Presentation is loading. Please wait.

Presentation is loading. Please wait.

CONSTRUCTION BS 60598 (BS 4533) K.F. Chan (Mr.) MEBS 6002.

Similar presentations


Presentation on theme: "CONSTRUCTION BS 60598 (BS 4533) K.F. Chan (Mr.) MEBS 6002."— Presentation transcript:

1 CONSTRUCTION BS (BS 4533) K.F. Chan (Mr.) MEBS 6002

2 PROTECTION AGAINST ELECTRIC SHOCK
K.F. Chan (Mr.) MEBS 6002

3 IP RATING – 1st digit K.F. Chan (Mr.) MEBS 6002

4 IP RATING – 2nd digit K.F. Chan (Mr.) MEBS 6002

5 IP symbols K.F. Chan (Mr.) MEBS 6002

6 IP65 luminaire K.F. Chan (Mr.) MEBS 6002

7 K.F. Chan (Mr.) MEBS 6002

8 Classification according to supporting surface material
K.F. Chan (Mr.) MEBS 6002

9 Shatter proof high bay luminaire
K.F. Chan (Mr.) MEBS 6002

10 Safety chain for shatter proof luminaire
K.F. Chan (Mr.) MEBS 6002

11 FLAMMABLE ATMOSPHERES
ZONE 0 – explosive gas/air mixture continuously present ZONE 1 – explosive gas/air mixture likely to occur in normal operation ZONE 2 – explosive gas/air mixture not likely to occur in normal operation K.F. Chan (Mr.) MEBS 6002

12 ZONE 0 EEx ‘ia’ intrinsically safe
EEx ‘s’ special protection (specifically certified for use in zone 0), e.g. factory sealed handlamp, completely encapsulated lighting fittings K.F. Chan (Mr.) MEBS 6002

13 ZONE 1 those suitable for zone 0 EEx ‘p’ Pressurized system
EEx ‘d’ Flameproof EEx ‘e’Increased safety, e.g. cold starting fluorescent tubular lamps with single pin caps, tungsten filament lamps for GLS, mixed lights EEx ‘ib’ Intrinsically safe K.F. Chan (Mr.) MEBS 6002

14 ZONE 2 those suitable for zone 0 and zone 1 EEx ‘o’ oil immersion
EEx ‘q’ sand filling EEx ‘n’ non-sparking K.F. Chan (Mr.) MEBS 6002

15 APPARATUS (GAS) GROUP Group 1 Mines susceptible to firedamp (methane)
Group II Places with a potentially explosive atmosphere, other than Group I mines, e.g. ethylene is gas group IIB. Refer to EN50014 for details K.F. Chan (Mr.) MEBS 6002

16 TEMPERATURE CLASS Ignition temperature is the lowest temp at which the most explosive mixture of the given substance and air will just ignite at a heated surface T1 – 450oC T2 – 300oC T3 – 200oC T4 – 135oC T5 – 100oC T6 – 85oC Refer to BS4683 Part 1 K.F. Chan (Mr.) MEBS 6002

17 Example – ammonia plant room
EEx ‘d’ Apparatus Group IIA, T1 temperature class, IP44 K.F. Chan (Mr.) MEBS 6002

18 EEXd IP66 luminaire K.F. Chan (Mr.) MEBS 6002


Download ppt "CONSTRUCTION BS 60598 (BS 4533) K.F. Chan (Mr.) MEBS 6002."

Similar presentations


Ads by Google