Download presentation
Presentation is loading. Please wait.
1
Alabama Section Meeting IEEE
Monitoring & Diagnostic Overview Alabama Section Meeting IEEE 2/2018 Chris White (904)
2
The Transformer … A Complex System
Cooling System Tap changer Main tank Core Coils Oil Control Cabinet Bushings P&C Education Seminar
3
Transformer Construction
Cooling System Oil Tank Bushings Tap changer Coils Core Control Cabinet The core is the most massive part of the transformer. It is a stack of several hundreds, even thousands, of precisely cut sheets of milled soft iron. Its purpose is to direct and concentrate the magnetic flux generated by the coils. It is sometimes referred to as the “magnetic” circuit. The coils are the “inputs” and “outputs” of the transformer. In most transformers we have three sets of two coils. Each pair make up a “phase” and are labeled “A,B,C” or “White, Blue, Red” or “1, 2, 3”. The two coils of each set are usually called “High Voltage” and “Low voltage”, or “Primary” and “Secondary”. However there are a wide variety of coil configurations and many other combinations exist. The tap changer’s function is to control the output voltage of the transformer. In essence it is a voltage regulator. Some tap changers are operated manually for seasonal adjustment, always requiring to remove the transformer from service to make the adjustment. Others operate automatically to maintain the transformer’s voltage as the load varies and are called “On-Load Tap Changers (OLTC)”. The OLTC could be located in the same tank as the core and coils (in-tank), or in a separate tank attached to the main tank where the leads are connected to the appropriate winding through either tap head connections or a barrier board. The transformer is a very efficient device and every effort is made in the design and construction of the transformer to minimize the amount of loss. However, even the most efficient transformer will have some losses which will generate heat. The cooling system consists of radiators or coolers, fans and pumps that recirculate the oil to remove the heat generated by the operation of the transformer. Bushings are the connection between the transformer and the power grid. Many consist of a conductor, wrapped with several layers of paper, impregnated with oil, and contained in a porcelain shell. Control cabinets contain the interconnection between the various control and monitoring elements of the transformer, such as the pumps and fans control, temperature display and gas relay alarms contact. Oil is the heat carrier in the transformer. Its function is to carry the heat generated by the coils and the core during normal operation to the radiator. The circulation of oil inside the transformer is a very critical function. Oil also acts as an electrical insulator between the various elements of the transformer.
4
Transformer Failure Modes
Component Failure rates Monitoring method (Not cost of failure) Main Tank % DGA monitoring of main tank Winding & oil temperature Acoustic PD PD recognition algo from BMT300 (next Gen) SFRA Tap changer % DGA of diverter and tap changer tanks Tap Changer models Motor torque monitoring Acoustic signature analysis Tap changer control Bushing % Tan delta Partial discharge Cooling System % Cooling efficiency models Cooling control Oil flow Source of data: The Hartford Steam Boiler Inspection and Insurance Co. 4
5
What is wrong inside this transformer?
6
First, What Is Transformer Dissolved Gas Analysis?
Sample Test Doc Diagnosis Doctors extract information about our health from our blood. Technicians extract information about the health of our transformers from the oil via DGA. Substations are more challenging for this sampling process than a doctor’s office
7
Transformer Dissolved Gas Analysis, The Process & Logic
Duvall’s Triangle Sample Test Tech Diagnosis We prefer a clean sample with no issues detected, just as a blood test in a doctor’s office. In the early 1970s a utility in the NW region of the United States had a transformer failure. They decided to take an oil sample and send it to a university in California to see if the chemistry department could make sense of it. It was then that dissolved gas analysis began its rise to prominence in the utility world.
8
Transformer Operating Temperatures
20 – 80 C? First signs of gassing begins around 100 C with CO2 & CO. First signs of hot metal gases begins around 150 C. While the typical power transformer may operate in the 20 to 80 deg. C range, there are many factors that influence the operation of a transformer, which can and do affect the overall life of the transformer.
9
What Are The Relevant Gases?
“Paper & Oil Gases” It is important to distinguish and categorize the gases. This is vital in our efforts to diagnose issues within a power transformer. While there’s more involved than simply knowing the starting point for each of the relevant gases, the starting point at which these gases generate is certainly a good place to start when attempting to understand DGA. How the gases behave and relate to each other is also another important piece of the puzzle. “Hot Metal Gases”
10
Oil degradation – Typical oil Molecule
H H H H C C H C H H H H C P&C Education Seminar
11
CO Paper degradation – gases developed CH2OH O C OH H Paper Molecule
CARBON MONOXIDE O CHO H WATER CO CH2OH OH O H C HOH FURAN HOH HOH Paper Molecule P&C Education Seminar
12
Key DGA gasses, and what they indicate
Hydrogen Nearly all fault conditions, low energy PD CH4 Methane Oil overheating between 200ºC and 500ºC C2H6 Ethane Oil overheating between 300ºC and 500ºC C2H4 Ethylene Oil overheating over 500ºC, possible formation of carbon particles C2H2 Acetylene High energy arcing, oil overheating over 800ºC, strong formation of carbon particles, metal melting CO Carbon Monoxide Paper insulation overheating CO2 Carbon Dioxide Oil oxidation, paper degradation O2 Oxygen Oxidation, leak P&C Education Seminar
13
Why Dissolved Gas Analysis?
By identifying which gas is increasing it is possible to determine the likely nature of the anomaly without having to shut down the transformer. Enables operational decisions based on this information. On-line DGA monitors with remote communications enable true Condition Based Monitoring (CBM) and decision making without going to site. P&C Education Seminar
14
Diagnosing Transformer Main Tank Faults
15
Where’s The Problem? Nitrogen Sealed #1 – 36 MVA
Notice that the hot metal gas signatures listed here have the same pattern for each transformer, but the outcome will be completely different due to “where” each of the 2 faults are located, as will be noted on slide 11. The question here is “what” further data is needed to understand the location of the fault prior to entering the transformer to attempt repairs?
16
Where’s The Problem? Continued
Ratio of CO2/CO gases decreased from 7:1 to 5:1 after the event Ratio of CO2/CO gases decreased from 117:1 to 2:1 after the event The greater the amount of paper involved in a fault, the greater the impact on the CO2/CO ratio. Note the impact on the CO2/CO ratio for each of these transformers as a result of a problem. In the example on the left, which relates to the example on the left on slide 9, a significant drop in the CO2/CO ratio is noted, which is an indicator of exactly how much paper was affected at the time of the event. In the example on the right, which relates to the example on the right on slide 9, the paper appears to be much less affected. If paper is truly involved in both faults, and since both scenarios did have an impact on the CO2/CO ratio, can we determine if the paper involved is a reflection of an overheated lead, or something more sinister buried in the windings? The answer is yes, we most certainly can. aaaaaaaaaaaaaaaaa aaajjjjjjjjjjjjjjjjjaaaaaa
17
Where’s The Problem? Continued
Winding Failure #1 Primary Lead – Repairable #2 As you can see from the example on the left, which had the vast reduction in the CO2/CO ratio did in fact fail in the winding paper (this example relates to the examples to the left on slides 9 & 10). This transformer in fact tripped on a transformer differential, and failed. The second example on the right was a primary lead (this example relates to the examples to the right on slides 9 & 10). This unit also tripped on a transformer differential, however it had a different outcome altogether. It is important to understand the information and correctly categorize the gases. Without this insight, it is impossible to know if the problem is more fatal, or repairable when attempting to diagnose via DGA. This is very important information to have prior to opening up the transformer for an investigation and possible replacement of a transformer. Of course, the ideal situation is to locate these problems prior to a differential trip, which can be done. Transformer Replaced Transformer Repaired
18
Where’s The Problem? Found coked De-Energized Tap Changer (DETC). DATE
TDCG CO2/CO 11/4/2009 235 12,771 68,988 686 277 2,879 228 1,523 52 3001 1/8/2010 268 14,477 81,770 986 369 4,063 323 2,196 54 4,238 2/23/2010 282 13,893 76,571 821 312 4,506 329 2,239 47 4,030 3/22/2010 272 13,034 71,225 834 284 3,200 302 1,892 33 3,617 5/6/2010 226 11,639 68,938 974 350 4,000 325 2,054 39 3,968 8/13/2010 134 11,897 59,148 1,138 298 3,451 337 2,358 14 4,279 1/12/2011 8,613 72,536 1,663 577 5,183 447 3,215 6,245 1/25/2011 256 9,233 67,438 1,151 491 4,979 421 2,443 16 4,778 2% Decline Overall 38% Increase Overall DETC Coked Found coked De-Energized Tap Changer (DETC).
19
Descending CO2/CO Ratios - 75 MVA, N2 Blanketed
DATE H2 O2 CH4 CO CO2 C2H6 C2H2 C2H4 CO2/CO 30-Jul-12 ND 9715 1 64 453 7 6-Jul-11 1180 22 485 2 25-Jan-10 5893 17 439 26 9-Mar-09 1738 TRACE 4 475 118 26-Mar-08 2829 25 851 3 34 15-Feb-07 1667 816 37 With the exception of the 2009 sample (likely poor handling during sampling), a downward trend in the CO2/CO ratio is exhibited in the six years leading up to failure. This unit failed shortly after the July/2012 sample. Had this knowledge of a descending CO2/CO ratio been available at the time, there’s a good chance that this transformer would have been removed from service, repaired/processed and returned to service. It is worthy to note that NONE of the gases displayed would be considered a problem by any standard available today. Sure, there are times when a transformer has reached its end of life, but wouldn’t it be nice to at least see it coming? You may not be able to save every transformer, but you can position yourself to have better planning tools and possibly avoid an unexpected outage. It is believed that the March/2009 sample was either not properly collected or work was performed on the unit, which drives home the point that when manual sampling is performed, always take great care to ensure all outside influences are mitigated while collecting the sample as well as maintaining good maintenance records. This transformer was manufactured in the 1960s. Transformers do eventually find their end of life.
20
15 MVA, 100 kV – Manufactured 1999 – Pre-Fault
Date H2 O2 CO2 CO CH4 C2H6 C2H4 C2H2 CO2/CO 2011 <2 845 579 8 5 6 2 <1 72.3 2012 831 524 4 1 104.8 2013 509 226 3 75.3 2014 1092 178 29.6 2015 500 124 10 12.4 83% Drop
21
15 MVA, 100 kV – Manufactured 1999 - Post-Fault
H2 O2 CO2 CO CH4 C2H6 C2H4 C2H2 CO2/CO 2015 <2 500 124 10 <1 1 12.4 2016 post fault 212 802 1188 414 210 72 372 422 2.8 77% Drop in 1 Year
22
1999, 15 MVA, 100 kV, Complete Picture
Date H2 O2 CO2 CO CH4 C2H6 C2H4 C2H2 CO2/CO 2011 <2 845 579 8 5 6 2 <1 72.3 2012 831 524 4 1 104.8 2013 509 226 3 75.3 2014 1092 178 29.6 2015 500 124 10 12.4 2016 post fault 212 802 1188 414 210 72 372 422 2.8 96% Drop
23
Analyzing Events via CO2/CO
In this example, the large increase in C2H6 that occurred in 2013 was accompanied by a similar increase in CO while CO2 exhibited a downward trend during this time, leading to a sharp decrease in the CO2/CO ratio. This method of analyzing the relationship that occurs between the carbon oxide gases and the generation of hot metal gases is not as consistent as the trending of the CO2/CO ratio over a given period of time. However, it has proven quite useful in situations such as a transformer trip event where large amounts of combustible gases are subject to being produced in a very short time frame. This is a very good example of the importance of maintaining historical data. Without it, the sharp decrease in the CO2/CO ratio may go unnoticed, depending on the impact of the event. With historical data in hand, it is easily compared with the established trend, thereby allowing a more accurate diagnosis of the impact on the paper. For example, during this particular event in 2013: CO2 = 1850 ppm CO = ppm Ratio = 9:1 This single ratio, in and of itself, really doesn’t tell us much. In fact, this ratio may be considered normal by many. However, when compared to the previous sample in 2011: CO2 = 2136 ppm CO = ppm Ratio = 101:1 As you can see, this became a 91% drop during the 2013 event, indicating a major amount of paper involved in the event. Without this insight, the analyst may be inclined to return the unit to service without further investigation, and the consequences of these actions could be catastrophic.
24
Acetylene Is Problematic, But Is It Fatal?
Not always: Is it present due to activity in the winding insulation, or is it bare metal? The problem could be easy to get to and simple to repair. Transformers have been discarded when the problem was a simple fix, but that was unknown at the time. It can mean the difference between a few thousand dollar$ in repairs, versus a few million dollar$ in potential replacement costs. Acetylene is obviously not a gas that we’d like to see in a power transformer’s main tank regardless of where the problem is. Having said that, it is important to be in a position to know whether or not it is present as a result of an issue in the main winding insulation, or perhaps a connection away from the windings. One is most assuredly fatal, while the other may be repairable on site.
25
Summary/Conclusion All internal faults are not fatal.
Know your fleet. It will only be beneficial in solving the diagnostic puzzles as they present themselves. All faults are not as easily identified. Don’t give up, as there is an answer. Allow software help with the data analysis and direct you to the critical assets and information, which are now available. Trending the fluctuations of gas concentration, rate of change and ratios is very important for understanding your transformers’ vital signs. Know when to reach out for additional support, if needed. We are all in this together.
26
Questions?
Similar presentations
© 2025 SlidePlayer.com. Inc.
All rights reserved.