EARTH-LEAKAGE AND GROUND-INTEGRITY MONITOR
SE-525 EARTH-LEAKAGE AND GROUND-INTEGRITY MONITOR
2
WHY MONITOR THE GROUND INTEGRITY?
PORTABLE EQUIPMENT + V- LOW GROUND RESISTANCE = LOW VOLTAGE BETWEEN EQUIPMENT AND GROUND DURING A FAULT FAULT CURRENT GROUND CONDUCTOR PORTABLE EQUIPMENT BROKEN GROUND CONDUCTOR FAULT CURRENT HIGH GROUND RESISTANCE = HAZARDOUS VOLTAGE BETWEEN EQUIPMENT AND GROUND DURING A FAULT + V-
3
EARTH-LEAKAGE AND GROUND-INTEGRITY MONITOR
The SE-525 is a microprocessor-based earth-leakage and ground-integrity monitor for welding applications. The SE-525 will detect one ohm of ground resistance and as low as 10 mA of ground-fault current.
4
SE-525 FEATURES LED and fluorescent-flag trip indication for both earth-fault and ground-integrity fault. Autoreset or Latching trips. Local and remote reset. Form C Trip relay. Two form C Indication relays. 4-20 mA analog output. Harmonic filtering (DFT) CT verification. Earth-fault test using CT-primary injection. One-ohm ground integrity test. Conformal coating for corrosion resistance.
5
GROUND-INTEGRITY TRIP
SE-525 0PERATION POWER INDICATION GROUND-INTEGRITY TRIP TRIP RELAY ENERGIZED EARTH-LEAKAGE TRIP RESET 10 150 GF LEVEL (mA) 30 400 GF TIME (ms) FIXED FREQENCY NON-FAIL-SAFE CT VERIFY ON AUTO RESET VARIABLE FREQ. CT VERIFY OFF FAIL-SAFE LATCHING
6
SE-525 TYPICAL APPLICATION
SPOT WELDER GROUND CONDUCTOR GROUND INTEGRITY TEST SENSE LEAD M SE-CS30-X GROUND FAULT TEST REMOTE RESET SPOT 1 Ω GROUND TEST Alternate two-wire ground integrity connection used when the resistance of the sense lead is in the one-ohm range. 4-20 mA OUTPUT GROUND-FAULT INDICATION RELAYS N.O. & N.C. GROUND INTEGRITY INDICATION RELAYS N.O. & N.C. L1 120 VAC N M
7
SE-525 TYPICAL APPLICATION
GROUND FAULT POWER GROUND INTEGRITY RESET TO WELDER