Determination of harmonic emission: problem of higher frequencies
Paper 32 & 37 of session 2: determination of a customer emission level Algorithms are very sensitive to measurement precision (magnitude and angle harmonics)
2
Harmonic emission of network user with 2 arc furnaces connected in 150 kV network
Estimation of the source impedance Zs with method Re(DV/DI) described in paper s2-32: good results until 5th harmonic Customer impedance Zc was determined by simulation (= impedance of filter installations) Approach described in paper s2-37 to determine the dominant factor was applied
3
125 Hz
4
250 Hz
5
Question to the authors
What is the experience of the authors with the application of the described approaches in practical circumstances at higher harmonics orders (above 500 Hz – frequency response VT’s & CT’s in magnitude and angle)?