Download presentation
Presentation is loading. Please wait.
Published byTamsin Powell Modified over 6 years ago
1
NEMA RV 3 Application & Installation Guidelines For Flexible & Liquid Tight Flexible Metal Conduits
2
Application Guidelines for FMC
Construction of FMC Grounding and Bonding Uses Permitted and Not Permitted
3
Construction for FMC Constructed in accordance with NEC
Complies with safety requirements of UL1 Interlocked corrosion resistant steel or Aluminum strip
4
Picture Example for FMC
5
Diagram Example for FMC
Cross-section view illustrating interlocking construction
6
Grounding and Bonding for FMC
Permitted for bonding When installed with listed fittings and; Flexibility is not required after installation and; When installed according to NEC Articles 348 and 250 and; Protected by overcurrent device rated 20 Amperes or less. Limited to 6’ lengths when used for bonding (see NEC (5)) Grounding conductor required if FMC installed for flexible equipment or when used in lengths greater than 6’. Grounding and bonding continued in slide 7…
7
Product Marking for FMC
Manufacturer’s designation UL Logo Conduit type Reduced wall (RW) Extra reduced wall (XRW) Material type Aluminum (AL) Steel (No Mark Required)
8
FMC Marking Example
9
Uses Permitted for FMC Exposed and concealed locations – NEC 348.10
Dry locations only Branch circuits and feeders Ducts or plenums for environmental air 300.22(B) limits to 4’ length 300.22(C) no length limit Under raised floors for computer rooms Lighting whips and motor leads These uses are not all inclusive, but serve as guidelines
10
Uses Not Permitted for FMC
NEC Wet locations 2008 NEC removed exceptions Hoistways except as permitted in (A)(1) Storage battery rooms
11
Uses Not Permitted – cont. for FMC
Hazardous locations except (B) and Where conductors are exposed to deteriorating material Underground or in concrete Where subject to physical damage
12
Reference Articles Reference UL 1 and NEC
NEMA RV – National Electric Code NEMA RV – Related NEC Articles NEMA RV – UL Standards Guide information page: White book “Guide Information for Electrical Equipment”
13
Application Guidelines for LFMC
Construction of LFMC Grounding and Bonding Marking Uses Permitted and Not Permitted
14
Construction for LFMC In accordance with NEC
Complies with safety requirements of UL360 Interlocked zinc-coated corrosion resistant steel Trades sizes are 3/8” through 4” Sizes 3/8” – 1 ¼” have bonding strip enclosed by convolution
15
Construction – cont. for LFMC
Jacket material is liquid-tight, non metallic Jacket specifications governed by UL 360 Fittings for LFMC are constructed to UL 514B
16
Picture example for LFMC
Cut-away view of Liquidtight Flexible Metal Conduit to illustrate construction
17
Diagram Example for LFMC
Cross-section view illustrating interlocking construction
18
Grounding and Bonding for LFMC
LFMC trade sizes 3/8” – 1 ¼” permitted for equipment bonding: When installed with listed fittings and; Flexibility is not required after installation and; When installed according to NEC Articles 350 and 250 and; Only in 6’ lengths or less Sizes 3/8” – 4” may be installed in unlimited lengths provided: A separate grounding conductor is installed And installed according to NEC Articles 350 and 250
19
Surface Print for LFMC Manufacturer’s name or location Trade size
Temperature rating Burial rating (when applicable) Flame rating (when applicable) Current rating (for equipment bonding according to NEC article 250)
20
Uses Permitted for LFMC
Exposed and concealed locations as follows: When flexibility or protection from liquids, vapors or solids are required As permitted by (B), , and Other hazardous classified locations per 553.7(B) Direct burial where listed & marked for that purpose If LFMC is marked direct burial it is also suitable for use in concrete or in poured concrete The following are references throughout the NEC code:
21
Uses Permitted –cont. for LFMC
Outside branch circuits and feeders Under raised floors for computer rooms Lighting whips and motor leads These uses are not all inclusive, but serve as guidelines References throughout the NEC Code:
22
Uses Not Permitted for LFMC
Where subject to physical damage Where operating conditions cause temperatures to exceed material ratings See NEC for prohibited uses
23
Reference Articles for LFMC
NEMA RV – National Electric Code NEMA RV – Related NEC Articles NEMA RV – UL Standards Guide information page: White book “Guide Information for Electrical Equipment”
24
Installation Guidelines
Installation Considerations Securing & Supporting FMC & LFMC Terminating FMC
25
Installation Considerations for FMC & LFMC
Minimum centerline bend radius Table 2 chapter 9 NEC “Other bends” column Maximum # of bends between pull points Not to exceed (4) - 90 degree bends Or a total of 360 degrees (any direction)
26
Lateral Offsets Use tables for length Lateral offset Example below
Offset Table 2 3/4" Trade Size 0.75 "B" (in.) "R" Offset Distance (in.) 7 7.6 8 8.3 8.7 9 9.2 9.5 9.8 10 10.2 10.4 10.6 11.0 11 11.1 11.3 11.5 11.8 12 12.1 12.2 12.4 12.7 13.0 13 13.1 13.2 13.4 13.6 13.8 14.4 14 14.1 14.2 14.3 14.5 14.7 15.3 15 15.1 15.2 15.5 15.6 16.1 16.7 20 20.0 20.1 20.2 20.3 20.4 20.7 21.2 21.7 22.9 24.4 25 25.0 25.1 25.2 25.3 25.6 25.9 26.2 27.2 28.3 30 30.0 30.1 30.2 30.4 30.7 31.0 31.7 32.7 Overall Length of Conduit for Given Offset and Lateral Distance Lateral Dist. 1.0 1.5 2 2.5 3.0 4.0 5.0 6.0 8.0 10.0
27
Vertical Loop Vertical loop w/offset L=(8xTS)+(1.57xA) +T/2+F
L = Overall length TS = Trade size A = Horizontal dist between fittings T = Travel distance F = Offset This accounts for suggested tangent length
28
Installation Considerations – cont. for FMC & LFMC
Fittings should be tightened properly Section 3.3, tables 1 and 2 of NEMA guidelines for proper torquing values Closely follow manufacturer's instructions
29
Securing & Supporting FMC & LFMC
According to NEC & Both must be supported and secured every 4.5’ or less Must be secured within 12” of each termination These support requirements are waived if needed for flexibility or for luminaries
30
Securing & Supporting – cont. for FMC & LFMC
Both may be unsupported when: Conduit is fished between access points through concealed spaces in finished buildings or structures and supporting is impractical Flexibility is required 3’ maximum for LFMC 3’ maximum for FMC ½” through 1¼” 4’ maximum for FMC 1½” through 2” 5’ maximum for FMC 2½” and larger Used on luminaries; 6’ maximum Run through non-vertical framing members with distances not exceeding 4½’
31
Terminating FMC Fitting Selection requires knowing:
Trade size or metric designator Type of FMC, (standard, reduced or extra-reduced wall) Type of metal (steel or aluminum)
32
Conduit Preparation for FMC & LFMC
Square the cut end of the metal conduit Insert conduit flush with fitting end stop Ensure seating of clamp on conduit before torquing Be careful torquing the securement screw Always follow the manufacturer's instructions Follow recommendations from NEMA FB 2.20, “Selection and Installation guidelines for Fittings for use with Flexible Conduit and Cable”
33
Cutting Conduit for FMC
Rotary armor cutters Hacksaw Cut one convolution at a 60 degree angle Diagonal wire cutters Brake the conduit or twist open Then cut with the cutters
34
Cutting Conduit for LFMC
Hacksaw Blade should have 32 teeth per inch Band saw with ½” X .025 Blade with 24 teeth per inch at 350 ft/min
35
Fitting Attachment for FMC
Always make sure the conduit is inserted completely to the smooth end stop When using a clamp type fitting, be sure the fitting seats between the convolutions Hand tighten the fitting screws and slightly rotate the conduit in the fitting If there are two screws, tighten alternately to provide even pressure. Table 1 in NEMA RV 3 shows standard torque values for FMC fittings
36
Terminating for LFMC Fitting Selection requires knowing:
Trade size or metric designator The environment of installation Conduit preparation Square the end of the conduit Fully insert conduit to end stop Ensure jacketing is not cut or ripped Always follow the manufacturers instructions Follow recommendations from NEMA FB 2.20, “Selection and Installation guidelines for Fittings for use with Flexible Conduit and Cable”
37
Fitting Attachment for LFMC
Squared end must be fully inserted into ferrule Assembly methods vary for LFMC fittings, follow manufacturer's instructions Table 2 in NEMA RV 3 show standard torque values for LFMC fittings
38
Unthreaded Entries Hand tighten the threaded portion of fitting to secured box using a locknut Assemble nut, gland and ferrule onto conduit After securely tightening the gland nut to the threaded body, finish tightening the locknut ¼ turn
39
Fitting Example
40
Verification of Installation
Conduit shall be properly terminated at boxes Conduit shall be properly secured and supported Conduit shall not show evidence of damage or physical abuse
Similar presentations
© 2024 SlidePlayer.com. Inc.
All rights reserved.