Replacing Gas Chlorine with Onsite Sodium Hypochlorite Generation
Tim Geraghty, P.E. Division Manager Alliance Water Resources, Inc. Introduce topic. Discuss my education and 24 yrs experience in design, construction and operation of water systems.
3
Replacing Gas Chlorine with Onsite Sodium Hypochlorite Generation
Goal: help other utility managers decide if changing disinfectants would be worth considering What made us consider a change What options we considered Costs & benefits Design Construction
4
Background Most water treatment facilities use chlorine as their primary disinfectant Chlorine use became widespread in the early 1900’s Chlorine has a proven track record Chlorine gas is a highly hazardous chemical
5
Background St. Charles County, MO Water Treatment Plant has successfully used chlorine gas in 1-ton containers as a disinfectant since 1941 Plant capacity 8 MGD average 22 MGD peak
6
Water Treatment Plant, St. Charles County, MO 1940 2013
Discuss plant’s history 1940 2013 They don’t build ‘em like they used to
7
Water Treatment Plant 1940 2013 Not much has changed
8
Background 2005 - Water District purchased the treatment plant
Water District completed an overall WTP assessment Reviewed existing condition of the plant facilities & equipment Reviewed plant processes Developed and prioritized a capital improvement plan
9
Background Results of the plant assessment
Electrical/efficiency upgrades $1.4M Filter upgrades $2.3M Booster pump station replacement $4.0M Replacement of the gas chlorine feed system $2.5M Lime, ammonia and fluoride system improvements $0.9M Total $9.7M
10
Why consider changing from chlorine gas?
Need to update existing chemical processes, controls and equipment due to age Safety Employees People in the surrounding community Environment
11
Why consider changing from chlorine gas?
1997 – one ton container split 25 miles away in Kirkwood, Missouri 2012 – one ton container leaking 10 miles away in Chesterfield, Missouri
12
48,000 pounds released - 63 people injured
Why consider changing from chlorine gas? 2002 – leaking 1” hose connected to 90-ton railcar 50 miles away in Festus, Missouri 48,000 pounds released - 63 people injured Pictures from US Chemical Safety & Hazard Investigation Board Report, 2003
13
Why change? Federal OSHA Safety Regulations (TOSHA requirements may be more stringent) EMPLOYEES Coordination with LEPC OSHA Process Safety Management (29 CFR ) Management of Change Chlorine Institute Pamphlet 65 for PPE Respirators – fit testing, medical baselines and periodic evaluations Chlorine Institute Pamphlet 155 for water and wastewater operators Hot Work Confined Space Training Contractor Safety & Record Keeping Record keeping, record keeping, record keeping
14
Federal Safety Regulations - EPA
Why change? PEOPLE IN THE SURROUNDING COMMUNITY Estimating offsite receptors Hazard reviews US EPA Risk Management (in section 112(r) of the Clean Air Act) Operating procedures Compliance Audits Mechanical integrity Worst case release scenario Employee participation Coordinating with LEPC Alternative release scenarios Communication with the Public Offsite consequence analysis Regular re-submittals Federal Safety Regulations - EPA
15
Protect the Environment
Why change? Water Plant Missouri Conservation Department -Wildlife Area US Army -Training Area University Research Area (added political pressure from regulators) Protect the Environment
16
To decide if a disinfectant change was worthwhile, we reviewed our goals and other disinfectants
17
Review of Alternatives - Water Quality Considerations
Requirements for disinfection Groundwater Rule 4-log removal of viruses Chlorine contact time Effects of chlorination on pH Distribution system bacteria re-growth potential THM’s/HAA’s Nitrate formation Chlorite formation Water Quality Considerations
18
Review of Alternatives - Selection Criteria
Safety Life Cycle Costs Capital O&M labor Power Chemicals Waste treatment/hauling Chemical & power cost stability Chemical strength stability Chemical availability Review of Alternatives - Selection Criteria
19
Review of Alternatives - Selection Criteria
Need for additional treatment Level of automation Permitting issues Space requirements Operational flexibility, familiarity & simplicity Equipment reliability Selection Criteria
20
Review of Alternatives
Gas chlorine Ozone Ultraviolet (UV) Light Chlorine dioxide Hypochlorite Calcium hypochlorite Sodium hypochlorite Onsite hypochlorite generation Bulk deliveries Combinations of the above
21
Review of Alternatives
Gas Chlorine in 1-ton containers (current practice) Advantages – low capital and operating cost, simple operation, low maintenance Disadvantages – hazardous and toxic chemical, potential of leaks & high level of regulation
22
Review of Alternatives
Gas Chlorine in 150-pound cylinders Advantages – low capital and operating cost, simple operation, low maintenance Disadvantages – hazardous and toxic chemical, potential of leaks & high level of regulation Switching to smaller cylinders would reduce the quantity released during a major leak, but more changeovers & handling would be required
23
Review of Alternatives
Ozone Expensive Additional disinfectant needed for maintaining residual in distribution Often used to eliminate a specific contaminant Ultraviolet (UV) Light Review of Alternatives
24
Review of Alternatives
Chlorine dioxide Strong disinfectant Stops THM formation May require additional treatment for chlorite Often used for pre-treatment – not as the lone disinfectant
25
Review of Alternatives
Bulk Sodium Hypochlorite (typically 12.5% solution) Advantages – Low capital cost, generally safer than chlorine gas Disadvantages – High operating cost, degradation, corrosive health hazard
26
Review of Alternatives
Generated Sodium Hypochlorite (0.8% solution) Advantages – no storage of highly hazardous chemicals, consistent product concentration Disadvantages – High capital cost, hydrogen gas byproduct, short product storage time
27
Review of Alternatives Process Schematic
Bulk hypochlorite components Onsite hypochlorite generation components
28
Bulk Sodium Hypochlorite (11 - 15%)
Hazardous to Environment, Users, and Community Chlorine Gas Bulk Sodium Hypochlorite ( %) NFPA Rating Health = 4 Flammability = 0 Instability = 0 Oxidizer Health = Lethal Short Term Exposure = Burns, Chest Pain, Emotional Disturbances, Lung Damage, Death Physical Hazards = Containers may rupture or explode. 4 NFPA Rating Health = 2 Flammability = 0 Instability = 1 Oxidizer Health = Intense or continued exposure could cause temporary incapacitation or residual injury. Instability = Can become unstable at elevated temperatures and pressures. 2 1 OX OX MIOX Proprietary and Confidential- DO NOT DISTRIBUTE
29
Environmentally Benign
0.45% Generated FAC or 0.8% Generated FAC NaCl (SALT) NFPA Rating Health = 1 Flammability = 0 Instability = 0 Health = Exposure may cause mild irritation Instability = Normally stable, even under fire conditions. NFPA Rating Health = 1 Flammability = 0 Instability = 0 Health = Exposure may cause mild irritation Instability = Normally stable, even under fire conditions. 1 1 MIOX Proprietary and Confidential- DO NOT DISTRIBUTE
30
Review of Alternatives
Comparison Capital Cost Annual O&M Hazard Potential* Chlorine Gas (add scrubber & other controls) $900,000 $50,000 highly hazardous gas Ozone High limited UV low Bulk Sodium Hypochlorite $650,000 $160,000 highly corrosive liquid Generated Sodium Hypochlorite $1,900,000 $100,000 hydrogen gas by-product Of these alternatives, only gas chlorine requires PSM & RMP programs
31
Review of Alternatives
Cost savings due to eliminating PSM training and administration 60 training hours annually for operators & maintenance staff 200 hours annually for contractor training 100 hours annually for administration per year training reports, maintenance reports, PSM Manual updates, PSM and RMP annual SOP certifications, periodic resubmission of PSM and RMP documentation, internal compliance audits, testing of chlorine sensors, … $10,000 - $15,000 per year
32
Review of Alternatives
UV and Ozone were ruled out - high costs + additional need for residual disinfectant For the two hypochlorite alternatives, onsite generation preferred because of lower O&M Chosen Alternative: Onsite Generation of Sodium Hypochlorite because of reduced safety concerns; estimated additional cost of treated water less than $0.04 per 1,000 gallons (<1% of user rate)
33
Design Considerations
First step – choose a hypochlorite generator manufacturer Equipment varies by manufacturer Major considerations Safety considerations Ease of operation/number of components Equipment footprint Life cycle costs Availability
34
Design Considerations
Choosing a hypochlorite generator manufacturer The cost of materials varies by manufacturer but one pound of chlorine is generated by roughly: 15 gallons soft water (at gpm and about 60 psi) 3 pounds salt 2 kilowatt-hours
35
Design Considerations – Site Visits
Designers and operators visited several installations of various manufacturers
36
Design Considerations
Efficiency & Complexity Indoor Equipment (generators, blowers, power and control panels) Room arrangement/ available space HVAC requirements & equipment heat loss Outdoor Equipment (tanks & accessories) Sunshades
37
Design Considerations
Sodium Hypochlorite Storage Tanks Storage time Degradation (esp. for 12.5%) Sodium Hypochlorite Metering Pumps Based on each feed point’s chlorine demand Sized for both 12.5% and 0.8% solution
38
Design Considerations
Standby Options Standby generator Provisions for bulk delivery Plant Shutdown (generally available at this location September through May)
39
Capital Costs Equipment Bids Construction Bids (includes equipment)
ChlorTec (two 750 ppd units)$ 536,500 MIOX (three 500 ppd units) $ 572,980 PSI (two 800 ppd units) $ 619,500 Construction Bids (includes equipment) Engineer’s final estimate $2,041,000 Low of 5 bids: KCI Construction $2,213,500
40
Chosen Alternative - MIOX
Simplicity / fewest components Smallest footprint / able to fit most equipment in the existing building
41
Design Considerations for Chosen Alternative
System Control Panel Inputs Water hardness Brine tank level Storage Tank Level System Components Brine pump Generators/rectifiers Hydrogen dilution blowers Sodium hypochlorite storage tank level
42
Chosen Alternative - MIOX
43
Construction Construction Sequence Site work
Install outdoor hypochlorite tanks Install new process piping and metering pumps Place bulk hypochlorite (12.5%) system in operation Remove existing gas chlorine piping and equipment Install hypochlorite generators in the space vacated by the gas chlorine system
44
Construction Schedule and current progress
Site work completed (relocated storm & sanitary sewers) Bulk tanks, piping, water softeners, pumps and dilution panel installed
45
Construction Schedule and current progress
SOP’s written and operators trained in bulk chemical feed process Bulk chemical (12.5%) and tanks being put in operation next week Remaining work to be completed by July 2013 Remove existing gas chlorination system Install hypochlorite generation and other equipment inside the building and start-up
46
Key Points Ultimately, the Water District Board decided that increasing the level of safety was worth the additional capital and O&M costs Our chosen disinfection alternative was not the lowest cost alternative The chosen manufacturer’s equipment was not the lowest cost alternative Involving the operators in the decision- making was critical and strongly influenced the decision The operators (and probably their spouses) can’t wait for the workplace to be safer
47
For More Information www.alliancewater.com Tim Geraghty, P.E.
Special Thanks to Black & Veatch and Parkson Disinfection for technical information they provided for the presentation For More Information Tim Geraghty, P.E. Division Manager Alliance Water Resources 100 Water Drive O’Fallon, MO 63368 x101