Presentation is loading. Please wait.

Presentation is loading. Please wait.

Analog Room Command Module

Similar presentations


Presentation on theme: "Analog Room Command Module"— Presentation transcript:

1 Analog Room Command Module
Header - Use 'Insert >Header & Footer' to modify this text and ‘Apply to all’ RS-7000 Stylish flush mount Analog Room Command Module Footer - Use 'Insert >Header & Footer' to modify this text and ‘Apply to all’

2 RS 7000 Analog Room Command Module Overview
Header - Use 'Insert >Header & Footer' to modify this text and ‘Apply to all’ RS 7000 Analog Room Command Module Overview The Hardware platform provides: RS Analog Room Command module comapible with former and new HVAC Controller White Version Only Benefit Modern design Large display with Push buttons Thin profile 14 mm and square 86 x 86 mm design Flush mount, made to fit EU box Configurable functions for SKU reduction and easy selection Combined Temperature and Humidity detection Consistent design between new generation of Room Sensors Flush mount European Box Footer - Use 'Insert >Header & Footer' to modify this text and ‘Apply to all’ NSA-7000 Room Command Module Resource pages

3 RS 7000 Analog Room Command Module User Interface
Header - Use 'Insert >Header & Footer' to modify this text and ‘Apply to all’ RS 7000 Analog Room Command Module User Interface Large Display Custom Display 40% of the front area Backlight with time-out No need of localization Show Set Point only option Show Humidity Set Point limits Show Units °C or F Temperature reading offset Fan Controls Set Point Control Depending on model Easy selection up / down of 0,5 °C Set Point mode ADJ or W/C configurable Occupancy Toggle OCC output ADJ 12 28 °C W/C -3 +3 Configurable Up to 5…35°C Up to °C SP MODE Keypad Lockable No lock Lock all keys Lock all keys except Occupancy Press and Hold 5 SEC to configure Footer - Use 'Insert >Header & Footer' to modify this text and ‘Apply to all’ NSA-7000 Room Command Module Resource pages

4 RS 7000 Analog Room Command Module Overview
Header - Use 'Insert >Header & Footer' to modify this text and ‘Apply to all’ RS 7000 Analog Room Command Module Overview RS 7000 Room Command Module Designed to be use with former and new HAVC Controller offers analogs output to transmit: Temperature, Setpoint and Fan Speed selection or Humidity. Main Difference with Current RS-1100: Flush Mount, low profile with larger a clear display Combined Temperature and Humidity option Local configuration via Display and pushbuttons: Set Point mode: Adjust or Warmer/Cooler Show Only Setpoint, Units °C or °F Locks Push buttons 3 Items codes for many configuration ADJ 12 28 °C W/C -3 +3 Configurable Up to 5…35°C Up to °C SP MODE Footer - Use 'Insert >Header & Footer' to modify this text and ‘Apply to all’ NSA-7000 Room Command Module Resource pages

5 RS 7000 Analog Room Command Module Item Codes
Header - Use 'Insert >Header & Footer' to modify this text and ‘Apply to all’ RS 7000 Analog Room Command Module Item Codes RS Four buttons model RS Three buttons model AO1 Temperature AO2 Set Points AO3 Fan Speed DO Occupancy override (*) AO1 Temperature AO2 Set Points AO3 Humidity RH% DO Occupancy override (*) RS Specification Power 15 VDC Temp range 0…40°C accuracy + 0,5 °C Humidity % accuracy 3% Only White finishing AO1 Temperature AO2 Humidity RH% (*) Open Collector, open when occupied Footer - Use 'Insert >Header & Footer' to modify this text and ‘Apply to all’ NSA-7000 Room Command Module Resource pages

6 RS 7000 Network Sensors Installation
Header - Use 'Insert >Header & Footer' to modify this text and ‘Apply to all’ RS Network Sensors Installation The NSA-7000 can be installed on rounded European boxes using the mounting plate included in the supply. Once installed the devices will cover completely the mounting plate and it will protrude from the wall of 14 mm only. A little screw keeps the device in place. Footer - Use 'Insert >Header & Footer' to modify this text and ‘Apply to all’ NSA-7000 Room Command Module Resource pages

7 RS 7000 Ordering codes Table 1: RS 7000 Room Command Module
Product code Color1 LCD Temp Humidity2 Fan control Temp. adjustment3 F/C scale toggle Occupancy override RS White No Yes Yes (±3%) N/A RS Adj/WC RS Note: For models with humidity sensor, the humidity value can be displayed in LCD too Device color white only Adj/WC means this model can work under Adjust 12 to 28°C or WC (Warmer/Cooler) +3 °C mode, selected in setting. NSA-7000 Room Command Module Resource pages

8 RS-7000 network sensor Benefit
Large backlit Display in a low profile enclosure Display larger than 40% of front area, provides real time status of the environment with intuitive and clear user interface Display helps to meet building policy Sensors can be configured to show temperature, humidity or set point only, in addition the keypad can be locked to avoid misuse in public spaces. Flush Mount installation make it stylish Suitable for various installation boxes, flush mount offer low profile of only 14 mm outside the wall. Customize colors to meet customer needs The front panel of the sensor can be white or customized in black or other colors with a minimum quantity. Mounting plate protection cap The mounting plate allows installation without opening the sensor. The removable and repositionable protection cap protects the sensor during commissioning or painting. Both avoid the risk of component damages during installation Configurable options reduce stock need Setpoint functionality Adjust or Warmer/Cooler can be configured from the display during the installation. Combined Temperature and Humidity Offer best comfort, and Service retrofit opportunity where RS-1100 can be replaced with a more advanced stylish unit. NSA-7000 Room COmmand Module Resource pages

9 RS-7000 Technical Specification
Supply Voltage 15VDC nominal Current consumption 35mA maximum Terminations Screw terminal block Wire size Screw terminal block: AWG ( mm diameter); 22AWG (0.6 mm diameter) recommended Outputs RS : Temperature: 0…10 0…40 °C Humidity : …10 0…100 RH% Outputs RS : AO1 Temperature: 0…10 0…40 °C AO2 Setpoint: … 10 V (*) AO3 Humidity : …10 0…100 RH% Occupancy: Open collector Occupied = Contact Open, Outputs RS : AO2 Setpoint: … 10 V (*) AO3 Fan Speed: V Occupancy: Open collector Occupied = Contact Open, Mounting Flush-mounted Temperature accuracy ±0.5℃ (±1oF) Humidity accuracy ±3%RH Default temperature set point adjustment range Default Adjust Range: °C, max configurable 0 to 40 °C in 0.5 °C increments Default W/C Range: -3 to +3 °C, max configurable 0 to + 5 °C in 0.5 °C increments SP adj 12°C = 3 V / 28°C = 7 V -- SP W/C 0°C = 5 V +3°C = 7 / -3°C = 3 V) Ambient conditions Operating: 0-40 °C with 10-90% RH, non-condensing Storage: -20 to 60 °C with 5-95% RH, noncondensing Shipping weight Approx. 300g Compliance CE mark RCM mark, Australia/NZ emissions compliance RoHS, REACH, WEEE (*) SP adj 12°C = 3 V / 28°C = 7 V -- SP W/C 0°C = 5 V +3°C = 7 / -3°C = 3 V) Footer - Use 'Insert >Header & Footer' to modify this text and ‘Apply to all’