Download presentation
Presentation is loading. Please wait.
1
Rapidzone Operation: Network Data Sharing
Discharge air temp information is broadcast to zone controllers via E-Bus Discharge Air Temp DAT RTU TL Z1 Z2 Z3 Terminal load information is sent to RTU controller via E-Bus Terminal Load
2
Zone Controller Operation: DAT Control
Suitable? DAT in MOD Open Y Occupied mode? N Damper Min Pos Y Damper Closes N
3
Setpoint Knob Operation
Setpoint knob determines centre of deadband between heating and cooling Example: deadband is set for 6° knob set for 73° heat setpoint becomes 70 ° cool setpoint becomes 76 ° deadband exists between 70 ° - 76 ° Heating Setpoint Cooling Setpoint Deadband 73 70 76
4
Rapidzone Operation: Terminal Loads
Terminal Load: zone deviation from setpoint Terminal Load is broadcast from each zone to RTU via E-Bus < 20 % zone is satisfied > 20 % zone requires heating or cooling Zones can be configured as ‘priority’, terminal load multiplied by 1.5 163% -163% 0 % Heat On Cool On +20 % -20 % Deadband Zone Satisfied
5
Terminal Load RTU Z1 TL + 18 Z2 TL + 18 Z3 TL + 25
RTU will run in cooling mode until Zone 3 is satisfied (TL drops below 20%) Zones 1 and 2 remain closed or in minimum position Z1 TL + 18 Z2 TL + 18 Z3 TL + 25
6
Terminal Load RTU Z1 TL - 25 Z2 TL + 18 Z3 TL + 25
RTU will alternate between heating and cooling until: zone 1 heating satisfied zone 3 cooling satisfied Zone 2 remain closed or in minimum position Length of Heat / Cool runtime entered by Rapidzone software Z1 TL - 25 Z2 TL + 18 Z3 TL + 25
7
Terminal Load RTU Priority Z1 Z2 Z3 TL + 25 TL + 18 TL - 18 x 1.5
Zone 2 configured as priority zone, terminal load multiplied by 1.5 RTU will alternate between heating and cooling until: zone 2 heating satisfied zone 3 cooling satisfied Zone 1 remain closed or in minimum position Length of Heat / Cool runtime entered by Rapidzone software Priority Z1 Z2 Z3 TL + 25 TL + 18 TL - 18 x 1.5 TL - 27
Similar presentations
© 2025 SlidePlayer.com. Inc.
All rights reserved.