Use of ATP to identify poor- performing filters Al Parrella Western Lake Superior Sanitary District Duluth, MN
3
Add bleach here Final effluent
4
Problem statement: Bacteria increases across effluent filters – Seems to be a seasonal phenomenon (worse towards end of season)
6
Fecal coliform, before and after filters Monthly geometric mean
7
Problem Limit
8
Troubleshooting Use of ATP pen Test ATP at various location including the effluent of each filter Results reported as difference between total and free
10
Results Clearly there was a problem with number 11 filter Found several mechanical issues related to backwash system
12
Conclusion Its hard to clean 100+ tons of media
15
Steps Start meter Obtain sample Submerge pen Break ampule Mix Obtain reading – Units are in relative light units
16
Thanks to… …Roger Sandstrom, Treatment Plant Operator Kathy Hamel, PE, Operations and Maintenance Supervisor, Clean Water Production