be iterative If you know ε, NTU Calculate R,P and get F, temps
10
Example Heat Exchangers Sensible and Enthalpy Wheels
11
Air Distribution System Design
Describe room distribution basics Select diffusers Supply and return duct sizing
12
Designing Room Airflow
Very complex problem Pumped flow, buoyant flow (or mixed flow) What non-dimensional parameters govern each regime? Archimedes number = Ar = gβLΔT/v2 L = characteristic length (m, ft) g = acceleration due to gravity (m/s2, ft/min2) T = absolute temperature (K, °R) β = 1/T (1/K, 1/ °R) v = kinematic viscosity (m2/s, ft2/min)
13
Computational Fluid Dynamics
14
CFD in Air Distribution Design
Contaminant concentration in a kitchen
15
Buoyancy driven flow: Example of airflow in a stairway
Heater (radiator)
16
Forced driven air flow Diffusers
Grill (side wall) diffusers Linear diffusers Vertical Horizontal one side
17
Diffusers types Valve diffuser swirl diffusers ceiling diffuser
wall or ceiling floor
18
Low mixing Diffusers Displacement ventilation
21
18.7
22
Diffuser Selection Procedure
Select and locate diffusers, divide airflow amongst diffusers V = maximum volumetric flow rate (m3/s, ft3/min) Qtot = total design load (W, BTU/hr) Qsen = sensible design load (W, BTU/hr) ρ = air density (kg/m3, lbm/ft3) Δt = temperature difference between supply and return air (°C, °F) Δh = enthalpy difference between supply and return air (J/kg, BTU/lbm)
23
Find Characteristic Length (L)
24
Indicator of Air Distribution Quality
ADPI = air distribution performance index Fraction of locations that meet criteria: -3 °F < EDT < 2 °F or -1.5 °C < EDT < 1 °C Where, EDT = effective draft temperature Function of V and Δt (Eqn 18.1) EDT=(tlocal-taverage)-M(Vlocal-Vaverage) , M=7 °C/(m/s) ADPI considers ONLY thermal comfort (not IAQ)
25
Ideal and Reasonable Throws
26
Select Register Pick throw, volumetric flow from register catalog
Check noise, pressure drop
27
Summary of Diffuser Design Procedure
Find Q sensible total for the space Select type and number of diffusers Find V for each diffuser Find characteristic length Select the diffuser from the manufacturer data
28
Example 18.3 Qtot = 38.4 kBTU/hr Δh = 9.5 BTU/lbma
Note omission in text
29
Reading asignement Chapter 18 (including 18.2)