Objectives Review exam problems Further discuss final projects
Compare VAV systems with DOAS systems
2
VAV Example One system Multiple Spaces/Zones
- VAV box for each space/zone
3
VAV System Terms & Equations (you can find them in ASHRAE Standard 62)
Fraction of minimum outdoor air in space/zone supply air Xi = VOAi / VSAi Critical space Space with maximum Xi , Z=max(Xi) Fraction of outdoor air in system supply air X = sum(VOA ) / sum(VSA) Required Fraction of outdoor air: Y=X/(1+X-Z)
4
Other Issues Related to VAV
Reheaters (sizing and control) Fan control Minimum supply air Occupancy sensors
5
DOAS System
6
DOAS with multi-split systems
Fresh air?
7
DOAS fresh air configurations
8
DOAS fresh air configurations
9
Issues Related to DOAS Split of sensible and latent load
Selection of hydronic system Winter vs. summer operation Winter operation with DX systems (heat pump)