Presentation is loading. Please wait.

Presentation is loading. Please wait.

ADW 535 SecuriSens ADW 535 Sales Presentation

Similar presentations


Presentation on theme: "ADW 535 SecuriSens ADW 535 Sales Presentation"— Presentation transcript:

1 ADW 535 SecuriSens ADW 535 Sales Presentation
Adrian Haenni, Sales Support

2 Content Principle of Operation Portfolio Strength Engineering Programming Remote Control & Visualization Networking Specifications Success Stories

3 Principle of Operation Linear Heat Family
Hollow Metallic Tube Pneumatic Only air Test Pump Detects leakage Detects squeezes Temperature Referencing At commissioning At regular intervals Corrects pressure drift Interfacing Relays Loop RS485 TCP/IP Alarm Fault Temperature sensors for referencing PRESSURE SENSOR Test Pump HOLLOW METALLIC TUBE Relays Loop Remote Control & Programming RS485 TCP/IP Fire Alarms Networking

4 Principle of Operation Cumulative Effects
Certified to EN 54-22 Specified response characteristics are at 9% heat exposure of the tube The larger the exposed part the faster the response Minimum tube length is 10m 10m SENSING TUBE Total Length 115m TEST FIRE

5 Portfolio Product Range
Two Units 1 or 2 Detectors ADW 535-1 1 Detector 2 Relays (Alarm & Fault) ADW 535-2 2 Detectors 4 Relays Det. 1: Alarm and Fault Det. 2: Alarm and Fault

6 Portfolio Plug-in Boards
Relay Expansions Loop Connectivity Networking RIM 36 5 Relays free programmable Max. 2 Boards per Unit XLM 35 Loop Interface SecuriLine Extended Transmits fault and alarm messages SIM 35 RS485 Max. 1’000m Max. 250 Units Fast Poll of 50 units/s Remote Configuration Event Display Relay Board: 5 Relays per board, max. 2 boards per unit, total of 13 relays per unit SD Memory Card Module: 1GB does it all (more does not help any)

7 Portfolio Accessories Competence
Material Description Typical Application TU 5/4 Cu Copper Ø 5mm (outer) Ø 4mm (inner) in 5.5m rods or in rolls High Temperature Application Room Monitoring Equipment Monitoring Vehicle Monitoring TU 5/4 SS Stainless Steel in 6m rods Aggressive Environment Food processing industry Petrochemical Industry Waste Water Treatment Plants TU 6/4 PTFE Teflon (PTFE) Ø 6mm (outer) in rolls ? Installation Various fixings in plastic, brass or steel

8 Strength Extremely Solid
The sensor material suits your application: Non-magnetic Non-rusting Non-altering Acid-proof Shock-proof Water-proof Heat-resistant Dirt-resistant

9 Strength Long Lasting No active components! Basically infinite lifetime

10 Strength Extremely Resistant
Works in any environment: Aggressive Radioactive Gaseous Liquid Solid (powder etc.)

11 Strength Extremely Flexible
Adaptable to your need Suitable for Ex zones without need for Atex certification and zone barriers. Programmable response: From slow to fast Sensing temperature range: -40° to +180°C Ex ZONE I/21 Ex ZONE II/21 SAFE ZONE -40°C +180°C

12 ADW 535 is certified to comply with all Classes and Groups.
Strength Flexibility Response Classes Environment Groups Response Class Detection Range °C Application A1 Rooms up to 7.5m Height A2 Rooms up to 6m Height B C D E F G Env. Group Op. Temp. Range °C Application 1 Indoor / stable and clean conditions Commercial Industrial 2 Indoor / varying and polluted conditions 3 Outdoor / harsh conditions ADW 535 is certified to comply with all Classes and Groups.

13 Strength Stability Self-Balancing
The ADW 535 is regularly referencing the tube’s pressure to the ambient temperature. The detection sensitivity remains stable for years, if not forever. In consequence, extreme temperature variations during the day are no problem for the ADW 535. It is the most dependable heat detector for outdoor applications. STABLE NEUTRAL UNSTABLE

14 Strength Extremely Fast
The ADW 535 is the fastest responding rate-of-rise heat detector. Cumulative effects are even accelerating the response. TSC rate-of-rise Alarm ADW 535 Rate-of-rise ALARM Fixed Threshold Detection 5 Minutes

15 Strength Extremely Reliable
“Dynamic Heat Watch” for zero nuisance alarms Procedure Detect abnormal “rate-of-rise” Check persistence after 1st delay Check for high temperature after 2nd delay Benefit Reduce nuisance alarms due to changes of the environment temperature Temperature [pressure] [mbar/min] Δ [pressure] [mbar] Rate-of-Rise Rate-of-rise threshold Time [s] Delay Time Window [600] Alarm Verification [rate-of-rise] Initial Trigger

16 Strength Extremely Reliable
Sample Application: Loading Docks Sudden release of warm air when opening gates. Temperature [pressure] [mbar/min] Δ [pressure] [mbar] Rate-of-Rise Rate-of-rise threshold WARM AIR Delay Time Window [600] Time [s] Alarm Verification [rate-of-rise] Initial Trigger

17 two detector dependency
Strength 2-in-1 Double Knock Easy to do two detector dependency for extinguishing controls Extinguishing Controls

18 Engineering ADW 535 HeatCalc
3D Drawing of the tubes: Tubes fittings Coils Specification of the wanted system performance Max. Threshold Verification Threshold Rate-of-Rise Delays Calculation of the system setup parameters: Parameter Export to ADWconfig Reporting Parts List

19 Engineering Programming Workflow
ADW HEATcalc By Software ADW Heatcalc ADWconfig Download By Hardware Technical Description Manual Setup by EASYconfig ADWconfig UP OK Two ways to setup the unit: By Software ADWconfig with on-screen parameter setting or loading the parameter set created by By manual setting via EASYconfig First Step: Check for appropriate code on page 40ff of the Technical Description ADW EASYconfig TECHNICAL DESCRIPTION

20 Remote Control & Visualization ADWconfig
Configuration Import of HEATcalc files Parameter setting Visualization Real-time charting of pressure values Firmware Update Upload of new firmware Documenting Printout of Parameter Setup

21 Networking RS485 Networking
Long Distance Up to 1km Extendable by repeater Full Control Remote configuration Remote monitoring of faults and alarms ADWconfig Software Fast Scanning 50 Units in 1 second Open Protocol Disclosed under a license agreement. 1 2 3 250 USB RS485 ADW 535config DONGLE

22 Specifications Unit Sensor Tube
Dimension (h x w x d ): 20 x 160 x 134 mm Protection Class IP 65 Operation Temperature Range: -30 to +70 °C Operating Voltage: – 30 VDC Number of Sensors: 1 or 2 Sensing Range 1’000mbar / 270K Sensor Tube Tube Diameter (inner/outer) Metallic: 5mm / 4mm PTFE: 6mm / 4mm Max. Tube Length (aggregated) 115m Max. Area to cover: 2 x 800m2 Engineering / Programming: Pre-defined (EasyConfig) or «as needed» (HeatCalc) Max. Number of sampling points: Class C /120 is a marketing figure. Physical constraints are limiting the number of sampling points to about 80 because of Practical reasons: holes of less than 2mm are easily stuck with dust. Pressure drop: To many holes are resulting in zero aspiration power at the distant sampling points

23 User Benefits Summary Strength Benefit Proof Extremely Solid
Indoor and outdoor application Low demand for maintenance Long life cycle Metallic or PTFE sensor tube IP65 enclosure Operating range -30°C to +70°C Long Lasting Low “Total Cost of Ownership” (TCO): Maintenance free and not needing any replacements – for decades. Metallic tubes Automated integrity check IP 65 Extremely Resistant Can be used in dangerous / aggressive environment. Works in any medium (solid, liquid, gas) Measures from -40°C to +180°C Extremely Flexible Can be used in Ex Zones without need for barriers or Atex approval Programmable response behavior Does Ex without the usual restraints: Serviceability Maintenance can take place without need to access the detection area Sensor tube is maintenance free Extremely Fast Buy extra time for securing the zone Fastest heat sensing technology available Engineering Reliability at performance extremes HeatCalc 3D design software 3000

24 Success Stories Car Parks
Parking «Esplanade» Europe’s largest Parking 4 Levels 11’000 Cars 9’800 Public 1’800 VIP Allianz Arena Parking in Munich

25 Success Stories Road Tunnels
COPPER TUBE Dozens of road tunnels worldwide. 2.5km Bypass Tunnel Ligerz, Switzerland

26 Success Stories Distilleries
COPPER TUBES Large Distillery in Italy with many Ex zones.

27 Success Stories Food Processing
VILSA Brunnen, Bremen, Germany Room protection with ADW tubes between ceiling panels.

28 Success Stories Floating Roof Tank
FOAM UNITS Hundreds of Floating Roof Tanks all over India. TANK FARM at MUNDRA PORT Gujarat, India

29 Success Stories Floating Roof Tank
Specialty: Covered Floating Roof Tanks TANK FARM at Klaipeda, Lithuania

30 Success Stories Wood Bridges
Bridge “Büren an der Aare” ADW sensor below floor for detecting fire attack by boat ADW sensor below roof tiles Fake point detectors on the beams below the roof containing just a switch for indicating tampering WOODBRIDGE Büren an der Aare, Switzerland

31 Thank you for your attention!
Securiton AG Alarm- und Sicherheitssysteme Alpenstrasse 20, CH-3052 Zollikofen


Download ppt "ADW 535 SecuriSens ADW 535 Sales Presentation"

Similar presentations


Ads by Google