1 CMS ventilation system
Air handling units Principle LHC status UX ventilation modes USC ventilation principle Fire detection and smoke extraction Pressurization safe areas Gas extraction Other buildings Bernard Pirollet TS-CV-EPA

2 Bernard Pirollet TS-CV-EPA
Air handling units SUX 50 units installed SH Bernard Pirollet TS-CV-EPA USC

3 Bernard Pirollet TS-CV-EPA
Air supplied & air extracted Quality Pressurization Temperature Dew point Smoke and gas extraction Principle BRR/T D M N S L - E V P BA6 BAY BFY BTO BT2 BLP MRM BLO MRE BTT BTB BTA + PRB 180 210 M L BAY BA6 BLO MRE Bernard Pirollet TS-CV-EPA

4 Bernard Pirollet TS-CV-EPA
Principle LHC status Cap open / Cap closed LHC run / Shut down Purge Emergency Bernard Pirollet TS-CV-EPA

5 Bernard Pirollet TS-CV-EPA
UX ventilation modes Supply Extraction (m3/h) Gas Cap open Shut down (SX) Cap closed Shut down Cap closed LHC run (recycling) 5 000 Purge (fresh air) (RP control) 5 000 Emergency Cap closed Emergency Cap open (SX) Bernard Pirollet TS-CV-EPA

6 Bernard Pirollet TS-CV-EPA
USC ventilation principle Supply Extraction (m3/h) Gas Service area Post treatment Racks areas Post treatment / Bernard Pirollet TS-CV-EPA

7 All the air handling units of the concerned area are
Cold smoke extraction Actions Detection Fire men All the air handling units of the concerned area are automatically stopped (Ts/cv) Smoke extraction mode activated by fire men (fire men cubicle) During extraction mode extraction filters will be by-passed End of fire men action No action with RP Air handling units in normal mode restarted by TS-CV Material design 400°C/2h Bernard Pirollet TS-CV-EPA

8 Bernard Pirollet TS-CV-EPA
“Fire cubicle” Bernard Pirollet TS-CV-EPA

9 Bernard Pirollet TS-CV-EPA
Pressurization areas 3 separate & independent areas: Experimental caverns (-) (UX pts 1/2/8 & UXC55 pt5) Protected areas- technical caverns (+) (USA 15 pt1,UX 85 pt8 & USC55 pt5) Safe area (++) (PM/PZ) M M M D S L N E L E V M M M D S L N E L E V M M M D S L N E L E V (-) UXC55 Differential pressure (+) PX56 (+ +) Services Racks Bernard Pirollet TS-CV-EPA PM54 USC55

10 Bernard Pirollet TS-CV-EPA
Pressurization safe areas Bernard Pirollet TS-CV-EPA

11 Bernard Pirollet TS-CV-EPA
Gas extraction UX USC55 PX56 PM54 UXC55 Cryogénie Racks SUPERVISEUR : J.ROCHE INDICE CERN ORGANISATION EUROPEENNE POUR LA RECHERCHE NUCLEAIRE EUROPEAN ORGANIZATION FOR NUCLEAR RESEARCH C.MARTEL 22/02/2000 UAEW-519/520-SX5-UXC55 Extraction mélange gazeux / Mixing gas extraction Schéma de principe - Principle schematic LHCU Extraction gaz Argon Argon gas Extraction M BLO MRE SX Espace confié / Confined room 5 000 m3/h A 5 000 m3/h BLO BLO standby BLO MRE BAY BAY BAY MRE MRE BA6 M BAY M M A M M L L L V BD1 5 000 m3/h BT5 UAEW-519-SX5-UXC55 BLO BAY BLO BLO MRE BAY BAY MRE MRE BA6 M BAY M M M L L L V UAEW-520-SX5-UXC55 UIAE UIAN Bernard Pirollet TS-CV-EPA

12 Bernard Pirollet TS-CV-EPA
Gas extraction USC Bernard Pirollet TS-CV-EPA

13 Bernard Pirollet TS-CV-EPA