1 CONTROL BOX RMO88.530

2 Dedicated to: Light oil burners PRESS SERIES ONE STAGE TWO STAGE
THREE STAGE RL SERIES ONE STAGE TWO STAGE

3 Dedicated to: Heavy oil burners PRESS SERIES RN SERIES TWO STAGE
THREE STAGE RN SERIES TWO STAGE

4 MODELS FEATURES RMO88.530A2RL RMO88.530A1RL Mode operation………….…...
Intermittent Intermittent Main voltage…………….…... AC V +10% -15% AC V +10% -15% Frequency…………….…... 50-60 Hz +/-6% 50-60 Hz +/-6% Under Voltage protection…... Approx. AC 170 V Approx. AC 70 V Primary fuse…………….…... Max 16 A Max 16 A Power consumption……..…... 20 VA 20 VA Internal fuse…….……..…... T6.3H250V (IEC ) T6.3 Polarity...………….……..…... To be observed To be observed Flame signal (photoresistence) >450 K (pre-purge) <200 K (operation) >450 K (pre-purge) <200 K (operation)

5 RMO88.530A2RL RMO88.530A1RL Timings of cycle NOTES
Waiting time………….…... 2 sec………………………….. Beginning when both # 4 & # 8 are energised. If not input to # 4 within 600 sec since # 8 is energised  lock out Pre-purge time (min)….…... 23 sec…………………………. Interval between # 11  # 10 outputs Pre-ignition time………….…... 22 sec………………………... Interval between # 12  # 10 outputs Post-ignition time……….…... 5 sec Ignition safety time……..…... 5 sec Interval 1st  2nd stage..…... 7 sec…………………………. Interval between # 10  # 13 outputs Interval 2st  3rd stage..…... 7 sec…………………………... Interval between # 13  # 14 outputs

6 CONTROL PROGRAM IN EVENT OF FAULT

7 INDICATION OF OPERATION

8 SELF-DIAGNOSTIC Operating concept
· Burner control has initiated lockout Þ Red fault LED on · Reset Press lockout reset button for about 1 s · Diagnosis of cause of fault – Press lockout reset button for > 3 s – Press again lockout reset button for > 3 s – Read blink code of red fault LED Þ «Error code table A»

9 Error code table A Blink code Possible cause
2 x ·· · No establishment of flame at the end of ignition safety time – Faulty or soiled flame detector – Faulty or soiled fuel valves – Poor adjustment of burner – Faulty ingnion equipment 4 x ···· · Extraneous light during pre-purging – Or internal device fault 7 x ······· · Loss of flame during operation 8 x ········ · Time-out release contact for oil pre-heater does not close 10 x ·········· · Wiring error or internal fault, output contact, unidentifiable fault, e.g. faults that occurred simultaneously