Download presentation
Presentation is loading. Please wait.
1
R4 Troubleshooting Refrigeration
R4 Troubleshooting Refrigeration - Subject 1 Compressor Problems v1.1 11/24/2018 R4 Troubleshooting Refrigeration #1 Compressors Problems © 2004 Refrigeration Training Services No reproduction or unauthorized use allowed
2
Common Causes of Compressor Failures
R4 Troubleshooting Refrigeration - Subject 1 Compressor Problems v1.1 11/24/2018 Common Causes of Compressor Failures Liquid slugging Floodback Flooded start Overheating © 2004 Refrigeration Training Services - R4 Subject 1 Compressor Problems v1.2 © 2004 Refrigeration Training Services No reproduction or unauthorized use allowed
3
Liquid Slugging “Slug” of liquid on piston head
Breaks valves, pistons, rods, and crankshafts Compressors cannot compress liquid © 2004 Refrigeration Training Services - R4 Subject 1 Compressor Problems v1.2
4
Slugging: broken suction valves
R4 Troubleshooting Refrigeration - Subject 1 Compressor Problems v1.1 Slugging: broken suction valves 11/24/2018 LIQUID If a large slug of liquid is drawn through the suction port, the mass and inertia of the liquid will drive the tip of the reed against the reed stop. The strain can eventually bend or break the tip. © 2004 Refrigeration Training Services - R4 Subject 1 Compressor Problems v1.2 © 2004 Refrigeration Training Services No reproduction or unauthorized use allowed
5
Slugging: broken discharge reed valves
R4 Troubleshooting Refrigeration - Subject 1 Compressor Problems v1.1 11/24/2018 During the compression stroke, the slug of refrigerant liquid oil is driven through the discharge port. That may be with such force that the reed may be broken, the backer bent, or hold down bolts broken or stripped. Discharge reed valve snapped off here © 2004 Refrigeration Training Services - R4 Subject 1 Compressor Problems v1.2 © 2004 Refrigeration Training Services No reproduction or unauthorized use allowed
6
Slugging: gaskets & broken crankshafts
R4 Troubleshooting Refrigeration - Subject 1 Compressor Problems v1.1 11/24/2018 Crankshaft Sheared off Due to the tremendous hydraulic force generated by slugging, gaskets can blow. Also, connecting rods and crankshafts can be bent or broken. Blown Gasket © 2004 Refrigeration Training Services - R4 Subject 1 Compressor Problems v1.2 © 2004 Refrigeration Training Services No reproduction or unauthorized use allowed
7
Floodback Liquid droplets in suction vapor Air cooled compressors:
Washes lubricant from cylinder walls Suction cooled compressors: Washes lubricant from crankshaft © 2004 Refrigeration Training Services - R4 Subject 1 Compressor Problems v1.2
8
Picture of piston worn by lack of lubrication
R4 Troubleshooting Refrigeration - Subject 1 Compressor Problems v1.1 11/24/2018 Floodback: Air Cooled Compressor Picture of piston worn by lack of lubrication This is one of the pistons from that compressor. Even though it ran for only a few hours and no slugging noise was heard, the results are obvious. The washing action of the liquid refrigerant removed the oil from the surfaces allowing metal to rub directly on metal. Washed away cylinder lubrication © 2004 Refrigeration Training Services - R4 Subject 1 Compressor Problems v1.2 © 2004 Refrigeration Training Services No reproduction or unauthorized use allowed
9
Picture of crankshaft damaged by flooding
Floodback: Suction Cooled Compressors R4 Troubleshooting Refrigeration - Subject 1 Compressor Problems v1.1 11/24/2018 Picture of crankshaft damaged by flooding Oil Pump End Lots of Damage Motor End Some damage The diluted oil contains enough refrigerant to reduce the volume of oil available for bearing lubrication. As the refrigerant boils off in the drive train, the shortage of oil results in a progressive wear pattern that gets worse as you move farther from the oil pump. The most severe damage will be present at the bearings closest to the motor. No damage © 2004 Refrigeration Training Services - R4 Subject 1 Compressor Problems v1.2 © 2004 Refrigeration Training Services No reproduction or unauthorized use allowed
10
Picture: motor burn from bearing damage by flooding
R4 Troubleshooting Refrigeration - Subject 1 Compressor Problems v1.1 Flooding: Suction Cooled Compressor 11/24/2018 Picture: motor burn from bearing damage by flooding Burnout from electrical problem? No. Flooding damaged bearing Rotor dropped As the motor end bearings wear significantly, the crankshaft will drop, causing the rotor to drag on the stator. That will result in a shorted or burned motor. If the compressor is not examined after it fails, the cause of the motor failure will remain unknown. Hit stator, causing burnout. © 2004 Refrigeration Training Services - R4 Subject 1 Compressor Problems v1.2 © 2004 Refrigeration Training Services No reproduction or unauthorized use allowed
11
Slugging and Flooding - Causes and Cures
1. Low evaporator load Causes Space temperature too low Air flow / dirty coil problems Cures Operate at design temperatures Proper airflow and clean evaporators 2. Metering device problems Cause Flooding evaporator Cure Maintain proper superheat © 2004 Refrigeration Training Services - R4 Subject 1 Compressor Problems v1.2
12
Diagnosing suction line frost
What does it mean? Floodback? Slugging? Low on charge? Frost means: The suction line is below 32° You must determine IF there is a problem © 2004 Refrigeration Training Services - R4 Subject 1 Compressor Problems v1.2
13
Picture: Floodback on Med. Temp compressor
R4 Troubleshooting Refrigeration - Subject 1 Compressor Problems v1.1 11/24/2018 Picture: Floodback on Med. Temp compressor Not good Floodback on Medium Temperature Compressor Many times liquid refrigerant can return to a compressor in small enough quantities that the heat of compression will vaporize the liquid and no noise will be heard. This picture shows an air cooled compressor in our lab with a metered amount of liquid refrigerant being fed into the suction line. The quantity fed was increased until noise was heard. The compressor was then disassembled for inspection. Did any damage result? Yes. Keep in mind, frost on a suction line and compressor does not mean liquid. © 2004 Refrigeration Training Services - R4 Subject 1 Compressor Problems v1.2 © 2004 Refrigeration Training Services No reproduction or unauthorized use allowed
14
Picture: frost on freezer compressor
R4 Troubleshooting Refrigeration - Subject 1 Compressor Problems v1.1 11/24/2018 Picture: frost on freezer compressor Freezer compressor: problem or not? Suction line: 0°F Suction pressure: 16 psig R404A -20°F Superheat: 0 - (-20°) = +20° This compressor may appear to have liquid refrigerant returning. However, the return line, when proper analysis is completed, is actually operating with 10°F superheat. The actual line temperature is -30°F. The saturated refrigerant temperature equivalent is -40°F; therefore, no liquid can be present. Is there a problem? NO © 2004 Refrigeration Training Services - R4 Subject 1 Compressor Problems v1.2 © 2004 Refrigeration Training Services No reproduction or unauthorized use allowed
15
Flooded Start During “off-cycle”: During start-up:
Refrigerant vapor migrates to coldest spot Vapor condenses to liquid in crankcase Liquid refrigerant sinks under compressor oil During start-up: Liquid under the oil “explodes” within crankcase Dilutes oil on crankshaft bearing surfaces © 2004 Refrigeration Training Services - R4 Subject 1 Compressor Problems v1.2
16
Refrigerant Migration
R22 (vapor) migrates to compressor oil R4 Troubleshooting Refrigeration - Subject 1 Compressor Problems v1.1 Compressor Start-up Compressor is OFF 11/24/2018 Refrigerant Migration This slide shows the refrigerant migrating to the oil and laying under the oil in the crankcase of the compressor. The more refrigerant under the oil the higher the level of the oil. If the rod caps or crankshaft hits the oil it could damage the compressor. OIL R22 © 2004 Refrigeration Training Services - R4 Subject 1 Compressor Problems v1.2 © 2004 Refrigeration Training Services No reproduction or unauthorized use allowed
17
Refrigerant Migration
R22 (vapor) migrates to compressor oil R4 Troubleshooting Refrigeration - Subject 1 Compressor Problems v1.1 Compressor Start-up 11/24/2018 Foaming refrigerant and oil is pulled out of the crankcase Refrigerant Migration This slide shows the refrigerant migrating to the oil and laying under the oil in the crankcase of the compressor. The more refrigerant under the oil the higher the level of the oil. If the rod caps or crankshaft hits the oil it could damage the compressor. OIL R22 © 2004 Refrigeration Training Services - R4 Subject 1 Compressor Problems v1.2 © 2004 Refrigeration Training Services No reproduction or unauthorized use allowed
18
Picture: crankshaft damaged by flooded start
R4 Troubleshooting Refrigeration - Subject 1 Compressor Problems v1.1 Evidence of Flooded Start 11/24/2018 Picture: crankshaft damaged by flooded start Scored surface The random pattern will result in damage to the bearing surface with no damage to the bearings on either side. The damage cannot be explained by oil flow. A good, bad, good, bad sequence will be present. Normal wear Normal wear Random pattern of damage © 2004 Refrigeration Training Services - R4 Subject 1 Compressor Problems v1.2 © 2004 Refrigeration Training Services No reproduction or unauthorized use allowed
19
R4 Troubleshooting Refrigeration - Subject 1 Compressor Problems v1.1
Crankcase heater 11/24/2018 How do we prevent flooded starts? Install crankcase heater (See accessories section) Or, pump-down solenoid (See valve section) © 2004 Refrigeration Training Services - R4 Subject 1 Compressor Problems v1.2 © 2004 Refrigeration Training Services No reproduction or unauthorized use allowed
20
Compressor Overheating
High heat causes lubrication breakdown Parts seize Carbon deposits form: On valve plates Clog filter-driers © 2004 Refrigeration Training Services - R4 Subject 1 Compressor Problems v1.2
21
Picture: carbon deposits on valves & plates
R4 Troubleshooting Refrigeration - Subject 1 Compressor Problems v1.1 Overheating: Carbon deposits on valves and plates 11/24/2018 Picture: carbon deposits on valves & plates The most obvious effect of overheating is the breakdown of oil and carbonization at the discharge reed and discharge side of the valve plate. The valve plate shown here has a carbon build up due to oil breakdown. Note the copper plating of the valve seating surfaces. Copper plating is a byproduct of heat as are moisture and carbon. © 2004 Refrigeration Training Services - R4 Subject 1 Compressor Problems v1.2 © 2004 Refrigeration Training Services No reproduction or unauthorized use allowed
22
Picture: drier clogged with carbon deposits
R4 Troubleshooting Refrigeration - Subject 1 Compressor Problems v1.1 Overheating: Carbon deposits in filter-driers 11/24/2018 Picture: drier clogged with carbon deposits The creation of carbon deposits can also plug dryers as shown here. © 2004 Refrigeration Training Services - R4 Subject 1 Compressor Problems v1.2 © 2004 Refrigeration Training Services No reproduction or unauthorized use allowed
23
Picture: piston rings damaged by heat
R4 Troubleshooting Refrigeration - Subject 1 Compressor Problems v1.1 Overheating: Oil breaks down, parts seize 11/24/2018 Picture: piston rings damaged by heat The hottest point of the compressor is the discharge valve port. Just below that is the the top of the piston and the cylinder walls. The heat generated here heats the walls faster than the suction vapor can cool the area. The heat thins the oil allowing metal to metal contact. The result is worn pistons, cylinder walls, and rings if the compressor has rings like the ones shown here. The wear has two main results affecting compressor operation. © 2004 Refrigeration Training Services - R4 Subject 1 Compressor Problems v1.2 © 2004 Refrigeration Training Services No reproduction or unauthorized use allowed
24
Compressor Overheating - Causes and Cures
1. High condensing temperatures Causes Low air flow / dirty condenser Overcharge / non-condensables Cures Check fans / clean condenser Verify proper condenser split / subcooling 2. High discharge temperatures Cause Lack of cool refrigerant / high superheat Cure Maintain proper superheat Keep suction pressures up © 2004 Refrigeration Training Services - R4 Subject 1 Compressor Problems v1.2
25
Inside View of Valve and Gasket Problems
The following 4 slides describe: Bad discharge valve From overheating or liquid slugging Worn piston or rings From overheating or floodback Broken suction valve From liquid slugging Blown head gasket © 2004 Refrigeration Training Services - R4 Subject 1 Compressor Problems v1.2
26
R4 Troubleshooting Refrigeration - Subject 1 Compressor Problems v1.1
Bad Discharge Valve 11/24/2018 Downstroke can’t open suction valve Refrigerant not moving Low side pressures start to rise Compressor can’t pump High pressure drops Causes: 1. Overheating 2. Slugging As the piston nears the bottom of its stroke, the pressure difference in the cylinder will not be low enough to keep the suction reed down and it will close the suction port. Thus we should recognize that the suction port is open for only a portion of the suction stroke of the piston. © 2004 Refrigeration Training Services - R4 Subject 1 Compressor Problems v1.2 © 2004 Refrigeration Training Services No reproduction or unauthorized use allowed
27
R4 Troubleshooting Refrigeration - Subject 1 Compressor Problems v1.1
Worn Piston or Rings 11/24/2018 Discharge gas “blows by” piston Discharge gas enters low side Compressor can’t pump Low side pressures rise High pressure drops Causes: 1. Overheating 2. Floodback As the piston nears the bottom of its stroke, the pressure difference in the cylinder will not be low enough to keep the suction reed down and it will close the suction port. Thus we should recognize that the suction port is open for only a portion of the suction stroke of the piston. © 2004 Refrigeration Training Services - R4 Subject 1 Compressor Problems v1.2 © 2004 Refrigeration Training Services No reproduction or unauthorized use allowed
28
R4 Troubleshooting Refrigeration - Subject 1 Compressor Problems v1.1
Discharge gas enters suction Broken Suction Valve 11/24/2018 Compressor can’t pump Low side pressures rise High pressure drops Cause: Liquid Slugging As the piston nears the bottom of its stroke, the pressure difference in the cylinder will not be low enough to keep the suction reed down and it will close the suction port. Thus we should recognize that the suction port is open for only a portion of the suction stroke of the piston. © 2004 Refrigeration Training Services - R4 Subject 1 Compressor Problems v1.2 © 2004 Refrigeration Training Services No reproduction or unauthorized use allowed
29
R4 Troubleshooting Refrigeration - Subject 1 Compressor Problems v1.1
Discharge gas enters suction Blown Gasket 11/24/2018 Low side pressures rise High pressure drops Cause: Liquid Slugging As the piston nears the bottom of its stroke, the pressure difference in the cylinder will not be low enough to keep the suction reed down and it will close the suction port. Thus we should recognize that the suction port is open for only a portion of the suction stroke of the piston. © 2004 Refrigeration Training Services - R4 Subject 1 Compressor Problems v1.2 © 2004 Refrigeration Training Services No reproduction or unauthorized use allowed
30
End of Compressor Troubleshooting
© 2004 Refrigeration Training Services - R4 Subject 1 Compressor Problems v1.2