Download presentation
Presentation is loading. Please wait.
Published byCaroline Schneider Modified over 5 years ago
1
Objectives Learn about Electricity Pricing Electric systems
2
Electricity Billing Electrical Use (energy) Peak Demand (power)
Power factor Which is largest portion of residential bill? What about for commercial buildings?
3
Example: September cost of Electricity for ECJ
Assume ECJ is 120,000 ft2 and that it needs, on average, 8 W/ft2 for 8 hours a day, 6 W/ W/ft2 for 4 hours a day, and 4 W/ft2 for 12 hours a day Use Austin Energy Large Primary summer service rate 1.5¢/kWh, $/peak kW/month Assume no power factor charges
4
Solution large primary service $/kW $/kWh Daily $ 12.60 $ 0.015 hours
$ $ hours kW kWh 8 960 7680 demand $12,096.00 4 720 2880 energy $ 7,344.00 12 480 5760 TOTAL 16320 Total $19,440.00
5
Other Pricing Strategies
Time of use pricing Becoming more common for residential and commercial Electricity cost related to actual cost Requires meter Interruptible pricing Utility can shut off electricity for periods of time
6
Conductors Material Form Composition Voltage class Insulation Covering
Temperature rating AWG American Wire Gage
7
Wiring method –Raceways
Electric tubes Rigid conduits Wire ways Bus ducts Underflow Different variation
8
Design issues with conductors
Material (copper/aluminum) Size of conductor (pg. 365) Conduit requirements Location Residential or Commercial With or without raceways Compression fittings or set screws Threaded connections NEC and local codes
9
Current-Carrying Capacity
Ref: Tao and Janis (2001)
10
Tubing size Ref: Tao and Janis (2001)
11
Other Issues In general, no more than 40% of raceway can be filled with wiring Why? To prevent extensive heat up To prevent physical installation of wires
12
Conductor Rules Explain each of the following: In the same conduit:
No more than 4 90 ° bends are allowed between pull boxes In the same conduit: No mixing of high- and low-voltage conductors No mixing control and power conductors No mixing phone and power conductors Do place all three phases in the same conduit
13
Receptacles and switches
Receptacles (duplexes) Number Shape Voltage rating Current Rating Number of poles and wires Switches Type (NEC rating) Contact method Speed of operation Voltage rating Number of poles Method of operation Enclosure Duty Other (dimming)
14
Protective Devices What are we protecting from? Circuit breakers
Overcurrent Overvoltage Circuit breakers Switch that responds to thermal or short circuit loads Can be bimetal, magnetic, or electronic Reusable, remote control, compact, can be used as disconnect switch Fuses Melting metal Self destructive, larger
15
Why use fuses instead of circuit breakers?
Fuses can be used multiple times Fuses are more aesthetically pleasing Fuses are safer Fuses cause less damage to equipment
16
Ref: Tao and Janis (2001)
17
Emergency power systems Batteries Power generators
Motor starters ON-OFF switches are NOT for motors Motor circuit-rated switches Reduce the current during the start until the motor rich full speed Protect the motor form overload Emergency power systems Batteries Power generators
18
Residential Systems Very little variation between different houses
Many similarities to commercial buildings Particularly as you get close to end uses Need to be watchful for unusual circumstances
19
Procedure Analyze building needs Determine electrical loads
Select electrical systems Coordinate with other design decisions Prepare plans and specifications
20
List of needs Appliances (incl. HVAC) Receptacles Lighting
Ground fault protected (GFI/GFCI) Switched Lighting Switches Ceiling Fans
21
Example House Master Bedroom Bathrooms
Entry and Outdoor (AC compressor) Bedrooms Dining and Mechanical Closet (resistance heat) Kitchen (appliance circuits, range, oven) Family Garage/Laundry/Closet (resistance water heater, dryer)
22
Outdoor Bathroom Closet Bedroom 2 Laundry Kitchen Bathroom Mechanical closet Family room Master Bedroom Entry Bedroom 3 Dining Garage
23
NEC about receptacles No longer approve non-polarized and ungrounded receptacles in new installations. Each receptacle (duplex) is rated for 1.5 A. For 120 V: Each duplex 1.5×120 = 180W
24
Residential system sizing
Typically 3 wire 1 phase system 120/240 V Procedure defined by NEC article 220: Identify characteristic electrical loads Add lighting (3W/ft2) Add two 20 Amps circuits for kitchen Add one 20 Amps circuit for laundry Electricity for HVAC equipment based on requirement for heating or cooling
26
Summary of Power Sizing
Include enough capacity for heating and cooling Work through kitchen and then other rooms Include any items that are unusual Take first 10 kVA and then 40% of remaining load
27
Panel Sizing Find panel power usage and neutral usage
Size panel conductors and associated conduit and switches
28
Electric panel - 3 wire 1 phase 120/240
29
Homework 5 - problem 2 Sizing the residential electrical system
Defined by NEC article Similar to the example we worked out You need to collect the data for several characteristic consumers Includes conductor sizing
Similar presentations
© 2024 SlidePlayer.com. Inc.
All rights reserved.