Download presentation
Presentation is loading. Please wait.
Published byMuriel Sparks Modified over 6 years ago
1
Distribution Feeder Voltage Regulation and Control
W. H. Kersting Milsoft Utility Solutions
2
Purpose of This Paper Present ANSI Voltage Standards
Present Step Voltage Regulator What it is Control Settings Model IEEE 13 Node Test Feeder Steps in regulating voltage on the test feeder
3
The ANSI Voltage Standards
Range A Nominal Utilization Voltage = 115 volts Maximum Utilization Voltage = 126 volts Minimum Service Voltage = 114 volts Minimum Utilization Voltage = 110 volts Range B Maximum Utilization Voltage = 127 volts Minimum Service Voltage = 110 volts Minimum Utilization Voltage = 107 volts
4
ANSI Range A Critical Voltages
5
Voltage Drop Assumptions
1 Volt drop on the service drop 2 Volt drop on the secondary 3 Volt drop through the transformer Minimum Voltage at the Transformer Primary Terminals will be 120 volts
6
Voltage Profiles
7
Step Voltage Regulator
8
Type B Step Voltage Regulator
9
The Step-Voltage Regulator Model
10
Three Phase Voltage Regulator Model
11
Model Matrix
12
Compensator Circuit
13
Control Panel
14
Control Circuit
15
Regulator Control Settings
Voltage Level – voltage to hold at the regulation point R and X setting (volts) – Equivalent impedance from the regulator to the regulation point Time Delay – time after a tap change required before the tap is changed Bandwidth – allowed deviation from the set voltage level
16
Compensator Impedance
17
Equivalent Line Impedance
18
Bandwidth
19
IEEE 13 Node Test Feeder (Modified)
20
Modifications Line 4-12 changed to phases B-C Transformer 6-7 changed to Ungrounded Wye – Delta Load at Node 7 converted to Delta-PQ Load at Node 8 converted to Delta-PQ Load at Node 14 changed to phase B with constant Z load Load added at Node 5: j145.3 kVA
21
Step 1 Select regulation point to be Node 4
Run power-flow with source set to 126 volts Display Voltage Profile Compute compensator impedance
22
Step 1 Voltage Profile
23
Voltages and Currents from Power-Flow Run
24
Compensator R and X Settting
25
Full Load with Regs, no Caps
26
Observations Regulator taps Concern about high voltage at Node 2
Phase a: 11 Phase b: 12 Phase c: 15 Concern about high voltage at Node 2 Need to add shunt capacitors
27
Shunt Capacitors Source reactive power Install shunt capacitors
Phase A: 765 kvar Phase B: 809 kvar Phase C; kvar Install shunt capacitors Node 3: kvar per phases a,b,c Node 4: kvar per phases a,b,c Node 13: 150 kvar on phase c
28
Full Load with Regs and Caps
29
Observations Regulator taps Notice good voltage balance
Phase a: 5 Phase b: 6 Phase c: 7 Notice good voltage balance All voltages between 120 and 122 volts at Node 4
30
50% Load with all Capacitors
31
50% Load with 900 kvar at Node 4 switched off
32
10% Load Growth with original caps
33
10% Load Growth 100 kvar per phase added at node 4
34
Questions?
Similar presentations
© 2024 SlidePlayer.com. Inc.
All rights reserved.