Download presentation
Presentation is loading. Please wait.
1
ABB INDIA DEVELOPMENT CENTER
ACHIEVING REDUNDANCY USING CONFIGURATION EXCHANGE THROUGH GOOSE COMMUNICATION IN SUBSTATION Ravishankar Y A, Arinjai Gupta, Murali Kandakatla, Pramod Kulkarni, Shivakumar N R and Sudheer B 2013 Colloquium November 13-15, 2013 Mysore – KARNATAKA - INDIA ABB INDIA DEVELOPMENT CENTER D2-02_03
2
If there is fault/short circuit in transmission line then
Protection scheme If there is fault/short circuit in transmission line then Relay A detects short circuit and gives signal to open circuit breaker so that healthy grid is isolated from fault. Power flow direction Generator Circuit Breaker G Long transmission line CT VT From Grid Fault Power load Power supply Relay A Sub-station A
3
After the faulty transmission line is isolated the healthy
Protection scheme After the faulty transmission line is isolated the healthy grid continues to function. Power flow direction Generator Circuit Breaker G Long transmission line CT VT From Grid Power load Power supply Relay A Sub-station A
4
Back up Protection scheme
Why back up protection in substation is used ? Overcome equipment failure Failure to detect fault Back up protection in substation is used where cost of failure out weight the cost of redundancy
5
Back up protection for fault detection (Time graded )
If the Relay B in substation B fails then Relay A trips at substation-A after a set time delay to isolate the fault. Power flow direction Circuit Breaker Circuit Breaker Long transmission line CT CT VT VT Fault Power load Relay A Relay B Power supply Sub-station A Sub-station B
6
Redundant IED for fault detection (Duplication )
If the Relay B1 fails then redundant Relay B2 trips at substation-B to isolate the fault without any time delay Power flow direction Circuit Breaker Long transmission line Circuit Breaker CT CT VT VT Relay B1 9’2 Fault Power load Relay A Sub-station B Power supply Sub-station A Relay B2
7
Using 9’2 merging unit and Protocol translator
9’2 merging units are used to get measurement values. Protocol translator can be used for GOOSE exchange Circuit Breaker CT Logical connection VT 9’2 samples 9’2 Merging Unit 9’2 samples Analog GOOSE Analog GOOSE Configuration/Setting IED1 S1 S2 . Sn Health Configuration/Setting IED2 S1 S2 . Sn Health Protocol translator Health Health Protocol translator Trip signal2 Trip signal1
8
Different Redundancy configuration
Peer-Peer configuration: Both IEDs function in parallel. Setting/configuration is synchronized using Analog GOOSE. The trip signals from both the Peer are connected to CB. Master- Slave configuration: Master IED sends its health information to the Slave continuously. If the Slave IED receives bad health signal from the Master, the Slave IED takes control of trip signal to the CB Master- Slave configuration: Slave sends its health information to the Master continuously. If the Master IED receives bad health information from Slave, then Master IED takes control of CB. Note: In case of communication failure in Master-Slave and Slave-Master configuration both function as Peer-Peer. Master and Slave are physically connected CB all the time but logically connected based on configuration.
9
Automatic Configuration Exchange
Each setting/ Configuration of IED is mapped as output in Analog GOOSE*. These values are exchanged. IED1/LD0/Application1 Status information Str (Start) Op (Operate) Setting Setting1 Setting2 … Settingn ActiveSettingGroup LD0.Health.stVal IED2LD0/Application1 Status information Str (Start) Op (Operate) Setting Setting1 Setting2 … Settingn ActiveSettingGroup LD0.Health.stVal Broadcast Analog GOOSE Sender Analog GOOSE receiver *GOOSE : Generic Object Oriented Substation Event
10
Acknowlege functionality
Data and acknowledgment are sent by SNDGGIO Logical Node. Data and acknowledgment are received by RECGGIO Logical Node. IED1 IED2 IED1/LD0/ RECGGIO1 Status information DataAvailable AckReceived IED2/LD0/ SNDGGIO1 Status information DataSent DataReceived Analog GOOSE receiver Data Handler Analog GOOSE Sender Data Handler IED1/LD0/ SNDGGIO1 Status information DataSent DataReceived IED2/LD0/ RECGGIO1 Status information DataAvailable AckReceived Analog GOOSE Sender Analog GOOSE receiver The DataSent, DataAvailable, DataReceived & AckRecieved are not part of standard Data object
11
Race around condition When both IEDs initiate configuration exchange simultaneously then race around condition occurs. It can be solved by assigning Priorities to one of the IEDs IED1 IED2 IED1/LD0/ RECGGIO1 Status information DataAvailable AckReceived IED2/LD0/ SNDGGIO1 Status information DataSent DataReceived Analog GOOSE receiver Data Handler Analog GOOSE Sender Data Handler IED1/LD0/ SNDGGIO1 Status information DataSent DataReceived IED2/LD0/ RECGGIO1 Status information DataAvailable AckReceived Analog GOOSE Sender Analog GOOSE receiver The DataSent, DataAvailable, DataReceived & AckRecieved are not part of standard Data object
12
We can have 4 different back up schemes:
IEDs of same manufacturer with same protection principle IEDs of same manufacturer with different protection principle IEDs of different manufacturer with same protection principle IEDs of different manufacturer with different protection principle Trip circuit
13
Configuration Exchange: Scheme 1
Configuration exchange between IEDs of same manufacturer with same protection principle IED1/LD0/PTOC Over current protection Status information Str (Start) Op (Operate) Setting StrVal(Start value) StrValMult(Start value multiplier ) ActiveSettingGroup LD0.Health.stVal IED2/LD0/PTOC Over current protection Status information Str (Start) Op (Operate) Setting StrVal(Start value) StrValMult(Start value multiplier ) ActiveSettingGroup LD0.Health.stVal Trip circuit Trip circuit Trip circuit For example : PTOC (over current ) each setting can be mapped and configuration of each setting is possible Trip signals (Operate) are “OR”ed and then connected to circuit breaker.
14
Configuration Exchange: Scheme 1
Configuration exchange between IEDs of same manufacturer with same protection principle Mode Setting/ Configuration exchange Health Signal communication During IED failure(1 Health Communication failure(2 Peer – Peer Configurable Not required Both trip signal connected to CB Both operate in parallel Master-Slave Master-> Slave When Master fails, Slave trip signal is connected to CB Both operate as Peer-Peer Slave-Master Slave-> Master When Slave fails, Master trip signal is connected to CB (1 failure in operation (measurement failure etc.).But it is still able to send health signal (2 failure in communication channel, failure in communication sending and communication receiving For example : PTOC (over current ) each setting can be mapped and configuration of each setting is possible
15
Configuration Exchange: Scheme 2
Configuration exchange between different protection principle and same IED manufacturer IED1/LD0/PTOC Over current protection Status information Str (Start) Op (Operate) Setting StrVal(Start value) StrValMult(Start value multiplier ) ActiveSettingGroup LD0.Health.stVal IED2/LD0/PDIS Under impedance protection Status information Str (Start) Op (Operate) Setting PhStr(Phase Start Value) PoRch(Polar Reach is the diameter) ActiveSettingGroup LD0.Health.stVal Trip circuit Trip circuit Trip circuit For example : Configuration exchange between PTOC (over current ) and PDIS (under impedance ) is not possible as the settings are different. Trip signals (Operate) are “OR”ed and then connected to circuit breaker.
16
Configuration Exchange: Scheme 2
Configuration exchange between IEDs of same manufacturer with different protection principle Mode Setting/ Configuration exchange Health Signal communication During IED failure(1 Health Communication failure(2 Peer – Peer Not configurable(3 Not required Both trip signal connected to CB Both operate in parallel Master-Slave Not configurable Master-> Slave When Master fails, Slave trip signal is connected to CB Both operate as Peer-Peer Slave-Master Slave-> Master When Slave fails, Master trip signal is connected to CB (1 failure in operation (measurement failure etc.).But it is still able to send health signal (2 failure in communication channel, failure in communication sending and communication receiving (3 None of the setting/configuration can be exchanged using Analog GOOSE as there are no similar settings between IEDs For example : Configuration exchange between PTOC (over current ) and PDIS (under impedance ) is not possible as the settings are different.
17
Configuration Exchange: Scheme 3
Configuration exchange between IEDs of different manufacturer with same protection principle IED1/LD0/PTOC Over current protection Status information Str (Start) Op (Operate) Setting StrVal(Start value) StrValMult(Start value multiplier ) ActiveSettingGroup LD0.Health.stVal IED2/LD0/PTOC Over current protection Status information Str (Start) Op (Operate) Setting StrVal(Start value) OpDlyTmms (Operate delay time) ActiveSettingGroup LD0.Health.stVal Trip circuit Trip circuit Trip circuit For example : Settings of IED1.LD0.PTOC1(over current ) may not be similar to settings of IED2.LD0.PTOC1. Hence all the setting configuration exchange many not be necessary. Trip signals (Operate) are “OR”ed and then connected to circuit breaker.
18
Configuration Exchange: Scheme 3
Configuration exchange between IEDs of different manufacturer with same protection principle Mode Setting/ Configuration exchange Health Signal communication During IED failure(1 Health Communication failure(2 Peer – Peer Configurable/Partial configurable(3 Not required Both trip signal connected to CB Both operate in parallel Master-Slave Configurable/Partial configurable Master-> Slave When Master fails, Slave trip signal is connected to CB Both operate as Peer-Peer Slave-Master Slave-> Master When Slave fails, Master trip signal is connected to CB (1 failure in operation (measurement failure etc.).But it is still able to send health signal (2 failure in communication channel, failure in communication sending and communication receiving (3 Few of setting/configuration can be exchanged using Analog GOOSE, only similar settings between IEDs For example : Settings of IED1.LD0.PTOC (over current ) may not be similar to settings of IED2.LD0.PTOC. Hence all the setting configuration exchange many not be necessary.
19
Configuration Exchange: Scheme 4
Configuration exchange between IEDs of different manufacturer with different protection principle IED1/LD0/PTOC Over current protection Status information Str (Start) Op (Operate) Setting StrVal(Start value) StrValMult(Start value multiplier ) ActiveSettingGroup LD0.Health.stVal IED2/LD0/PDIS Under impedance protection Status information Str (Start) Op (Operate) Setting PhStr(Phase Start Value) PoRch(Polar Reach is the diameter) ActiveSettingGroup LD0.Health.stVal Trip circuit Trip circuit Trip circuit For example : Configuration exchange between PTOC (over current ) and PDIS (under impedance ) is not possible as the settings are different. Trip signals (Operate) are “OR”ed and then connected to circuit breaker.
20
Configuration Exchange: Scheme 4
Configuration exchange between IEDs of different manufacturer with different protection principle Mode Setting/ Configuration exchange Health Signal communication During IED failure(1 Health Communication failure(2 Peer – Peer Not configurable(3 Not required Both trip signal connected to CB Both operate in parallel Master-Slave Not configurable Master-> Slave When Master fails, Slave trip signal is connected to CB Both operate as Peer-Peer Slave-Master Slave-> Master When Slave fails, Master trip signal is connected to CB (1 failure in operation (measurement failure etc.).But it is still able to send health signal (2 failure in communication channel, failure in communication sending and communication receiving 3) None of the setting/configuration can be exchanged using Analog GOOSE as there are no similar settings between IEDs For example : Configuration exchange between PTOC (over current ) and PDIS (under impedance ) is not possible as the settings are different.
21
Security aspect of redundancy configuration
How important is security aspect in automated configuration of redundant protection schemes? Very important !! GOOSE is configured for One-to-One and broadcast communication using MAC address . GOOSE message can also be sent using encryption during communication It is necessary for redundant IEDs to have minimum security aspect like authority, User log etc.
22
Conclusion: Configuration exchange helps to automate porting of setting/configuration from IED to IED in redundancy scheme. Redundancy and automatic configuration exchange improves reliability of operation without manual intervention These are first steps to achieve self-healing grid systems
Similar presentations
© 2025 SlidePlayer.com. Inc.
All rights reserved.