Download presentation
Presentation is loading. Please wait.
1
University of Virginia
PID Controllers Gang Zhou University of Virginia February 2006
2
Outline I Control: Integral Control
PI Control: Proportional-Integral Control PD Control: Proportional-Derivative Control PID Control: Proportional-Integral-Derivative Control Summary
3
Introducing I Control What is wrong with P control?
Non-zero steady-state error Prove it A real CS case See p259
4
Introducing I Control What is I control?
The controller output is proportional to the integral of all past errors
5
Steady-State Error with I Control
Start from Example 9.1: the IBM Lotus Domino Server
6
More General The steady-state error of a system with I control is 0, as long as the close-loop system is stable.
7
The steady-state error due to disturbance
8
Transient Response with I Control
I Control eliminates the steady-state error, but it slows the system down The reason is the added open-loop pole 1, which generates a close-loop pole that is usually close to 1. Example 9.2: Closed-loop poles of the IBM Lotus Domino Server
9
Example 9.2 (continue) Observe the root locus
The largest closed-loop pole is always closer to the unit circle than the open-loop pole 0.43. Ask Ting why Fig 9.2 (a) has root locus, since it has only one pole and has no K. --- It is a P controller by default.
10
Example 9.3 Disturbance Rejection in the IBM Lotus Domino Server
11
Example 9.4 Moving-average filter plus I control
A moving average slows down the system responses An I control also slows down the system response So the combination leads to undesirable slow behavior Example: IBM Lotus Domino server + I control + Moving-average filer The settling time will be very long, here greater than 78.
12
Moving-average filter vs. I controller
An I controller works like a moving-average filter: More response to sustained change in the output than a short transient disturbance An I controller drives the steady-state error to 0, but the moving-average filter does not.
13
PI Control
14
Steady-state Error with PI Control
PI has a zero steady-state error, in response to a step change in the reference input It also holds for the disturbance input
15
PI Control Design by Pole Placement
Design Goals: Assumption: G(z) is a first-order system A higher-order system is approximated by a first-order system (chapter 3) Equation 3.30 in Chapter 3
16
PI Control Design by Pole Placement
Approaches: Step 1: compute the desired closed-loop poles Step 2,3,4: find the P control gain and I control gain Step 5: Verify the result Check that the closed-loop poles lie within the unit circle Simulate transient response to assess if the design goals are met
17
PI Control Design by Pole Placement
Example 9.5: Consider the IBM Lotus Domino server
18
Example 9.5 (continue)
19
Example 9.5 (continue) P control leads to quicker response
I control leads to 0 steady-state error
20
PI Control Design Using Root Locus
The new issue: The root locus allows only one parameter to be varied A PI controller has two parameters: The P control gain, and the I control gain Solution to this issue: Determine possible locations of the PI controller’s zero, relative to other poles and zeros For each relative location of the zero, draw the root locus For the most promising relative locations, try a few possible exact locations Simulate to verify the result
21
PI Control Design Using Root Locus
Example 9.6: PI control using root locus
22
Example 9.6 (continue)
23
Example 9.6 (continue) P control leads to quicker response
I control leads to zero steady-state error
24
CHR Controller Design Method
The bump test is in page 310
25
CHR Controller Design Method
26
CHR Controller Design Method
Example 9.7:
27
Example 9.7 (continue) No simulation is needed to verify it. Why?
- Only one option in the table
28
D Control A Real CS Example:
An IBM Lotus Domino server is used for healthy consulting. (MaxUsr, RIS) Bird flu happens in this area. More and more people request for the service. More and more hardware is added to the server. So the reference point keeps increasing. To deal with the increasing reference point, do we have better choices than P/I control? How about setting the control output proportional to the rate of error change?
29
D Control D Control: the control output is proportional to the rate of change of the error D control is able to make an adjustment prior to the appearance of even larger errors. D control is never used alone, because of its zero output when the error remains constant. The steady-state gain of a D control is 0.
30
PD Control The 0 pole is at page 317
31
PD Control PD controllers are not appropriate for first-order systems because pole placement is quite limited PD controllers can be used to reduce the overshoot for a system that exhibits a significant amount of oscillation with P control Example: consider a second-order system
32
Example (continue)
33
Example (continue) It is real good It sounds good
34
Example (continue)
35
Example (continue)
36
PID Control
37
PID Control PI controllers are preferred over PID controller
D control is sensitive to the stochastic variations A low-pass filter can be applied to smooth the system output. In that case, the D control only responds to large changes But the filter slows down the system response PID Control Design by Pole placement Compute the dominant poles based on the design goals Compute the desired characteristic polynomial Compute the modeled characteristic polynomial Solve for the gains of the P, I and D control by coefficient matching Verify the result PI controllers are preferred over PID controllers --- in the second paragraph in page 323
38
PID control design by pole placement
Example 9.8: Consider the IBM Lotus Domino Server
39
Example 9.8 (continue)
40
Example 9.8 (continue)
41
Summary I control adjust the control input based on the sum of the control errors Eliminate steady-state error Increase the settling time D control adjust the control input based on the change in control error Decrease settling time Sensitive to noise P, I and D can be used in combination PI control, OD control, PID control
42
Summary (continue) Pole placement design Root locus design
Find the values of control parameters based on a specification of desired closed-loop properties. Root locus design Observe how closed-loop poles change as controller parameters are adjusted Empirical method: The values of control parameters can be determined by empirical methods based on the step response of the open-loop system
Similar presentations
© 2025 SlidePlayer.com. Inc.
All rights reserved.