Presentation is loading. Please wait.

Presentation is loading. Please wait.

Tracer Applications.

Similar presentations


Presentation on theme: "Tracer Applications."— Presentation transcript:

1 Tracer Applications

2 Typical Steam Tracing Piping
distribution Spares manifold Steam supply Condensate return Outlet Condensate riser collecting manifold Traced pipe Tracer Spares

3 Process Temperatures: 101°F to 200°F
Convection Tracers Designed for use with medium-low to medium heat transfer requirements, the metallic tracer tube is either bare or covered with a thin, high temperature coating that provides a measure of personnel burn protection without sacrificing thermal performance. Process Temperatures: 101°F to 200°F

4 Process Temperatures: 151°F to 400°F
Conduction Tracers Designed for use when the heat requirements exceed the capabilities of isolated and convection tracers. Conduction tracers are aided by heat transfer compounds that provide excellent heat transfer at a fraction of the cost of a jacketed pipe system while eliminating the possibility of product contamination. A single tracer utilizing heat transfer compound will perform as well as 3 to 5 bare (convection) tracers. Process Temperatures: 151°F to 400°F

5 Tracer Materials The tracer is selected to fulfill the thermal and installation requirements. The tracer metal should be close to the material of the process pipe to minimize galvanic corrosion. Copper tubing can be used if the saturated steam pressure or the item being traced does not exceed 400°F and there is no corrosion or other deterrent (copper oxide) for using copper. Stainless steel tubing can be used if the saturated steam pressure or the item being traced exceeds 400°F and there is no corrosion or other deterrent (chlorides) for using stainless steel. Carbon steel pipe should NEVER be used. During shutdown periods, air and moisture causes rapid rust and pitting.

6 AVTR AVTR is the accumulated vertical tracer rise i.e. the sum of
all the elevation rises (see Figure 5.1). The AVTR should be limited to 15% of the inlet steam pressure for any steam tracing circuit. For example, with an inlet steam pressure of 50 psig, the AVTR should not exceed 7.5 feet. The AVTR is further reduced by losses due to bends, valves, and fittings in the tracer circuits (see Table 5.2). The resultant losses must be deducted to determine the actual AVTR.

7 AVTR Example

8 AVTR Reduction Losses

9 Insulation Guidelines

10 Tracer Tubing Installation

11 Small Diameter Tube Tracing
Steam 1/2” or 3/8” tubing 1/2” or 3/8” tubing Steam 1/2” or 3/8” tubing Trap Steam Trap Trap Trap Valves Pumps Instruments Very light condensate loads; small diameter tubing ok Condensate must flow downward by gravity to trap Small diameter tube bends around objects easily Each tracer circuit has separate trap

12 Process Pipe Tracing Methods
Hot product flowing in steel pipe loses heat through insulation Products may solidify as they cool: Plastics solidify at low temperatures Asphalt solidifies at ambient temps Increased viscosity when cooled; won’t flow Sulfur solidifies above 350°F and below 250°F Tracer internal with direct contact with product, potential product contamination Tracer external to and in contact with product pipe under insulation Internal Tracing External Tracing

13 Process Pipe Tracing Notes:
Horizontal No! Metal Strap Vertical Yes! Insulating spacer Notes: Low steam velocity to move condensate; must flow by gravity; don’t use wound tracer on horizontal runs Vertical wound tracer on short runs only Metal straps hold tracer Insulating spacers used if product may char, burn or crystallize with intense heat

14 Number of ½” Diameter Tracers
Product line size Freeze Protection or Product solidification at °F - 75°F Product Solidification 75°F – 150°F Product solidification °F - 300° F 25 mm, 1" 1 40 mm, 1-1/2" 2 50 mm, 2" 80 mm, 3" 3 100 mm, 4" 150 mm, 6" 200 mm, 8" mm, 10" - 12" mm, 14" - 16" 6 mm, 18" - 20" 8 mm, 10

15 Multiple Tracer Spacing
Vertical Horizontal Space evenly at bottom of pipe Evenly spaced around pipe

16 Tracer Lines! How Long? Condensing steam in small diameter tubing causes pressure drop. To insure enough pressure at the trap to remove condensate, tracer length should be limited. 3/8”, 8 mm 75 ft, 23 m 1/2”, 15 mm 125 ft, 38.5 m 3/4”, 20 mm 150 ft, 46.2 m

17 Multiple Tracing Traps
No! Multiple circuits - 1 trap Do not gang trap! Multiple circuits - multiple traps Yes!

18 Line Tracing Installation
Yes! No! Expansion Loops Flange Loops

19 Steam Jacketed Pipe Why? Rate of heat transfer = f((T1 - T2), Cf)
Insulation Steam Jacket Pipe Steam Jacket Product Pipe Product T2 T1 Why? Rate of heat transfer = f((T1 - T2), Cf) Steam temperature close to product temperature Product has low coefficient of heat transfer

20 Steam Jacketed Installation
Steam in Trap Pitch Steam flow counter to product flow Pitch in direction of steam flow Section <= 20 ft. 6 m Moderate climates Trap every 80 to 100 ft, 24 to 30 m Severe climates Trap every 40 ft, 12 m Ideal ! OK ! No !

21 Jacketed Line Sizing

22 Steam Tracing Condensate
Q = L x A x U x (t1 – t2) x E/(H x N) Q = Condensate load, lb/hr, kg/hr L = Length of tracer, ft, m U = Heat transfer coefficient pipe to air, btu/hr/deg f/sq ft, t1 = Product temperature, °F, t2 = Minimum air temperature °F, E = 1 – insulation efficiency/100 A = Area of pipe per ft length, sq ft/ft, H = Latent heat of steam btu/lb, N = Number of tracers Example: 20” pipe, 200 °F product, -20 °F air, 100 psig steam Q = 125 x 1.93 x 12 x (200-(-20)) x .25/(880 x 4) = 45 lb/hr per tracer


Download ppt "Tracer Applications."

Similar presentations


Ads by Google