Tutorial for Psyc0226 Wei Fang, Ph.D., Professor

Similar presentations


Presentation on theme: "Tutorial for Psyc0226 Wei Fang, Ph.D., Professor"— Presentation transcript:

1 Tutorial for Psyc0226 Wei Fang, Ph.D., Professor
Dept. of Bio-Industrial Mechatronics Engineering National Taiwan University Software last updated: 2002/02/26 Tutorial last updated: 2003/11/28

2 Capability of Psyc0226 Allow alteration on atmospheric pressure
Provide handy PsyTables Totally 11 tables are available Provide PsyCharts State calculation: besides AtmP, values of 2 independent states are required to calculate others Process calculation: find differences between 2 states More process calculation: Evaporative cooling Vapor pressure deficit on leaf

3 More message of the selected cell
Abbreviations of thermodynamic properties of moist air used in Psyc0226 Tdb: dry bulb Temp. RH : relative humidity Twb: Wet bulb Temp. Tdp: dew point Temp. AH : absolute humidity SV : specific volume Hfg: Saturated DOS: degree of Saturation Pws: saturated vapor pressure Pw: vapor pressure More message of the selected cell

4 Block in red defined as Psychart window

5 Set the Atmospheric pressure is the first step

6 Handy PsyTables

7 Totally 11 PsyTables

8 User friendly 3-step design in PsyTable
1. Define the ranges 2. Set the intervals 3. List the values

9 Table 1: Twb = f(Tdb, RH) Twb RH (50 – 100%)and Tdb (20 – 44 oC)

10 Wet Bulb Depression is the limit of evaporative cooling methods.
Table 2: WBD = f(Tdb,RH) WBD Wet Bulb Depression is the limit of evaporative cooling methods.

11 Table 3: RH = f(Tdb,Twb) RH Twb (20 – 44 oC) and Tdb (20 – 44 oC)

12 Table 4: VPD of air

13 VPD=Pws@Tdb – Pw@Tdb AHD=Sat.AH@Tdb – Sat.AH@Tdp
VPD/AHD of air

14 Table 5: VPD’ of air

15 VPD’=Pw@Twb – Pw@Tdb AHD’=Sat.AH@Twb – Sat.AH@Tdp
VPD’/AHD’ of air

16 Psycharts Evaporative cooling process calculation
Besides atmospheric pressure, values of 2 independent states are required to derive others find differences between 2 states Evaporative cooling process calculation Vapor pressure deficit on leaf

17 State Calculation

18 Independent Properties (IP)
Twb RH Tdp AH SV H hfg DOS Pws Pw Tdb IP Any pair of IP can be the given values to derive others.

19 One click in Psychart window using left button of the mouse can define a state

20 Process Calculation

21 Use mouse to define 2 states
To define 2nd state, change from ‘Inactive’ to ‘Active’ first. Click in the Psychart window at the selected state or click on the crosshair region to move along constant lines or curves. Click on ‘Cal.’ to calculate the difference.

22 Move along prefix lines or Curves
Constant Twb Constant Tdb Constant RH Constant Tdp, Pw, AH Constant Tdp, Pw, AH Constant RH Constant Tdb Constant Twb

23 A process with sensible heat gain

24 Process: between states
Sensible Heating (3->4) Sensible Cooling (4->3) Humidification (4->5) Dehumidification (5->4) Heating (3->5, 3->1) Cooling (5->3, 1->3) Air Mixing (1, 2->3) Evaporative Cooling,Drying (1->2, 1->3) Combination of above (1->2->3->4->5)

25 Evaporative cooling process

26 Enter ‘Tdb after pad’ or ‘pad efficiency’ to derive others followed by a Click on ‘Draw’ icon.
WBD

27 Temperature drop after passing through pad (ΔT)
ΔT = WBD of outdoor x Efficiency of the pad T T- ΔT

28 Vapor pressure deficit (VPD)
Enter Leaf temperature, then click on Draw icon. VPD

29 Other user friendly designs

30 Lines and curves can be visible or hidden by (de)selecting related icons

31

32 Zoom in & out

33 Labels in Psychart window can be hidden by de-select the Unit label icon

34 The state user defined in the psychart window using left button of the mouse will be placed in the center of the psychart window if the Centralize icon was selected. This option is set inactive by default.

35 Enjoy playing with Digital Psychart
Please send us information regarding found bugs. Mail to :


Download ppt "Tutorial for Psyc0226 Wei Fang, Ph.D., Professor"

Similar presentations