Planning Commission January 20, 2016
Item # 3.2 Public Hearing – Site plan approval of a Questar regulator facility at 148 West 800 South in the R8 zone Applicant: Mark Johnson
2
R8 15,246 square foot lot Permitted as per Section (F) Neighborhood meeting held on January 7 Utility substations. Utility substations or similar facilities are permitted in residential zones subject to the following standards: 1. the primary access must be from an arterial or collector street; 2. an 8-foot high masonry fence shall be constructed and maintained on the property line of all adjoining parcels; 3. the fence shall be set back at least 20 feet from dedicated streets; 4. the setback area from streets shall be landscaped with a combination of grass, shrubs, and trees (both deciduous and conifer); and 5. all structures (excluding the required masonry fence) shall be set back from the property lines a distance of at least equal to the height of the structure and in no case less than 20 feet.
4
Site Plan Masonry wall Gravel Landscaping outside of wall
5
Landscape Plan Trees and shrubs Low maintenance No landscaping inside of wall
6
Details Iron gate 8’ masonry panel wall 12’ x 15’ building with 8’ walls