Universal Interrupted Electronic Oil Primary R7184U Training Module

Similar presentations


Presentation on theme: "Universal Interrupted Electronic Oil Primary R7184U Training Module"— Presentation transcript:

1 Universal Interrupted Electronic Oil Primary R7184U Training Module

2 What you will learn R7184U Product Overview Key Features and Benefits
Installation and Set Up Troubleshooting Product Cross Reference R7184U Oil Primary Advantages

3 R7184U Interrupted Electronic Oil Primary
What is the R7184U? It is a line voltage, safety rated, primary control for residential oil fired burners used in boilers, forced air furnaces and water heaters. Applicable for use with both hydronic and forced air systems. Used with a cad cell flame sensor, operates an oil burner and optional oil valve. Universal Oil Primary Part Numbers: R7184U1004 R7184U1012 R7184U1020

4 R7184U Key Features Universal compatibility
This control replaces Carlin, White Rodgers and all prior Honeywell Oil Primary Controls EnviraCOMTM communications enabled: Includes EnviraCOM™ Connection for local networking & diagnostics Compatible with the Honeywell EnviraLINK™ remote monitoring application, which enables dealers to monitor their customers systems remotely.

5 R7184U Key Features Diagnostic LED
Indicator light monitors burner flame status and system lockout The versatile R7184U includes these “Exclusive Features”: Pump priming cycle Cad cell flame strength indicator Limited recycle Extended Service Life (Control and Application)

6 Additional R7184U Features
Available in 15-, 30-, and 45-second lockout times R7184U1004 = 15 second lockout R7184U1012 = 30 second lockout R7184U1020 = 45 second lockout Optional valve-on delay, blower-off delay models: Models: 15 seconds, or selectable 0 or 15 second valve-on delay Zero time or selectable 0-, 2-, 4-, 6-minute blower-off delay Safe start check – check for flame presence prior to lighting the burner Compatible with power venters without integral timers Oil-resistant plastic cover for electronics

7 R7184U Feature Function Benefit
Pump Purge Temporary setting of safety timing to 4 minutes Allows installer to purge oil lines without remaining at oil primary CAD Cell Resistance Readout Flash CAD resistance range while burner is running Allows installer to check that flame strength is adequate prior to leaving job site Limited Recycle Limits recycle to 3 per any one call for heat Detects running saturation or poor combustion from partially clogged nozzle and locks out to prevent heat exchanger clogging or oil flooding Limited Reset Limits resets to 3 during any single call for heat Prevents homeowner from continually pressing reset button when service is needed Communications HVAC communications Allows local and remote diagnostics for better troubleshooting and new services

8 R7184U Feature Function Benefit
Communicating Accessories Additional devices to utilize communications capability Remote access, test tools Leadwire and Quick Connect Termination Support both quick connects and leadwire termination Replaces both OEM and installed base with one model Alarm Contacts Indication of control lockout Allows connection to security system or other indications to warn of control lockout Selectable Valve On Delays Field selectable valve on delay Allows user to inventory and carry one universal product for various valve on delay times Selectable Blower Off Delay Field selectable blower off delay Allows user to inventory and carry one universal product for various blower delay on times

9 Key Features: Oil Primary R7184U
EnviraCOM™ Communications Data Port Diagnostic LED – enables monitoring of system status to speed troubleshooting Limited reset – prevents continued homeowner reset without proper service checkout EnviraCOM™ Terminals. Alarm Contacts (dry contacts, normally open) – Provides switch action to remote alarm panels T-T Terminals Timer Setting Dip Switches – Universal Application

10 Installation

11 Installing the R7184U Follow the installation instructions per the application: Locate proper location Mount Wire per application type Oil fired boiler without EnviraCOMTM Oil fired boiler with EnviraCOMTM Oil fired forced air with EnviraCOMTM Etc.

12 Set-Up

13 Set-Up of the R7184U: Setting Delay Times
1st Switch: Valve On Delay 2nd & 3rd Switches: Burner Motor OFF Delay Sec Valve On Delay ON Easy access to set up delay times. ON ON ON ON 0 min min min min.

14 Setting Delay Times Oil Pump Delay ON 1 2 3 OR Delay Off Delay On ON
ON ON OR 3 3 Delay Off Delay On

15 Model Valve ON Delay Blower OFF R7184A None None R7184B 15 None
Setting Delay Times Delay Choices Model Valve ON Delay Blower OFF (Seconds) (Minutes) R7184A None None R7184B 15 None R7184P R7184U 0 or

16 Troubleshooting

17 Troubleshooting of the R7184U
The indicator light on the control provides lockout, recycle and cad cell indications as follows: Flashing at 1 Hz (1/2 second on, 1/2 second off): system is locked out or in restricted mode. Flashing at 1/4 Hz (2 seconds on, 2 seconds off): control is in recycle mode. On: cad cell is sensing flame. Off: cad cell is not sensing flame. Cad Cell Resistance Check For proper operation it is important that the cad cell resistance is below 1600 ohms. During a normal call for heat, once the control has entered the Run mode, press and release the reset button. Indicator light will flash 1 to 4 flashes. See next slide for equivalent cad cell resistance.

18 Troubleshooting: Diagnostics
Push lockout button once to get cad cell resistance and system status Flashes Indication Steady Control is sensing flame Off Control is not sensing flame Flashing ( ½ sec on / ½ sec off) Control is in lockout or restricted mode Flashing ( 2 sec on / 2 Sec off) Control is in recycle mode 1 < 400 ohms 2 ohms 3 ohms 4 1600 – 5000 ohms *CAD Cell Ohms decreases with increased flame brightness

19 Troubleshooting of the R7184U
For Honeywell EnviraCOM™ enabled equipment Read EnviraCOM Error Codes Line Voltage Cad Cell Ohms The QuickLookTM 72 is available through

20 Product Cross Reference

21 Product Cross Reference
Where do I find Honeywell universal electronic oil primary cross reference information? Honeywell Application Selection and Cross Reference Guide – Form Honeywell Laminated Truck Visor – Form Honeywell Oil Primary Countermat – Form Honeywell Residential Technical Support:

22 Oil Primary Cross Reference Table
This chart can be found in the Residential Combustion Application Guide: Form #

23 See Cross Reference Search box in right column.

24 R7184U Oil Primary Advantages
When promoting the R7184U Universal Oil Primary keep these advantages in mind: Universal Compatibility This control replaces Carlin, White Rodgers and all prior Honeywell Oil Primary Controls Honeywell R7184U “Exclusive Features” Pump priming cycle Cad cell flame strength indicator Limited recycle Diagnostic LED Indicator light monitors burner flame status and system lockout EnviraCOM communications enabled It includes EnviraCOM™ Connection for local networking & diagnostics Compatible with Honeywell EnviraLINK™ remote monitoring application

25 R7184U Interrupted Electronic Oil Primary Knowledge Test

26 R7184U Oil Primary Knowledge Test
Now that you completed this training module, take the short quiz to test your knowledge.

27 Test The R7184U can be used in both hydronic and forced air systems? T or F The Honeywell R7184U can replace ALL prior Honeywell oil primary controls, as well as Carlin and White Rodgers controls? T or F There is one way to determine cad cell ohms and that is through the diagnostic LED? T of F The R7184U is available in 3 lockout times, 15, 30 and 45 seconds? T or F The pump priming cycle requires that the installer be present at the oil primary to purge the line? T or F

28 Test Limited reset prevents the homeowner from continually pressing the reset button instead of calling for service? T or F The diagnostic LED can identify system lockout? T or F The valve on and blower off delay times are factory set and cannot be set by the installer during installation? T or F The limited recycle features can help prevent clogging the heat exchanger or flooding? T or F EnviraLink is the remote monitoring service that can be used with R7184U EnviraCOM enabled oil primary? T or F

29 Answer Key T F