1 Drip System Design for a Difficult Site
by David Morgan

2 Design Parameters 3 Bedroom 2 bath home Soil loading rate
450 gallons, 150 g/d/bedroom Soil loading rate 0.2 g/d/ft2, from soil report Depth to seasonal high water table 20 inches, from soil report Depth to restrictive horizon 36 inches, from soil report Slope 2 to 4%, from site evaluation

3 Preliminary Design 2250 ft2 required 1125 linear feet drip tube
450 g/d ÷ .2 g/d/ft2 1125 linear feet drip tube 2250 ft2 ÷ 2 ft drip tube spacing 3 laterals 1125 lft req ÷ 400 ft (available area) = 2.8 10 g/m Operating flow 1200 lf ÷ 2 ft dripper spacing X 1 g/h ÷ 60 m/h 14.5 g/m Flushing flow 3 lines X 1.48 g/m(2 ft/sec) + 10 g/m operating 48 minutes maximum run time per day {[(2 ft X 2 ft) X .2 g/d/ft2] ÷ 1 g/h} X 60 m/h 45 minutes Actual run time per day 450 g/d ÷ 10 g/m (dosing rate)

4 Preliminary Design

5 Preliminary Design 33 psi operating loss on drip tube
93 psi flushing loss on drip tube WE MUST REDESIGN

6 Modified Design

7 Modified Design 4 psi operating loss on drip tube
24 psi flushing loss on drip tube NOW THAT WILL WORK

8 Modified Design for Quicker Pressurization

9 Typical Control Valve How well do they drain? 24VAC NC Diaphragm
Lower Body Diaphragm Diaphragm Spring, 2 psi Upper Body Flow Control Knob Solenoid Manual Override

10 Questions or do you want to head down the road?
Thank You Questions or do you want to head down the road?