Download presentation
Presentation is loading. Please wait.
Published byDjaja Tedjo Modified over 5 years ago
1
Psychrometric analysis Revision of principles - Central plant
for UBCLQT-40-3: Building & Engineering Systems Performance and UBLLSM-20-3: Mechanical Services
2
Psychrometric quantities
temperature dry bulb, t [oC d.b.] wet bulb, t’ [oC w.b.] relative humidity, [%rh] = avp / svp percentage saturation, μ [% sat.] = ms/mss moisture content, x [kg.kg-1dry air] specific volume, v [m3.kg-1 dry air] = 1/ specific enthalpy, h [kJ.kg-1 dry air] dew point temperature, td [oC]
3
Psychrometric chart Lines of constant d.b. temp.
Dry bulb temperature, t
4
Psychrometric chart Lines of constant moisture content
Moisture content, x
5
Psychrometric chart percentage saturation ,
Lines of constant relative humidity, (percentage saturation)
6
Psychrometric chart Wet bulb temperature, t’
Lines of constant w.b. temp. Wet bulb temperature, t’ 5oC wb 5oC db
7
Psychrometric chart Lines of constant specific volume
specific volume, v
8
Psychrometric chart Specific enthalpy, h ‘Lines’ of constant
9
Psychrometric chart Dew point temperature, td oC
10
State point Any two psychrometric quantities can be used to define a state point. All other properties can be read from the chart 50 %rh 26.5 kJ.kg-1 0.82 m3.kg-1 8.9oC db kg.kg-1 14oC db
11
Exercise - complete Table 1
12
Exercise – Solutions
13
Ideal processes Isothermal humidification Adiabatic humidification
Sensible heating Sensible cooling Adiabatic dehumidification Isothermal dehumidification
14
Real processes - Sensible Heating
Heating load, QH = ma (h2 - h1) h2 - h1 1 2 Heater Battery
15
Heating load, QH = ma (h2 - h1)
Real processes - Sensible Heating Plant Loads Example 1: Air flows at a rate of 3.42 kg.s-1 into a heater battery. If the initial condition of the air is state 5 (see Table 1) and the air leaves the heater battery at a temperature of 31 oC d.b., determine the load on the heater battery in kW. Heating load, QH = ma (h2 - h1)
16
Real processes - Sensible cooling
Cooling load, QC = ma (h1 - h2) (Nominal) h1 - h2 2 1 Cooler Battery
17
Real processes - Cooling & Dehum.
1 2 Cooler Battery
18
Real processes - Cooling & Dehum.
Cooling load, QC = ma (h1 - h2) (Nominal) h1 - h2 1 2 Cooler Battery
19
Real processes - Cooling & Dehum.
Cooling load, QC = ma (h1 - h2) (Nominal) h1 - h2 1 2 Cooler Battery
20
Contact Factor Cooling load, QC = ma (h1 - h2) h1 - h2 1 2 s ADP t
21
Real processes – Cooling with dehum
Plant Loads Example 2: A cooler battery takes a flow of 1.5 kg/s of air at 25oC d.b. with a moisture content of 11.3 g/kg and dehumidifies to obtain a moisture content of air leaving the battery of 8 g/kg. If the cooler contact factor is 85%, determine the apparatus dew point and the nominal cooling load in kW. Cooler Contact Factor,
22
Real processes - adiabatic humidifier
Adiabatic process - where no energy transfer occurs i.e. h1 = h2 Load = 0 2 1 Air Washer
23
Real processes - steam injection
h 2 1 Steam humidifier
24
Humidifier saturation efficiency
ADP 2 1
25
Humidifier saturation efficiency,
Real processes – Humidification Plant Loads Example 3: Air enters an air washer at 31oC d.b., 14.4oC w.b. and leaves with a moisture content of kg/kg d.a. Determine the saturatiion efficiency of the air washer. What factors influence the saturation efficiency of humidifiers generally? Humidifier saturation efficiency,
26
Room heat loads Summer room loads:-
Sensible heat gain + Latent heat gain Sensible Heat Ratio 1 Room ratio line R S tR - tS
27
Room heat loads Winter room loads:-
Sensible heat loss + Latent heat gain Sensible Heat Ratio 1 Room ratio line R S tS - tR
28
Room heat loads Example 4: The room is to be kept at state 4 using a flow of 1.50 kg.s-1 of air at state 6. Determine the room sensible and latent loads in kW. The specific heat capacity of moist air is 1.02 kJ.kg-1K-1
29
Central plant AHU - 100% fresh air
Summer cycle 2 4 6
30
Central plant AHU - 100% fresh air
Summer cycle 2 Cooler battery 8 4 6
31
Central plant AHU - 100% fresh air
Summer cycle 2 Cooler battery + Re-heater battery 8 4 6
32
Central plant AHU - 100% fresh air
Summer cycle O Cooler battery + Re-heater battery C R S Room ratio line (RRL)
33
Central plant AHU - 100% fresh air
Winter cycle 3 7 5
34
Central plant AHU - 100% fresh air
Winter cycle Pre-heater battery 3 7 5 10
35
Central plant AHU - 100% fresh air
Winter cycle Pre-heater battery + steam humidifier 3 9 7 5 10
36
Central plant AHU - 100% fresh air
Winter cycle Pre-heater battery + steam humidifier 3 + re-heater battery 9 7 5 10
37
Central plant AHU - 100% fresh air
Winter cycle Pre-heater battery Room ratio line (RRL) + steam humidifier R + re-heater battery B S O A
38
Central plant AHU - 100% fresh air
Winter cycle Pre-heater battery Room ratio line (RRL) + adiabatic humidifier R + re-heater battery B S O A
39
Mixing AM A xA BM M xM B xB tB tM tA
40
Real processes - Mixing
Example 5: Air in state 3 is mixed with air in state 4 to obtain mixed air, state M, with a dry bulb temperature of 25oC. If the mass flow rate of mixed air is 1.45 kg/s, determine the flow rates of consituent air flows.
41
Central plant AHU - recirculation air
2 6 4 C C’ M Summer cycle
42
Central plant AHU - recirculation air
S M Room ratio line (RRL) Winter cycle
Similar presentations
© 2025 SlidePlayer.com. Inc.
All rights reserved.