Presentation is loading. Please wait.

Presentation is loading. Please wait.

This webinar brought to you by the Relion® product family

Similar presentations


Presentation on theme: "This webinar brought to you by the Relion® product family"— Presentation transcript:

1 This webinar brought to you by the Relion® product family
Relion. Thinking beyond the box. Designed to seamlessly consolidate functions, Relion relays are smarter, more flexible and more adaptable. Easy to integrate and with an extensive function library, the Relion family of protection and control delivers advanced functionality and improved performance.

2 ABB Protective Relay School Webinar Series
Disclaimer ABB is pleased to provide you with technical information regarding protective relays. The material included is not intended to be a complete presentation of all potential problems and solutions related to this topic. The content is generic and may not be applicable for circumstances or equipment at any specific facility. By participating in ABB's web-based Protective Relay School, you agree that ABB is providing this information to you on an informational basis only and makes no warranties, representations or guarantees as to the efficacy or commercial utility of the information for any specific application or purpose, and ABB is not responsible for any action taken in reliance on the information contained herein. ABB consultants and service representatives are available to study specific operations and make recommendations on improving safety, efficiency and profitability. Contact an ABB sales representative for further information.

3 Bus Protection Fundamentals
ABB Protective Relay School Webinar Series Bus Protection Fundamentals Jack Chang July 12, 2016

4 Presenter Jack Chang is the regional technical manager for ABB Inc. in the Substation Automation Products BU supporting customers in Canada. He provides engineering, commissioning and troubleshooting support to customers applying ABB’s high-voltage protective and automation devices. Prior to joining ABB, Jack worked as a substation P&C project engineer in two specialized consulting firms (now ABB and Quanta Services, respectively) and also as an engineering consultant to a public owned utility in their transmission expansion and upgrade projects. Jack is a registered professional engineer in the province of Alberta, Canada. Jack Chang ©ABB November 13, 2018November 13, 2018

5 Learning objectives Types of bus configurations
Current transformer characteristics and their effect on bus protection Types of bus protection schemes Modern Numerical Bus Protection Features Questions: ©ABB November 13, 2018November 13, 2018

6 Why bus protection? Different configuration and design
Usually very robust, high current faults Need to clear quickly for internal faults and stays stable for external faults. A Delayed bus trip or a mis-trip could lead to: Network instability pole slip of nearby generators Possible system collapse Bigger fault related damages & risk to human life or injury Many bus faults caused during maintenance (eg. Arc flash) ©ABB November 13, 2018November 13, 2018

7 Bus fault protection Easy to detect because of robust nature
Easy to protect for internal faults (87B) Summation of currents not equal to zero for internal fault External faults can cause current transformer saturation which results in unwanted differential currents Infrequent, but must be cleared with high speed for internal fault and stable for external faults Substation is well shielded Protected environment ©ABB November 13, 2018November 13, 2018

8 Bus configurations Single bus Main and transfer bus
Double bus, single breaker Double bus, double breaker Breaker and a half Ring bus ©ABB November 13, 2018November 13, 2018

9 Single bus ©ABB November 13, 2018November 13, 2018

10 Main and transfer bus With this bus configuration any breaker can be taken out of service for maintenance without disrupting the electrical supply via the transfer bus. ©ABB November 13, 2018November 13, 2018

11 Double bus single breaker
Typically seen in GIS SWGR Flexible, transfer and balance load to either bus Easy to schedule maintenance Lots of feeders, seen mainly in big industrial plants and utility distribution stations Some types of dynamic zone switching scheme must be in place (modern low impedance bus differential IEDs) ©ABB November 13, 2018November 13, 2018

12 Double bus, double breaker
Each link protected by two circuit breakers. Most expensive but reliable and flexible. Dedicated bus protection each of two main bus bars ©ABB November 13, 2018November 13, 2018

13 Breaker and one half Typically seen in HV/EHV transmission and major power plant switching stations, quite popular in North America Each link protected by 1.5 breaker so to speak. Dedicated bus protection each of two main bus bars Bus stubs are located in the line/transformer/reactor zones and no dedicated bus protection required. ©ABB November 13, 2018November 13, 2018

14 Ring bus Popular in North America (72, 138, 230 KV). Cheaper design than 1-1/2. same number of links as the number of breaker. less reliable. Usually no dedicated bus bar protection as the bus stubs are in the zones of line/transformer/reactor etc with redundant A/B All bus protection zones should be overlapped ©ABB November 13, 2018November 13, 2018

15 Main-Tie-Main Most popular for MV (15, 25 KV) small industrial/utrility distribution systems Dedicated bus diff. for each bus if so designed blocking scheme via communciation Some types of bus transfer scheme may be designed ©ABB November 13, 2018November 13, 2018

16 Some issues Availability of overlapping protection zones (CTs)
Blind or end zone protection Will loads or sources be switched from one bus to the other Current transformer switching from one zone to another Open circuit current transformers CT Saturation ©ABB November 13, 2018November 13, 2018

17 Zones of protection Station B Station A Station C Station D G G G
Bus protection Station D M ©ABB November 13, 2018November 13, 2018

18 Zones of protection CT for Green Zone CT for Blue Zone Green Zone
Dead tank breaker, two CTs A overlapping set of CTs across the tie breaker poses no problem to a energized bus. Bus fault beside the CT and Breaker when the breaker is normally closed : no problem. Fault can be cleared by relays operating in both protection zones However, when the breaker is already in open position, it would be unnecessary for Blue zone to operate. There is a solution to avoid over-tripping the blue zone - To avoid over tripping with breaker operated normally open, logics can be made to remove the two CTS to the bus relay when the breaker is open ©ABB November 13, 2018November 13, 2018

19 Zones of protection CT for Green Zone CT for Blue Zone Green Zone
Live tank breaker, single CT Blue zone will operate for this fault and trip all breakers in the zone, including this tie breaker, but Green relay is restrained. Even though the blue zone is cleared, the fault is still persisting. Local breaker failure protection (blue zone) could be used to initiate back-up tripping if time delay is acceptable. Very rare in likelihood of occurrence There is a solution for this type of “under-tripping” scenario. The correct solution is to “disconnect” the two CTs to both relays when the breaker is open. This will speed up the tripping. If the breaker is operated normally open, logic can be made to disconnect the CTs to avoid over-tripping (blue) and under-tripping (Green) ©ABB November 13, 2018November 13, 2018

20 Current Transformers: Equivalent circuit of a CT
November 13, 2018

21 Ratings of concern for bus protection
Current transformer Ratings of concern for bus protection Ratio: 200/5, 1200/5, …500/1 Burden capability: VA burden Accuracy Class: C800, K200, T400 Knee point, saturation voltage (can be derived from chart in C class CTs) CT availability IEEE Standard C (R2003), IEEE Standard Requirements for Instrument Transformers IEEE Standard C , IEEE Guide for the Application of Current Transformers Used for Protective Relaying Purposes Accuracy Definition: For relaying CTs, ANSI/IEEE defines a limit of 10 percent for the ratio error for a steady-state, symmetrical (no dc offset) secondary current equal to 20 times rated secondary current at the standard rated burden C: Leakage flux neglegiable. Eg. Multi-ratio bushing, window type CTs. CT Excitation chracteristic can be used to determine CT performance T: CT ratio error must be derived from test. CT transient behavior must take into account the system X/R ratio (dc offset, deteriorating) and remnant flux (derate rated votlage). Simply size CT according to the steady-state rating is not sufficient to avoid saturation, ©ABB November 13, 2018November 13, 2018

22 Steady State Performance of CT
VB – Burden voltage KS – a measure of how close to saturation for a given application. Used in time to saturate calc. VSM – saturation voltage at 20 time rated secondary current at 10% error (10A exciting current) Vx – rated CT voltage, voltage rated across the burden with 10% error and 20 times rated CT current without driving the CT into Saturation VK – CT Knee point voltage is the voltage at the point where the tangent to the curve (on log-log axes) is at 45 degrees to the abscissa

23 ANSI current transformer accuracy class
Example 1200/5 C800 This current transformer will deliver 800 volts on its secondary when it is connected to a standard burden and 20 times rated current is flowing in the primary winding without exceeding 10% ratio error. ©ABB November 13, 2018November 13, 2018

24 Standard chart for class C current transformers
ANSI accuracy class Standard chart for class C current transformers ©ABB November 13, 2018November 13, 2018

25 CT saturation CT core may reach saturation flux density due to a combination of dc offset in the fault current, with possibility remnant flux (20-80%, no way to predict, but can be erased by demagenatizing) The output current suddenly changes from a proportional signal to zero DC saturation depends on system time constant (X/R)- large close to generating stations secondary burden ©ABB November 13, 2018November 13, 2018

26 CT saturation CT secondary model
a perfect current source in parallel with an exciting impedance branch that drives proportional current Exciting impedance is normally very high At saturation, exciting impedance drops to a very low value the CT appears short-circuited neither delivers nor resists current flow Time to saturation is important in low impedance bus protection ©ABB November 13, 2018November 13, 2018

27 Issues effecting bus protection selection
Bus arrangement Fixed Switchable Availability and characteristics of current transformers Performance requirements Speed Dependability Security Sensitivity (for high impedance grounded system) ©ABB November 13, 2018November 13, 2018

28 Types of bus protection
Differential Differentially connected overcurrent Percentage-restrained differential (low Z) High impedance differential Partial differential Zone interlocked scheme Back up schemes (eg. remote over-reaching zones) ©ABB November 13, 2018November 13, 2018

29 Differentially connected over-current relay
51 The OC element must be set to overcome any CT Steady State measurement error plus margin and is does not deal very well with CT saturation. ©ABB November 13, 2018November 13, 2018

30 TOTAL OUT OF BUS MINUS IE
External fault case Protected Bus = FAULT LOCATION IE IT TOTAL OUT OF BUS MINUS IE TOTAL INTO BUS TOTAL OUT OF BUS Relay Id = IE IE is the exciting current loss due to slight CT saturation in high external fault level ©ABB November 13, 2018November 13, 2018

31 Internal fault case Protected Bus I1 I2 I3 I4 Id Id = I1+ I2 + I3 + I4

32 Overcurrent relay bus differential
Application OK if: Symmetrical CT secondary current less than 100 Burden less than rated Typical pickup setting IPU > 10A Trip delay greater than 3 x primary time constant (L/R) Protected bus Id Essentially the CT must have matching characteristics and stringent sizing requirement to avoid saturation. If a 50 speed is desired, then the pick up set point must be above all possible CT measuring errors (less sensitive). No built-in protection to CT transient behavior ©ABB November 13, 2018November 13, 2018

33 Multiple restraint Percentage Differential (Legacy)
PROTECTED BUS A B C D RESTRAINT R,S AND T ARE COILS All circuits have 10 Amp contribution Restraint = 60 Operate = 0 R S 10 10 10 30 Net restraint (0) T (20) 20 20 (40) ONLY ONE PHASE SHOWN OPERATE COIL External fault example – 4 circuit connection This is how the restraint feature was implemented in legacy bus differential relays. ©ABB November 13, 2018November 13, 2018

34 Multiple restraint Percentage Differential (Legacy)
PROTECTED BUS A B C D RESTRAINT R,S AND T ARE COILS All circuits have 10 Amp contribution Restraint = 0 Operate = 40 R S 10 10 10 10 Net restraint (0) T (0) 20 20 (0) ONLY ONE PHASE SHOWN 40 OPERATE COIL Internal fault example – 4 circuit connection ©ABB November 13, 2018November 13, 2018

35 Torque for typical multi-restraint relay
Operating Torque Two Restraint One Restraint Amperes ©ABB November 13, 2018November 13, 2018

36 Torque for typical multi-restraint relay
55 A. of restraint overcomes 7 A of operating current with one restraint winding Operating Two Restraint Torque One Restraint 7 55 Amperes A certain current restraint can overcome a certain amount of operating torgues. Similar to the modern numerical restraint-operating current characteristics shown in slopes. ©ABB November 13, 2018November 13, 2018

37 Multi-restraint percentage differential
Good sensitivity Good security Allows other relays on the same CT core Different CT ratios with Aux CTs. Slow compared to high impedance Number of feeders limited by restraint windings Each CT is wired to relay Not easily extendable ©ABB November 13, 2018November 13, 2018

38 High impedance bus protection
High resistor (R > 1500 ohm) in series with relay coil and a MOV to prevent over-voltages High voltage develops for internal faults. lower Voltage will develop on external faults under ct saturation Voltage unit must be set higher than the maximum junction point voltage for any external fault The lowest achievable sensitivity must verified for the application Proven reliability and very sensitive Operating times of less than one cycle for internal faults R Depending on the relay design the stablizing resistor and metal oxide varistor (MOV) may locate in anther hardware, requiring space and external wiring Some applications connect 86 lockout relay contact in parallel with the relay coil and MOV to further limit the duration of over-voltages during fault. ©ABB November 13, 2018November 13, 2018

39 High impedance bus protection
EXTERNAL FAULT - SECURITY Setting VR > (IF / N ) ( RL +R S) K = margin factor IF = Max external fault current RS = Ct secondary resistance RL = Lead resistance to junction box N = ct turns ratio INTERNAL FAULT - SENSITIVITY IM I N = (XIE + IR + IV ) N X = number of circuits IE = Ct exciting current at VR IR = resistor current at VR IV = Varistor current at VR R > 1500 W Assuming a completely saturated CT B to calculate VR (the operating voltage) and minimum operating current. IE can normally be read off the CT excitation curve with one exception. IV (current through MOV) can normally be ignored for operating voltage < 1000 V. If CT B is only partially or minutely saturated, then the developed VR = I2 x (RL + RCT) -VE (CT exciting voltage) – , which will be smaller. ©ABB November 13, 2018November 13, 2018

40 High impedance bus protection
Criteria to be met Objective: Keep VR and Imin low Ct secondary loop resistance kept low Impedance from junction point to relay is of no consequence so good practice to parallel the CTs as close to the CTs as possible. Theoretically no limitations in the number of parallel CTs but sensitivity reduced with each parallel connection Setting VR higher that the CT rated voltage (400V for C400 CTs) will produce errors when estimating CT exciting branch current, hence inaccurate sensitivity calculation. All cts must have the same ratio and magnetizing characteristics ©ABB November 13, 2018November 13, 2018

41 Differential comparator (Legacy, Static type)
RADSS/REB103 Developed to lessen restrictions imposed by high impedance All CT secondary circuits connected via interposing cts Connection made using a special diode circuit producing rectified incoming, outgoing and differential currents IIN IOUT SR AUX CTs IDIFF DR ©ABB November 13, 2018November 13, 2018

42 Differential comparator
Single phase connection IIN is sum of all feeder instantaneous positive values IOUT is sum of all feeder instantaneous negative values IDIFF = IIN - IOUT AUX CTs Start IDIFF VOp IOUT VRes Trip IIN ©ABB November 13, 2018November 13, 2018

43 Differential comparator
Internal X L1 L2 L3 L4 X External External Internal ©ABB November 13, 2018November 13, 2018

44 Differential comparator
Single phase connection IDIFF is typically small (normally 0) for external fault and restraint voltage, VRes, is greater than operating voltage, VOp. IDIFF is typically large for an internal fault and operating voltage, VOp, is greater than restraining voltage, VRes. This produces voltage across trip relay. AUX CTs Trip / LO Start Start IDIFF VOp Trip IOUT VRes Trip IIN ©ABB November 13, 2018November 13, 2018

45 Numerical differential comparator
Analog input currents are instantaneously sampled and quantized to numerical number Similar technique to legacy differential comparator, but with measured sampled data Secondary circuit loop resistance no longer a critical factor Critical factor is time available to make the measurement, i.e. time to saturation. (only 3ms required to properly restrain for heavy external faults) Algorithms for Ct saturation Detection and CT state supervision ©ABB November 13, 2018November 13, 2018

46 Differential comparator
All measurement decisions based on three quantities IDIFF - difference of input current and output current (IDIFF = IIN - IOUT) IIN - total input current S - % differential setting IDIFF > S x IIN e.g. for setting S=50%, differential current  50% of incoming current before operation ©ABB November 13, 2018November 13, 2018

47 Differential comparator
Characteristic can be shown in a typical operate-restraint chart ©ABB November 13, 2018November 13, 2018

48 Differential comparator
Advantages over high impedance differential Lower ct requirements Allows much higher ct loop resistances Accommodate different CT ratios / auxiliary CTs Fast operating times for internal faults Detects internal ms Before ct saturation ©ABB November 13, 2018November 13, 2018

49 Quick operation for internal fault
REB 670 detects that I_IN goes up while I_OUT goes down at the beginning of the internal fault and enables fast tripping When ID>Diff Operation Level trip is issued Small i: samples Capital I: Phasors ©ABB November 13, 2018November 13, 2018

50 Proper & secure restrain during external fault
REB 670 detects this short interval when i_in=i_out (after every fault current zero crossing) and restrain properly during external fault REB 670 detects that I_IN=I_OUT at the beginning of the external fault Iin = Iout for a short duration before CT saturation, eg. CT saturation detection. The relay restrains properly. ©ABB November 13, 2018November 13, 2018

51 fulfilled & REB is blocked
Fast open CT algorithm REB 670 detects that I_IN doesn't change while I_OUT goes down when some of the CTs is open/short circuited ID>Open CT Level second condition fulfilled & REB is blocked Diff Operation Level Must be set to higher value than Open CT Level The relay notices the trend and locus of these points and then makes the decision. The relay sees normal load conditions for 500msec and then sees a sudden drop in the current. ©ABB November 13, 2018November 13, 2018

52 Other Features in Modern Numerical Bus IEDs
Each device capable of connecting multiple bays (eg. CTs) in 3- ph or 1-ph design Multiple differential zones, dynamic bay switching, zone interconnection, and check zone logic External fault/CT saturation detection, open CT detection algorithms Blind zone protection (see next 2 slides) End zone protection (see next 2 slides) Backup protection (eg. 50/51, 50BF) for each connected bay Modern substation automation communication (DNP 3.0, IEC61850) ©ABB November 13, 2018November 13, 2018

53 Blind zone detection for bus coupler bays
Blind zone between live tank CT and breaker Fault strikes in the blind zone Tie bkr normally closed: ZA operates but Zone B restrains -> the fault is persisting Tie bkr normally open: ZA operates unnecessarily and ZB restrains Solution: connect BKR NC (open) status to the bay to remove the tie CT from ZA, ZB (software) ZA will then restrain and ZB operates properly for the blind zone fault ©ABB November 13, 2018November 13, 2018

54 Blind zone detection for feeder bays
Regions not overlapped by both red and blue boundaries are blind zones CTs are used for both feeder and bus protection measurement (live tank CTs) Common in HV 1-1/2 stations For 3. measuring CT can be removed (BBP) to avoid over-tripping on open pos. Fast OC set up to DTT (open pos) For 4. measuring CT can be removed (BBP) to force tripping on open pos (feeder protection operates first) Similar to the previous slide the over-tripping and under-tripping zones are shown together for illustration purposes. I do not reckon anyone would design a bus configuration this way. The measuring and fault clearing boundary will typically be symmetric for a bus system. ©ABB November 13, 2018November 13, 2018

55 Other distribution (MV) bus protection methods
Partial differential Blocking on feeder fault ©ABB November 13, 2018November 13, 2018

56 Partial differential Seen more in a main-tie-main bus configuration where you can connect the incoming source CT and the tie CT in a partial differential circuit to isolate the two bus bar. The fault on each bus bar and feeder circuits can be protected selectively. It also reduces the amount of coordination required. In this case, multiple sources are bounded together and must coordinate with downstream protection. This reduces the number of relays needed and coordination requirement. ©ABB November 13, 2018November 13, 2018

57 Blocking scheme For MV or LV systems equipped with arc flash protection or arc flash not a concern (eg. GIS), no dedicated bus differential is really needed. This type of blocking scheme can provide relatively fast bus bar protection, if necessary. ©ABB November 13, 2018November 13, 2018

58 Conventional Blocking Scheme
Zone of protection T+100 ms 100 ms I> I>> blocking Traditional busbar protection based on upstream blocking Dedicated hard-wire signal paths needed Signal path delay needs to be considered, input and output delay + auxiliary relays Changes in the protection scheme may require re- wiring Typical needed delay in incoming relay is over 100 ms Delay setting with inst. O/C protection (conventional approach) Safety marginal, e.g. delay in operation due to CT saturation. 20…40 ms O/C protection start delay + output relay’s delay <40 ms Start delay with receiving relay + retarding time for the blocking signal *) ALL TOGETHER 100…120 ms Now we will shortly go though one example of using GOOSE in one protection schema Blocking based busbar protection Outgoing feeders sends over copper-wire a blocking signal to incoming feeder if there is fault in the line A certain delay introduced due to the delays between IEDs

59 Blocking Scheme with IEC-61850 GOOSE
Yes I am! I’ll block the Inst. O/C! Block-PHIPTOC! Delay setting with inst. O/C protection (REF615 GOOSE approach) Safety marginal, e.g. delay in operation due to CT saturation. 20…40 ms O/C protection start delay 20 ms Retardation time of inst. O/C stage blocking 5 ms GOOSE delay (Type 1A, Class P1) <10 ms ALL TOGETHER 55…75 ms IEC Who is interested? PHLPTOC-start! When same schema is done with GOOSE blocking signal is sent over the Ethernet based station bus to incoming feeder Faster communication between IEDs due to the missing I/O output and input delays More protection scheme examples are shown in 615 series presentations

60 Bus protection comparison chart
COST EASE OF USE SENSI- TIVITY DEPEND ABILITY SECURITY FLEXI- BILITY SPEED SIMPLE OVER-CURRENT LOW GOOD POOR MULTIPLE RESTRAINT MED BEST HIGH IMPEDANCE FAST PERCENTAGE RESTRAINED DIFFERENTIAL HIGH PARTIAL DIFFERENTIAL BLOCKING ©ABB November 13, 2018November 13, 2018

61 Questions? Recommended reading
ANSI C Guide for Protective Relay Applications to Power system Buses ©ABB November 13, 2018November 13, 2018

62 Thank you for your participation
For more information on ABB’s protection and control solutions, visit: Please subscribe to our YouTube channel to view recorded webinars and technical training © ABB Group November 13, 2018November 13, 2018

63


Download ppt "This webinar brought to you by the Relion® product family"

Similar presentations


Ads by Google