Povezava procesnega elementa v eksplozijsko ogroženem okolju Janez Kokalj, univ.dipl.inž. ELSING Inženiring, d.o.o. Ljubljana
2
“EExi – lastna varnost”
Oblika protieksplozijske zaščite: “EExi – lastna varnost” Ex okolje Varno okolje Varnostna bariera – pridružen element Transmiter – lastnovaren element Krmilnik IOUT Zalito RS UOUT UZ UN PA Markings Current and voltage are limited - even when a fault occurs. If the voltage on the non-I.S. side of the barrier rises above the highest admissible value due to a fault in the instrumentation room, the zener diodes limit the voltage for the I.S. circuit to the zener voltage (plus tolerance) Uz, the zener diodes conducting an increasing current. Since the current-carrying capacity of the zener diodes is limited, a fuse is included before the diode. If a short-circuit occurs on the I.S. side, resistor Rs limits the short-circuit current to the maximum safety value Im = Uz / Rs. Maximum power at output Pmax = 1/4 ( Uout x Iout ), values Uout and Iout are the already known maximum voltage and current that can pass through the barrier to the I.S. side in no-load or short-circuit condition. Usually, the designations Uz and Im will be used instead of the otherwise common designations Uo and Ik. Series resistance RL tends to interfere with normal operation, usually being higher than the resistance Rs taken into account for current limitation. This is because the resistance of the fuse is not taken into consideration from a safety perspective. An additional connection to earth is required (because of the absence of galvanic isolation). Many safety barriers of differing electrical construction are available. 28
3
Klasični način povezave
Prednosti enostavnost za določene oblike instrumentacije edina možna rešitev varnost Pomanjkljivosti množica kablov, splonk, barier
4
Dislociran sistem Prednosti
malo kablov med Ex in varnim okoljem, malo sponk, barier enostavnost uporabe Pomanjkljivosti razen o procesni veličini ne zvemo nič drugega od procesnega elementa diagnostika le za RIO postaje Ex
5
Dislociran sistem (RIO) - primer
6
Lastnosti procesnih vodil
PLC/DCS Prednosti več informacij močna diagnostika Pomanjkljivosti nova in nepoznana tehnologija dražji procesni elementi več različnih standardov omejitve v Ex okolju glede prenosa moči
7
Pregled nekaterih procesnih vodil
8
HART Hibridna zgradba Hitrost samo 1,2 kbit/s Lastna varnost „Exi“
4-20 mA in komunikacija FSK modulacija Hitrost samo 1,2 kbit/s Lastna varnost „Exi“ Multidrop (le teoretično) 4 mA samo za napajanje FSK = frequency shift keying Multidrop = več porabnikov na skupnem vodilu (Bus)
9
Standard medija IEC Velja za Foundation Fieldbus H1 in Profibus PA: hitrost: kbit/s max dolžina kabla: 1900 m brez repeaterja lahko obstoječi kabli za 4-20 mA moč in podatki na isti parici komunikacija: moduliranje bazičnega toka s +-9mA primerno za Ex okolja, Exi interface zahtevan napetost: tip. 24 V DC (specialni napajalniki) procesni elementi: 9-32 V / 10 mA max. štev. procesnih elementov (omejitev standarda): 31 max. štev. procesnih elementov (omejitev zaradi Exi): 4 do 6 terminator: 100 Ohm + 1 uF
10
Dostop do vodila (Profibus)
logični krog pošiljanja med master postajami activne postaje, master PC PLC PLC Profibus pasivne postaje (slave), ki jih kliče master
11
Dostop do vodila (Foundation Fieldbus)
Urnik prenosa Urnik a b c LAS Fizični medij 2. DL(a) 1. CD(x,a) Element x Element y Element z a b c a d a P S P S P S LAS = Link Active Scheduler / urnik dovoljenja pošiljanja P = Publisher / ponudnik S = Subscriber / naročnik DL = Data Link Packet / Prenos podatkovnega paketa CD = Compel Data / Proženje prenosa
12
Kateri način je najboljši?
realna arhitektura H2 DI / DO
13
FuRIOS: primerjalna študija med procesnim vodilom in RIO
Referenčni objekt: Kemična sinteza v farmaciji, Aventis, Frankfurt, 2002: 369 merilnikov in aktuatorjev s 821 I/O točkami realiziran z RIO naknadna študija o posledicah uporabe procesnih vodil Vključeni proizvajalci opreme: ABB, Emerson, Endress+Hauser, Camile Bauer, Honeywell, Pepperl+Fuchs, Samson, Siemens, Wika
14
PROFIBUS PA Profibus-PA komunikacija, realizirana z Exi napajalniki ali z barierami v coni 1
15
FuRIOS: primerjalna študija med procesnim vodilom in RIO
Rezultati študije: Prednosti procesnih vodil odpadejo I/O moduli enostavnejše projektiranje enostavnejša izvedba programske opreme zveznim merilnikom ni potrebno nastavljati merilnih območij (npr. 0-5bar /4-20mA) več podatkov
16
FuRIOS: primerjalna študija med procesnim vodilom in RIO
Rezultati študije: Prednosti RIO cenejša obdelava on/off signalov (končna stikala, krmiljenje on/off ventilov) tudi RIO omogočajo digitalno komunikacijo z analognimi procesnimi elementi - HART večja razpoložljivost procesnih elementov z analognimi signali napram s procesnimi vodili višji nivo zahtevane varnosti celotnega sistema (SIL – Safety Integrity Level po IEC 61508)
17
Integracija različnih komunikacij
Ethernet TCP/IP Krmilnik Profibus DP Remote I/O Segment coupler PROFIBUS-PA HART naprave mA naprave
18
Povezava procesnega elementa v eksplozijsko ogroženem okolju Janez Kokalj, univ.dipl.inž. ELSING Inženiring, d.o.o. Ljubljana