Download presentation
Presentation is loading. Please wait.
Published byΣαπφώ Σκλαβούνος Modified over 5 years ago
1
Opportunities in variability of indoor temperature
Effect of spatial transitions on thermal comfort perception of occupants in closed office spaces Opportunities in variability of indoor temperature Introduction Background Research Question and Hypothesis Research Methods Findings / Data Discussion Conclusions Further research 7LS1M0 BPS research project A Date: 4 May 2018 Student: J.J. (Arjan) Kraakman Supervisors: dr. A.K. (Asit) Mishra dr.ir. M.G.L.C. (Marcel) Loomans
2
Introduction Limiting global warming <1.5 ⁰C
EU low-carbon economy in 2050 100% renewable energy sources Constant non-constant energy supply Variability in indoor conditions Ensuring comfort perception Paris Agreement 80% reduction of Greenhouse gasses 1990 Office space rapidly evolves like flexible working Introduction
3
330 North Wabash (IBM building)
Wind city 330 North Wabash (IBM building) Introduction
4
Background Primarily focused steady frame
Adaptation time and thermal perception1 Magnitude (∆T) of the temperature jump2 Not affected within ±3 ⁰C1 Primarily focused on occupants in a steady frame Looked at adaptation time and thermal perception immediately following transitions Effect of spatial transition on thermal perception depends on the magnitude of the temperature jump At comfort level ± 2 degrees and warm of cold already at 1 degrees Thermal perception is not significantly affected when the temperature difference across which the transition takes places keeps within ±3 degrees [1] Mishra et al, 2016 [2] Palma & Stevenson, 2015 Figure 1 Relaxed thermal comfort requirements for transition spaces. (Mishra et al., 2016) Background
5
Research Question Hypothesis
Movement across what range of inter-zone temperature difference does not impact occupant thermal perception? Hypothesis Temperature differences of 3 ℃, or less, between regular use and transitional spaces does not influence thermal sensation to a significant degree. Research Question
6
Research Methods 6 occupants Room level control of indoor temperature
Two weeks General comfort End of October and end of November Figure 4 Result comfort vote general survey Metaforum level 5 Figure 2 Floorplan MetaForum level 5 Figure 3 thermostat rooms Research Methods
7
Instruments Questionnaire survey Time Spent out of room
Spent in room since last entry Previous location Temperature sensation vote (TSV) Temperature comfort vote (TCV) Measuring parameters Wireless sensors on desks Wireless sensors hallway (1,7 m) Thermostat sensor of system Point-in-time survey Import questions: Time until fill in after transition, location before and TSV Figure 6 position wireless T sensor and climate pole Figure 5 Point-in-time survey Research Methods
8
Results 142 usable responses
Temperature samples not significantly differ (p < 0.001) Step change responses Tair,BMS 77 Δ Tsensor 103 Did not significantly differ between the two periods of measurements Delta Tdesk – Thallway Delta TBMS – Thallway Results
9
Results Results
10
Results Results
11
Results p value = 0.000 p value = 0.085 Hallway Hallway
TSV vs Δ Tsensor weak (positive), non-significant TSV vs Δ TBMS weak (positive), significant Figure 8 Section office MetaForm with hallway Figure 7 Section office MetaForm with hallway p value = 0.000 p value = 0.085 Results
12
Discussion Hypothesis not rejected with Tair,desk-sensor
Indicate that effect of transitions across temperature difference ±2 ℃, if any, on thermal perception is to short to affect perceptions significantly. Figure 9 Section office MetaForm with hallway Discussion
13
Discussion Most step changes within ±2 ℃ Small data sample
Cooler temperature for Tair,BMS TSV similar to Tair,BMS and Tair,hallway TSV correlated to Tair,hallway museum study3 Important limitation of the study Mean values of 21.8 vs 22.5 ⁰C Distance to hallway Within the last 20 minutes TVS correlate outdoor temp [3] Mishra et al, 2016 Figure 9 Section office MetaForm with hallway Discussion
14
Conclusion Δ Tair,desk-sensor ±2 ℃ TSV is negligibly impacted by ∆T
Promising results for climate chamber studies Thermal zoning Energy usage Conclusion
15
Further research Creating larger Δ T Over other seasons
Different office building layouts Different use patterns Further research
16
Questions
Similar presentations
© 2025 SlidePlayer.com. Inc.
All rights reserved.