Use of ATP to identify poor- performing filters Al Parrella Western Lake Superior Sanitary District Duluth, MN.

Similar presentations


Presentation on theme: "Use of ATP to identify poor- performing filters Al Parrella Western Lake Superior Sanitary District Duluth, MN."— Presentation transcript:

1 Use of ATP to identify poor- performing filters Al Parrella Western Lake Superior Sanitary District Duluth, MN

2

3 Add bleach here Final effluent

4 Problem statement: Bacteria increases across effluent filters – Seems to be a seasonal phenomenon (worse towards end of season)

5

6 Fecal coliform, before and after filters Monthly geometric mean

7 Problem Limit

8 Troubleshooting Use of ATP pen Test ATP at various location including the effluent of each filter Results reported as difference between total and free

9

10 Results Clearly there was a problem with number 11 filter Found several mechanical issues related to backwash system

11

12 Conclusion Its hard to clean 100+ tons of media

13

14

15 Steps Start meter Obtain sample Submerge pen Break ampule Mix Obtain reading – Units are in relative light units

16 Thanks to… …Roger Sandstrom, Treatment Plant Operator Kathy Hamel, PE, Operations and Maintenance Supervisor, Clean Water Production