Protection IED platform, product release 1
AQ 200 series Protection IED platform, product release 1
2
AQ 200 series – first release products
AQ F201 – Overcurrent and earth-fault relay AQ F210 – Feeder protection IED AQ M210 – Motor protection IED AQ V211 – Voltage protection IED AQ F215 – Feeder protection IED AQ M215 – Motor protection IED AQ S214 – Alarm and indication IED AQ S215 – Bay control IED
3
AQ 200 series – key benefits
Genuinely modular software and hardware platform Logistics benefits for stocking, replacement, upgrades and maintenance Reduced life cycle cost in terms of training, engineering, operation and spare parts Application specific productization
4
AQ 200 series – key benefits cont.
Performance Powerful 3 CPU system - separation of protection, I/O and communication tasks 64 samples per cycle sampling rate Instant protection operation time typically <20ms 60MB memory allocated for DR and user files >100 disturbance records in Flash memory > events in Flash memory
5
AQ 200 series – key benefits cont.
Wide measurement ranges Operating frequency band of 6…75Hz Phase current measurement range from10mA to 250A Coarse residual current I01 measurement range from 1mA to 150A Fine residual current I02 measurement range from 0.1mA to 75A Voltage measurement 0-460V (RMS) Protection algorithms’ design Versatile setting alternatives Harmonic overcurrent stage based on 2nd / 3rd / 4th / 5th / 7th harmonic Compensated cable-end differential protection Integrated arc protection Fast operation times
6
AQ 200 series – key benefits cont.
Measurement accuracy Class 0.2 over frequency range of 6-75Hz !! Conventional measurement Arcteq patented frequency tracking algorithm Measurement error with fixed 50Hz sampling frequency when frequency changes. Constant current of 5A, frequency sweep from 6 Hz to 75 Hz Measurement error with frequency tracking when frequency changes. Constant current of 5A, frequency sweep from 6 Hz to 75 Hz
7
Sensitive cable end differential protection
Normal measurement without compensation Fault seen by IED, with compensated measurement Proactive protection!
8
AQ 200 series – key benefits cont.
Superior usability Easy to use and simple to set Large customizable HMI with full language support and clear indication windows Extensive log information including complete user history register (e.g. setting change tracking) Downloading of files to relay memory (commissioning report, manual…)
9
AQ 200 series – common characteristics
5 CT inputs as standard 3 phase currents (1/5 amps software settable) Io1 (1/5A software settable) Io2 (0.2/1A software settable) Wide setting ranges 0.1…40 x In (phase overcurrent) 0.005…40 x In (earth-fault) DT, IEC or ANSI time/overcurrent curves with settable release delays 8 setting groups available Freely software settable digital input threshold voltage Measurement of up to 31st harmonic and THD Measurement accuracy %
10
AQ 200 series – common characteristics cont.
Logic programming On-line indication of active/de-active signals Program cycle 5ms for fast protection logic 16 programmable LEDs MIMIC display with up to 5 controllable devices IEC 61850, IEC 103 and Modbus protocols as standard (DNP 3 and IEC 101/104 and SPA under development) AQtivate 200 freeware software suite for all settings and configuration AQview freeware software for disturbance recorder analyzing
11
AQ 200 series – AQtivate 200 software suite
Free of charge Easy to use Ethernet connection to IED On-line / Off-line modes Clear Menu structure Instant download of settings All IED settings < 1 second Logic programming feature Templates / macros MIMIC Diagram Communication parameters AQview software module for disturbance recorder analysis
12
AQ 200 series - modular platform
13
AQ 200 series – modern platform
Computing power designed for needs far ahead Modern high-performance multi-CPU system
14
AQ 200 series Modern R&D environment
Developed algorithms are thoroughly tested and optimized in development phase in PC environment. Child diseases can be found in very early phase. Function development from idea to product is extremely fast.
15
AQ 200 series Easy and modern HMI - Custom displays
- User editable menus - Local language - Consistent and modern HMI and PC tools
16
AQ 200 series Easy and modern HMI Large freely configurable display
System LED:s 4 (fixed function) 16 user programmable LED:s Direct CB control Local Ethernet port for PC programming Local panel HMI buttons for setting and using the relay
17
AQ 200 series – applications
Feeder protection and control Arc protection Motor protection and control Alarm annunciation & I/O extension Bay control Transformer protection Generator protection Power monitoring etc.
18
AQ F201 – Overcurrent and earth-fault relay
3 stages o/c (50/51) 3 stages e/f (50/51N) REF, high-impedance (87N)* 1 Neg. seq. balance stage (46) 1 Harmonic overcurrent stage (50/51h) CBFP (50BF) 3 Digital inputs 6 Output relays RJ 45 and RS 485 comms Modbus, IEC 103 protocols * Requires external resistors (e.g. Metrosil)
19
AQ F210 – Feeder protection IED
4 stages o/c (50/51) 4 stages e/f (50/51N) REF low or high*-impedance (87N) or cable end differential protection 4 Neg. seq. balance stages (46) 4 Harmonic overcurrent stages (50/51h) Cable thermal protection (49) Autoreclose (79) CBFP (50BF) 3 Digital inputs (standard) 6 Output relays (standard) RJ 45 and RS 485 comms (standard) IEC 61850, Modbus, IEC 103 protocols Optionally available: 4 xI/O card slots (8DI / 5DO / 2xfiber Ethernet / arc protection) * Requires external resistors (e.g. Metrosil)
20
AQ M210 – Motor protection IED
4 stages o/c (50/51) 4 stages e/f (50/51N) 4 Neg. seq. balance stages (46) 4 Harmonic overcurrent stages (50/51h) Cable end differential protection Motor thermal protection (49M) Locked rotor / start-up supervision (48) Speed switch (14) Frequent starts (66) Undercurrent (37) Mechanical jam (51M) CBFP (50BF) 3DI (standard) 6DO (standard) RJ 45 and RS 485 comms (standard) IEC 61850, Modbus, IEC 103 protocols Optionally available: 4xI/O card slots (8DI / 5DO / 2xfiber Ethernet / arc protection)
21
AQ V211 – Voltage protection IED
4 stages overvoltage (59) 4 stages undervoltage (27) 4 stages residual overvoltage (59N) 8 stages over/under frequency (81U/O) CBFP (50BF) Fuse failure (60) 3DI (standard) 6DO (standard) RJ 45 and RS 485 comms (standard) IEC 61850, Modbus, IEC 103 protocols Optionally available: 5xI/O card slots (8DI / 5DO / 2xfiber Ethernet)
22
AQ F215 – Feeder protection IED
4 stages o/c (50/51) 4 stages e/f (50/51N) 4 stages directional o/c (67) 4 stages directional e/f (67N) REF low or high*-impedance (87N) or cable end differential protection 4 Neg. seq. balance stages (46) 4 Harmonic overcurrent stages (50/51h) Cable thermal protection (49) 4 stages overvoltage (59) 4 stages undervoltage (27) 4 stages residual overvoltage (59N) 8 stages over/under frequency (81U/O) Autoreclose (79) CBFP (50BF) 3 Digital inputs (standard) 6 Output relays (standard) RJ 45 and RS 485 comms (standard) IEC 61850, Modbus, IEC 103 protocols Optionally available: 3 xI/O card slots (8DI / 5DO / 2xfiber Ethernet / arc protection) * Requires external resistors (e.g. Metrosil) Feeder management with full measurements
23
AQ M215 – Motor protection IED
4 stages o/c (50/51) 4 stages e/f (50/51N) 4 stages directional e/f (67N) 4 Neg. seq. balance stages (46) 4 Harmonic overcurrent stages (50/51h) Cable end differential protection Motor thermal protection (49M) Locked rotor / start-up supervision (48) Speed switch (14) Frequent starts (66) Undercurrent (37) Mechanical jam (51M) 4 stages overvoltage (59) 4 stages undervoltage (27) 4 stages residual overvoltage (59N) 8 stages over/under frequency (81U/O) CBFP (50BF) 3DI (standard) 6DO (standard) RJ 45 and RS 485 comms (standard) IEC 61850, Modbus, IEC 103 protocols Optionally available: 3xI/O card slots (8DI / 5DO / 2xfiber Ethernet / arc protection) Motor management with full measurements
24
AQ S214 – Alarm and indication IED
5 controllable objects 16 programmable LEDs Non-volatile event records Logic programming 3DI (standard) 6DO (standard) RJ 45 and RS 485 comms (standard) IEC 61850, Modbus, IEC 103 protocols Optionally available: 6xI/O card slots (8DI / 5DO / 2xfiber Ether.) Alarm annunciation and I/O extension
25
AQ S215 – Bay control IED Measurements (I, U, P, Q ,S, pf, E+ ,E-)
Fuse failure (60) CT supervision Auto-reclose (79) 5 controllable objects 16 programmable LEDs Non-volatile event records Logic programming 3DI (standard) 6DO (standard) RJ 45 and RS 485 comms (standard) IEC 61850, Modbus, IEC 103 protocols Optionally available: 3xI/O card slots (8DI / 5DO / 2xfiber Ether.)
26
AQ 200 series CPU CPU card with basic IO. This configuration will be always available for any IED. COM A RJ-45 Ethernet based communications COM B RS-485 Serial based communications 1 DI_1 Input group 1 digital input no. 1, Name in relay DI_1 2 DI_2 Input group 1 digital input no. 2, Name in relay DI_2 3 DI_3 Input group 1 digital input no. 3, Name in relay DI_3 4 DI_comm GND Common ground for CPU card digital input group 5 Control 1 Control binary out contact NO 6 7 Control 2 8 9 Control 3 10 11 Control 4 12 13 Control 5 Control binary out contact changeover NO/NC 14 15 16 SF_Indication System fault binary out contact changeover NO/NC 17 18 19 Aux_voltage Auxiliary voltage input. Two possible variations. 24…80 V AC/DC and 80…265 V AC/DC 20 GND IED grounding
27
AQ 200 series CT card
28
AQ 200 series DI8 option card
29
AQ 200 series D05 option card
30
AQ 200 series Versatile IO
31
AQ 200 series Versatile IO AQ-X210-AAAA AQ-X213-BEC (future)
AQ-X213-BEA (future) AQ-X215-AAA (future) AQ-X213-AAA (future) AQ-X213-BAA (future)
32
AQ 200 series Products of the platform
Example of X215 and X235 hardware
33
AQ 200 series Thank You