Smitty’s Two Minute Drill #1: Feeders and Branch Circuits
A drill to help you improve your code skills and your ability to find answers in the code book. © Ted “Smitty” Smith 2016, 2017
2
Directions Left click on the presentation ICON located at the bottom of the slide directory to the left of the this slide. Each slide will transition to the correct answer automatically in 2:00 minutes. The correct answer will transition in 5 seconds. Do not worry about writing down the correct answer for now. You will have the opportunity to do that at the end of the two minute drill Good luck
3
Question 1 An outlet installed for the purpose charging electric vehicles shall be supplied by a ________________ branch circuit. This circuit shall have no other outlets. A. Listed B. Separate C. Multi-wire D. None of the above Copyright 2005 Ted "Smitty" Smith
4
Question 1 Answer B. Separate 210.17 Copyright 2005 Ted "Smitty" Smith
5
Question 2 Overhead conductors for festoon lighting shall not be small than ______ AWG unless the conductors are supported by messenger wires. A. 16 B. 14 C. 12 D. 10 Copyright 2005 Ted "Smitty" Smith
6
Question 2 Answer C. 12 225.6 (B) Copyright 2005 Ted "Smitty" Smith
7
Question 3 Tire inflation and automotive vacuum machines provided for public use shall be protected by a ____________________. A. Listed over current device rated at 125% of the full load current B. arc-fault circuit interrupter C. Duel element fuse rated at 80% of the full load current D. ground-fault circuit interupter Copyright 2005 Ted "Smitty" Smith
8
Question 3 answer D. Ground-fault circuit interupter 422.23
Copyright 2005 Ted "Smitty" Smith
9
Question 4 Loads for new circuits or extended circuits in other than dwelling units shall be calculated with ______________, as applicable. A. a #2 pencil and paper B. A scientific programmable calculator C. either or D. a derating factor of 75% or 80% Copyright 2005 Ted "Smitty" Smith
10
Question 4 Answer C. 220.12 or 220.14 220.16(B)
Copyright 2005 Ted "Smitty" Smith
11
Question 5 Branch circuits shall not be derived from autotransformers unless the circuit supplied has a grounded conductor that is ______________________ ___________________ _____ a grounded conductor of the system supplying the transformer. Sized larger than Noncontiguous electrically to Electrically connected to Separated completely from Copyright 2005 Ted "Smitty" Smith
12
Question 5 C. electrically connected to 210.9
Copyright 2005 Ted "Smitty" Smith
13
Question 6 What is the minimum height that the auxiliary equipment of electric discharge lamps can be mounted on poles for athletic fields if the voltage rating for the equipment is 600 volts? 10 feet 18 feet 22 feet 30 feet Copyright 2005 Ted "Smitty" Smith
14
Question 6 answer C. 22 feet 210.6(D)(1)(a)
Copyright 2005 Ted "Smitty" Smith
15
Question 7 High voltage conductors in tunnels shall be installed in metal conduit, other metal raceway or type _____________ cable. A. AC B. NM C. SO D. MC Copyright 2005 Ted "Smitty" Smith
16
Question 7 answer D. MC 110.53 Copyright 2005 Ted "Smitty" Smith
17
Question 8 Outdoor mobile home disconnecting means shall be installed so the bottom of the enclose containing the disconnecting means is not less than _________ above the finished grade or working platform. A. 2 feet B. 6 feet, 7 inches C. 10 feet D. 12 feet Copyright 2005 Ted "Smitty" Smith
18
Question 8 answer A 2 feet 550.32(F) Copyright 2005 Ted "Smitty" Smith
19
Question 9 Where the positive polarity of a dc system does not serve as the connection point for the grounded conductor, each positive ungrounded conductor shall be identified by:[ Select the answer that is incorrect.] A. a continuous red outer finish B. a continuous red stripe durably marked along the conductors entire length on insulation of a color other than green, white, gray or black C. a continuous red stripe durably marked marked along the conductors entire length on insulation of a color other green, white, or gray. D. imprinted plus signs (+) or the word POSITIVE or POS durably marked on insulation of a color other than green, white, gray or black. Copyright 2005 Ted "Smitty" Smith
20
Question 9 answer C. a continuous red stripe durably marked marked along the conductors entire length on insulation of a color other green, white, or gray. Missing that it can not be black wire 210.5(C) (2) (a) (1-3) Copyright 2005 Ted "Smitty" Smith
21
Question 10 Where connected to a branch circuit supplying two or more receptacles, a 20 ampere rated branch circuit shall be allowed to supply ______________ rated receptacles. A. 15 ampere receptacles B. 20 ampere receptacles C. Both A and B D. Neither A or B Copyright 2005 Ted "Smitty" Smith
22
Question 10 Answer C. Both A and C 210. 21 (B)(3)
Copyright 2005 Ted "Smitty" Smith
23
Question 11 The minimum feeder conductor size shall have an allowable ampacity not less than the maximum load to be served after the application of _________________________. A. any adjustment or correction factors. B. temperature derating adjustments in accordance with C. conduit fill derating corrections based on Table 5 D. continuous duty rating of loads based on Copyright 2005 Ted "Smitty" Smith
24
Question 11 Answer A. any adjustment or correction factors.
215.2(A)(1)(b) Copyright 2005 Ted "Smitty" Smith
25
Question 12 Vegetation such as trees may be used for support of overhead conductor spans if the attachment point is at least 8 feet above the ground and secured with a device listed for the purpose. A. True B. False Copyright 2005 Ted "Smitty" Smith
26
Question 12 Answer B. False 225.6 Copyright 2005 Ted "Smitty" Smith
27
Question 13 The grounded conductor for a service feeder shall not be smaller than the minimum size as required by ___________________. The authority having jurisdiction 250.24(C) The electrical engineer None of the above Copyright 2005 Ted "Smitty" Smith
28
Question 13 answer 250.24(C) 230.42(C)
Copyright 2005 Ted "Smitty" Smith
29
Question 14 The equipment branch of the Essential Electrical System of a health care facility shall be installed and connected to the alternate power source such that the equipment is automatically restored to operation at ________________. A. no more than 10 seconds from loss of power B. no more than 30 seconds from loss of power C. no more than 2 minutes from loss of power D. at appropriate time-lag intervals following the energizing of the essential electrical system. Copyright 2005 Ted "Smitty" Smith
30
Question 14 answer D. at appropriate time-lag intervals following the energizing of the essential electrical system. 517.34 Copyright 2005 Ted "Smitty" Smith
31
Question 15 At least one receptacle shall be installed at each peninsular countertop space with a long dimension of 24 inches or greater and short dimension of __________ inches or greater. A. 6 B. 9 C. 12 D. 18 Copyright 2005 Ted "Smitty" Smith
32
Question 15 Answer C. 12 210.52(C)(3)
Copyright 2005 Ted "Smitty" Smith
33
End of Drill Click on this slide to continue to the repeat of the questions. The timer will not operate in this section. Click on each slide to advance. Review the questions and look up the answers. Copyright 2005 Ted "Smitty" Smith
34
Question 1 An outlet installed for the purpose charging electric vehicles shall be supplied by a ________________ branch circuit. This circuit shall have no other outlets. A. Listed B. Separate C. Multi-wire D. None of the above Copyright 2005 Ted "Smitty" Smith
35
Question 1 Answer B. Separate 210.17 Copyright 2005 Ted "Smitty" Smith
36
Question 2 Overhead conductors for festoon lighting shall not be small than ______ AWG unless the conductors are supported by messenger wires. A. 16 B. 14 C. 12 D. 10 Copyright 2005 Ted "Smitty" Smith
37
Question 2 Answer C. 12 225.6 (B) Copyright 2005 Ted "Smitty" Smith
38
Question 3 Tire inflation and automotive vacuum machines provided for public use shall be protected by a ____________________. A. Listed over current device rated at 125% of the full load current B. arc-fault circuit interrupter C. Duel element fuse rated at 80% of the full load current D. ground-fault circuit interupter Copyright 2005 Ted "Smitty" Smith
39
Question 3 answer D. Ground-fault circuit interupter 422.23
Copyright 2005 Ted "Smitty" Smith
40
Question 4 Loads for new circuits or extended circuits in other than dwelling units shall be calculated with ______________, as applicable. A. a #2 pencil and paper B. A scientific programmable calculator C. either or D. a derating factor of 75% or 80% Copyright 2005 Ted "Smitty" Smith
41
Question 4 Answer C. 220.12 or 220.14 220.16(B)
Copyright 2005 Ted "Smitty" Smith
42
Question 5 Branch circuits shall not be derived from autotransformers unless the circuit supplied has a grounded conductor that is ______________________ ___________________ _____ a grounded conductor of the system supplying the transformer. Sized larger than Noncontiguous electrically to Electrically connected to Separated completely from Copyright 2005 Ted "Smitty" Smith
43
Question 5 C. electrically connected to 210.9
Copyright 2005 Ted "Smitty" Smith
44
Question 6 What is the minimum height that the auxiliary equipment of electric discharge lamps can be mounted on poles for athletic fields if the voltage rating for the equipment is 600 volts? 10 feet 18 feet 22 feet 30 feet Copyright 2005 Ted "Smitty" Smith
45
Question 6 answer C. 22 feet 210.6(D)(1)(a)
Copyright 2005 Ted "Smitty" Smith
46
Question 7 High voltage conductors in tunnels shall be installed in metal conduit, other metal raceway or type _____________ cable. A. AC B. NM C. SO D. MC Copyright 2005 Ted "Smitty" Smith
47
Question 7 answer D. MC 110.53 Copyright 2005 Ted "Smitty" Smith
48
Question 8 Outdoor mobile home disconnecting means shall be installed so the bottom of the enclose containing the disconnecting means is not less than _________ above the finished grade or working platform. A. 2 feet B. 6 feet, 7 inches C. 10 feet D. 12 feet Copyright 2005 Ted "Smitty" Smith
49
Question 8 answer A 2 feet 550.32(F) Copyright 2005 Ted "Smitty" Smith
50
Question 9 Where the positive polarity of a dc system does not serve as the connection point for the grounded conductor, each positive ungrounded conductor shall be identified by:[ Select the answer that is incorrect.] A. a continuous red outer finish B. a continuous red stripe durably marked along the conductors entire length on insulation of a color other than green, white, gray or black C. a continuous red stripe durably marked marked along the conductors entire length on insulation of a color other green, white, or gray. D. imprinted plus signs (+) or the word POSITIVE or POS durably marked on insulation of a color other than green, white, gray or black. Copyright 2005 Ted "Smitty" Smith
51
Question 9 answer C. a continuous red stripe durably marked marked along the conductors entire length on insulation of a color other green, white, or gray. Missing that it can not be black wire 210.5(C) (2) (a) (1-3) Copyright 2005 Ted "Smitty" Smith
52
Question 10 Where connected to a branch circuit supplying two or more receptacles, a 20 ampere rated branch circuit shall be allowed to supply ______________ rated receptacles. A. 15 ampere receptacles B. 20 ampere receptacles C. Both A and B D. Neither A or B Copyright 2005 Ted "Smitty" Smith
53
Question 10 Answer C. Both A and C 210. 21 (B)(3)
Copyright 2005 Ted "Smitty" Smith
54
Question 11 The minimum feeder conductor size shall have an allowable ampacity not less than the maximum load to be served after the application of _________________________. A. any adjustment or correction factors. B. temperature derating adjustments in accordance with C. conduit fill derating corrections based on Table 5 D. continuous duty rating of loads based on Copyright 2005 Ted "Smitty" Smith
55
Question 11 Answer A. any adjustment or correction factors.
215.2(A)(1)(b) Copyright 2005 Ted "Smitty" Smith
56
Question 12 Vegetation such as trees may be used for support of overhead conductor spans if the attachment point is at least 8 feet above the ground and secured with a device listed for the purpose. A. True B. False Copyright 2005 Ted "Smitty" Smith
57
Question 12 Answer B. False 225.6 Copyright 2005 Ted "Smitty" Smith
58
Question 13 The grounded conductor for a service feeder shall not be smaller than the minimum size as required by ___________________. The authority having jurisdiction 250.24(C) The electrical engineer None of the above Copyright 2005 Ted "Smitty" Smith
59
Question 13 answer 250.24(C) 230.42(C)
Copyright 2005 Ted "Smitty" Smith
60
Question 14 The equipment branch of the Essential Electrical System of a health care facility shall be installed and connected to the alternate power source such that the equipment is automatically restored to operation at ________________. A. no more than 10 seconds from loss of power B. no more than 30 seconds from loss of power C. no more than 2 minutes from loss of power D. at appropriate time-lag intervals following the energizing of the essential electrical system. Copyright 2005 Ted "Smitty" Smith
61
Question 14 answer D. at appropriate time-lag intervals following the energizing of the essential electrical system. 517.34 Copyright 2005 Ted "Smitty" Smith
62
Question 15 At least one receptacle shall be installed at each peninsular countertop space with a long dimension of 24 inches or greater and short dimension of __________ inches or greater. A. 6 B. 9 C. 12 D. 18 Copyright 2005 Ted "Smitty" Smith
63
Question 15 Answer C. 12 210.52(C)(3)
Copyright 2005 Ted "Smitty" Smith