1 Lightning and Surge Protection according to EN 50539 standard
DEHN + SÖHNE Lightning and Surge Protection according to EN standard VAL general short SEMINAR JAN 2016

2

3 DEHN + SÖHNE DEHN PROTECTS
VAL general short SEMINAR JAN 2016

4 REASON OF SEASONS GOD SUN CREATES SEASONS , SUNSHINE , CLOUDS , RAIN , WIND , STORMS AND THUNDERSTORMS….. (SOURCE - ADITYAHRIDYA SROTRAM) A SOLAR PLANT HAS TO WITHSTAND ALL THE SEASONS IN EXPECTED LIFE TIME AND STILL SHOW THE DESIRED OUTPUT.

5 SEASONS GOD SUN CREATES SEASONS , SUNSHINE , COULDS, RAIN , STORMS AND THUNDERSTORMS….. (SOURCE - ADITYAHRIDYA SROTRAM) ROI IS CALCULATED BASED UPON AN EXPECTED DEGRDATAION BUT DISASTERS ARE NOT COUNTED FOR— PROTECTION AGAINST RISKS OF NATURAL DISASTERS IS REQUIRED.

6 We are world leaders in the field of : Lightning protection
DEHN History DEHN + SÖHNE is an innovative, globally operating family-owned company with more than 100 years of experience and tradition. We are world leaders in the field of : Lightning protection Surge Protection Human Safety

7 VAL general short SEMINAR JAN 2016
KULLU MANALI VAL general short SEMINAR JAN 2016

8 VAL general short SEMINAR JAN 2016

9 VAL general short SEMINAR JAN 2016

10 VAL general short SEMINAR JAN 2016

11 VAL general short SEMINAR JAN 2016

12 Bijlee Mahadev @ 2480 m from sea level

13 VAL general short SEMINAR JAN 2016

14 VAL general short SEMINAR JAN 2016
Lightning current damage to a meter distribution cabinet: Destroyed main circuit breaker and RCCB detail A detail A detail B detail B VAL general short SEMINAR JAN 2016 / 6410_E_1

15 Surge damage Destroyed electronic component
VAL general short SEMINAR JAN 2016 / 6431_E_1

16 Why is lightning protection essential ?
Required by Indian and international lightning protection standard (IS/ IEC x including risk assessment) FOR HUMAN SAFETY AND PROTECTION OF EQUIPMENT/SERVICES Disastrous damages in the past in several areas in the world NATIONAL BUILDING CODE – NBC 2016 Requirement by Indian BIS standards and also in National Electrical Code VAL general short SEMINAR JAN 2016

17 Basics: Comparison of test currents inside the building
Photovoltaik Seminar - Überspannungsschutz 2 8/20 5 0,1 0.4 ·103 IEC 1 100 kA Wave form µs i max. kA Q As W/R J/ Standard 10/350 100 50 2.5 ·106 IEC I (kA) 80 kA 60 kA 50 kA 40 kA 1 20 kA 20 µs 200 µs 350 µs 600 µs 800 µs 1000 µs t (µs) VAL general short SEMINAR JAN 2016 PV_ÜSS.ppt / 2005

18

19 Damage statistics photovoltaics Frequency of causes
Photovoltaik Seminar - Blitzschäden Damage which has been settled by a German solar insurance company between 2003 and 2005 according to quantity Source: Mannheimer Versicherung 2006 PV_Schaeden.ppt / 2005

20 Photovoltaik Seminar - Blitzschäden
Damaged PV modules due to lightning strike Photovoltaik Seminar - Blitzschäden A SOLAR PV PLANT IN INDIA PV_Schaeden.ppt / 2005

21 DAMAGES IN RAJASTHAN

22 Lightning Protection System as per National Building Code 2016

23 NBC: Air Termination System
CLEAR NO to RADIOACTIVE air terminals or other kind like ESE/Dissipation/CSE X X X

24 5th RE, India 2011 lightning protection photovoltaic
External lightning protection - Rolling sphere method used to design an air-termination system GJB 230 / 400 V SEB GJB = generator junction box SEB = service entrance box MEB = main earthing busbar MEB 5th RE, India 2011 lightning protection photovoltaic / S6695e_i

25 Design of the air-termination system
radius of the rolling sphere depending on the class of LPS protection angle separation distance s air-termination rod shadow line 15° 5th RE, India 2011 lightning protection photovoltaic / 4025e

26 5th RE, India 2011 lightning protection photovoltaic
Lightning protection system – separation distance kept with air-termination rods Beitrag - Autor Source: D. Salansky Luma Plus s.r.o (CZ) 5th RE, India 2011 lightning protection photovoltaic / 6454_c 5. Forum für Sachverständige, 08. /

27

28 Galvanic coupling Lightning voltage of a system
Class of LPS Current amplitude kA I 200 II 150 III - IV 100 i t î Wave form 10 / 350 µs Reference: DIN EN (VDE ) ûE = î · Rst EB Example: ûE = 100 kA · 1  = 100 kV Rst

29 Galvanic coupling Lightning voltage in a building
100 kA 230 V 100 kV 100 kV 230 V 100 kV 1 

30

31 Photovoltaik Seminar - Blitzschäden
Damaged inverters Photovoltaik Seminar - Blitzschäden PV_Schaeden.ppt / 2005

32

33 Failures at Mahindra Susten, Kolayat

34 Real Life Experience

35 Basics: Equipotential Bonding Concept
Photovoltaik Seminar - Blitzschäden CASE 1 10 KV 230V RESULTS - ? CASE 2 100 KV 100 KV RESULTS - ? PV_Schaeden.ppt / 2005

36 Basics: Galvanic coupling Lightning voltage in a building
100 kA 20 kV 100KV 230V 100 kV 100 kV 100 kV 1 

37 Basics: Lightning equipotential bonding for incoming lines
Photovoltaik Seminar 2008 Lightning equipotential bonding MEB* LPZ 0 LPZ 1 utility external lightning protection system water gas M heating system Cathodically protected tank pipe foundation earth electrode *MEB = main earthing busbar 02_PV_Schaeden.ppt 2008

38 Lightning Protection System (LPS)
Photovoltaik Seminar 2008 External Lightning Protection Air-termination system- collection of Lightning Down-conductor system- Discharge of Lightning Earth-termination system- Dissipation of lightning to ground Internal Lightning Protection Lightning equipotential bonding Surge protection Separation distance s must be observed to prevent dangerous spark formation 5th RE, India 2011 lightning protection photovoltaic / 4509e 02_PV_Schaeden.ppt 2008

39 Take care of short circuit/ DC arcs
ARC produce d by 12V DC battery –Imagine 1000 V ARC in PV ARC PRODUCED BY 12 V CAR BATTERY- IMAGINE 1000V ARC in PV!!

40 LOAD CURRENT AND SC CURRENT BREAKING CAPACITY OF ARRESTER ?
I string 1 I stringTotal I string 2 I string n LOAD CURRENT AND SC CURRENT BREAKING CAPACITY OF ARRESTER ? e.g. IL=16 STRINGS X 10 A = 160A ISCWPV > 180A

41 Photovoltaik Seminar - Überspannungsschutz
Selection of surge protective devices Case 2: Type 2 SPD in Y-connection with 3 varistors Photovoltaik Seminar - Überspannungsschutz = ~ Practical example: Open-circuit voltage of the generator UOC STC PV_ÜSS.ppt / 2005

42 Photovoltaik Seminar - Überspannungsschutz
Surge Arrester DEHNguard® M YPV SCI Functional principle of the 3-step d.c. switching device Photovoltaik Seminar - Überspannungsschutz SCI.... Short Circuit Interruption SCI The electrical isolation of an overloaded protection module by means of the integrated fuse allows safe replacement of protection modules without arc formation PV_ÜSS.ppt / 2005

43 Surge Arrester DEHNguard® M YPV SCI Safe electrical isolation
Photovoltaik Seminar - Überspannungsschutz Circuit diagram Can be used without backup fuse in all low-, medium- and high-performance photovoltaic systems due to the integrated fuse SCI PV_ÜSS.ppt / 2005

44 Surge Arrester for PV MUST HAVE
Photovoltaik Seminar - Überspannungsschutz APPROPRIATE RATING OF ISCWPV Y Connection SURGE DISCHARGE RATING of >= 10KA at 8/20 microsec or 12.5KA 10/350 microsec END OF LIFE- Proper disconnection of DC ARC through by pass FUSE PV_ÜSS.ppt / 2005

45 PV Lightning and Surge PROTECTION REQUIREMENT
Photovoltaik Seminar - Überspannungsschutz Good ELP design from professional as per IS/ IEC 62305 Good Earthing design as per IEEE 80 Ensure Equipotential Bonding using SPDs at all AC and DC inputs END OF LIFE- Proper disconnection of DC ARC through by pass FUSE KEMA approved products and not funkies as bodygaurd PV_ÜSS.ppt / 2005

46 www.dehn.in THANK YOU Vikas.almadi@dehn.in / info@dehn.in