PLC 5 and ControlLogix Subroutine Parameters
2
Input Parameters Simple Example
Three variable frequency drives heat sink temperatures input to PLC Temperatures input in degrees Celsius Convert to degrees Fahrenheit and display on operator interface
3
Option #1 Ladder Conversion
Each time temperature input could add a rung to do calculations. This would make ladder file longer. More rungs Slower scan
4
Option #2 Subroutine Conversion
Put conversion instructions in a subroutine Access subroutine each time conversion necessary Less rungs in ladder JSR input parameters used to move temperature data to subroutine
5
JSR Instructions with Parameters
6
Heat Sink Temperature from Three Different Sources
Drive node 21 temperature to F8:0 Drive node 22 temperature to F8:1 Drive node 23 temperature to F8:2
7
JSR Sends Information to SBR
JSR sends temperature information to SBR instruction input parameter address F8:10. Node 21, F8:0 temperature Node 22, F8:1 temperature Node 23, F8:2 temperature
8
Subroutine Shares Data
- F8:10 is where temperature is stored. - F8:10 data used in calculation
9
CPT Destination Stores Result
10
Result, F8:11 to RET Output Parameter
11
Data Returned to JSR Data from RET instruction return parameter to JSR
return parameter F8:12
12
Data Flow Ladder 2 A D E Ladder 3 C B
13
No Return Parameter Faults Processor