1
Tony Faris JSIS Meeting October 2017
DFR/DDR Testing at BPA Tony Faris JSIS Meeting October 2017
2
Test Methodology Set trigger limits – frequency, voltage, etc.
Create waveforms with test set State sim for step tests DFR records from field units for actual events COMTRADE playback Play waveforms into DFR/DDR Verify timestamp of event, accuracy of waveform, and any computed values Compare measurement with input signal Test back-to-back events
3
DFR/DDR Testing Create Test Signals Relay Test Set DFR/ DDR
3 Phase Voltages Create Test Signals Relay Test Set DFR/ DDR Oscillography Record COMTRADE Compare/ Plot (MATLAB) A Phase Voltage Scope Capture Oscilloscope
4
Lab Setup GPS antenna and receivers Relay test set(s)
High accuracy scope Internal LAN Access to field PMU and DFR/DDR data
5
Input Signal
6
Input Signal
7
DFR/DDR Testing
8
APP-601
9
KoCos EPPE Px
10
PSL PQube 3 *Not yet tested: Requires GPS Module for High Accuracy Mode
11
Qualitrol BEN 6000
12
SEL 487E
13
Device A Response
14
Device B Response
15
Device C Response
16
Device D Response
17
Preliminary Results Device Time Error Phase Error Device A 0.9317 ms
20.13 deg Device B 0.197 ms 4.25 deg Device C ms 1.05 deg Device D ms 0.03 deg
18
DFR Evaluation Criteria
Length and reporting rate of event records Reporting rate of continuous recording Calculated/sampled values vs. point-on-wave Computed values – power, frequency, phasors Data formats – .csv, COMTRADE, etc. Expandable storage? Moving components? Time synchronization – GPS? IRIG-B? Architecture: external CTs/shunts, modules, etc. Portability and ease of installation Access to records
19
Contact Tony Faris Bonneville Power Administration Measurement Systems