Download presentation
Presentation is loading. Please wait.
Published byAnnegret Ziegler Modified over 6 years ago
1
Incompatibility between MV Switchgear conforming TO the international standards and their use in DNO’s substations M. Arens – Y Tits – Belgium – Session 1 – Paper 0950
2
Distribution network criteria
MV switchgear has to meet the following criteria : Network’s real service conditions Network use Load current capacity under high ambient temperature Service continuity M. Arens – Y Tits – Belgium – Session 1 – Paper 0950
3
Network’s real service conditions
Substation in the humid countryside without heating Substation in cellar (P) Metallic substation High temperature Low temperature Moisture M. Arens – Y Tits – Belgium – Session 1 – Paper 0950
4
Network use Connection of cable with cross section according to Irswitchgear : Ir = 630 A Cable section = 630 mm² Al Ir = 800 A Cable section = 2x400 mm² Al mechanical stress on the connection during connection work and during temperature rise and short circuit (expansion ) Few operations (except for smart grid application) higher forces for switching operations M. Arens – Y Tits – Belgium – Session 1 – Paper 0950
5
Load current capacity for high ambient temperature
Generally low load current Peak current for some hours in emergency situation M. Arens – Y Tits – Belgium – Session 1 – Paper 0950
6
Service continuity Very high cost of outage Maintenance free
Cost of outage due to cable or switchgear failure Cost of operation to liberate the installation Maintenance free M. Arens – Y Tits – Belgium – Session 1 – Paper 0950
7
Modes of ageing Corrosion of metal parts under the influence of humidity and heat Degradation of the insulating parts under the influence of moisture, heat and dielectric stress Tightness of the vessel containing the insulation gas mainly influenced by temperature M. Arens – Y Tits – Belgium – Session 1 – Paper 0950
8
Standards: implemented improvements
Example of improvement implemented in the last IEC Stress on interlock mechanism: attempt to operate the switching device in the wrong direction with a prospective force of 750 N M. Arens – Y Tits – Belgium – Session 1 – Paper 0950
9
Standards: examples of needed improvements
Normal service conditions IEC should include: Use for network service conditions Consequently define required type tests 60587 Tracking test but with increased number of cycles, HV impuls test and PD measurements Salt mist Tightness at 40°C M. Arens – Y Tits – Belgium – Session 1 – Paper 0950
10
Standards: examples of needed improvements
Other required type tests Temperature rise test and short circuit test to perform with a representative cable connection Dielectric test on SWG equipped with all accessories ( connection points for cable test) M. Arens – Y Tits – Belgium – Session 1 – Paper 0950
11
Standards: examples of needed improvements
Additional design criteria to be taken into account: Possibility to respect EN for maintenance purposes (appropriate interlockings) Required accessories for test purposes arc suppressors are not addressed Active parts outside the enclosure are not addressed M. Arens – Y Tits – Belgium – Session 1 – Paper 0950
12
Conclusions Need to specify the DNO requirements
discussion and preparation between DNO more implication of DNO in normative working groups M. Arens – Y Tits – Belgium – Session 1 – Paper 0950
Similar presentations
© 2025 SlidePlayer.com. Inc.
All rights reserved.