Download presentation
Presentation is loading. Please wait.
Published byWidya Sugiarto Modified over 5 years ago
1
Objectives Review conductor and conduit selection
Learn about protection systems (basic rules) Learn to design Residential Electrical Systems
2
Current-Carrying Capacity
Ref: Tao and Janis (2001)
3
Tubing size Ref: Tao and Janis (2001)
4
Other Issues In general, no more than 40% of raceway can be filled with wiring Why? To prevent extensive heat up To prevent physical installation of wires
5
Conductor Rules Explain each of the following: In the same conduit:
No more than 4 90 ° bends are allowed between pull boxes In the same conduit: No mixing of high- and low-voltage conductors No mixing control and power conductors No mixing phone and power conductors Do place all three phases in the same conduit
6
Receptacles and switches
Receptacles (duplexes) Number Shape Voltage rating Current Rating Number of poles and wires Switches Type (NEC rating) Contact method Speed of operation Voltage rating Number of poles Method of operation Enclosure Duty Other (dimming)
7
Protective Devices What are we protecting from? Circuit breakers
Overcurrent Overvoltage Circuit breakers Switch that responds to thermal or short circuit loads Can be bimetal, magnetic, or electronic Reusable, remote control, compact, can be used as disconnect switch Fuses Melting metal Self destructive, larger
8
Why use fuses instead of circuit breakers?
Fuses can be used multiple times Fuses are more aesthetically pleasing Fuses are safer Fuses cause less damage to equipment
9
Ref: Tao and Janis (2001)
10
Emergency power systems Batteries Power generators
Motor starters ON-OFF switches are NOT for motors Motor circuit-rated switches Reduce the current during the start until the motor rich full speed Protect the motor form overload Emergency power systems Batteries Power generators
11
Residential Systems Very little variation between different houses
Many similarities to commercial buildings Particularly as you get close to end uses Need to be watchful for unusual circumstances
12
Procedure Analyze building needs Determine electrical loads
Select electrical systems Coordinate with other design decisions Prepare plans and specifications
13
List of needs Appliances (incl. HVAC) Receptacles Lighting
Ground fault protected (GFI/GFCI) Switched Lighting Switches Ceiling Fans
14
Example House Master Bedroom Bathrooms
Entry and Outdoor (AC compressor) Bedrooms Dining and Mechanical Closet (resistance heat) Kitchen (appliance circuits, range, oven) Family Garage/Laundry/Closet (resistance water heater, dryer)
15
Outdoor Bathroom Closet Bedroom 2 Laundry Kitchen Bathroom Mechanical closet Family room Master Bedroom Entry Bedroom 3 Dining Garage
16
NEC about receptacles No longer approve non-polarized and ungrounded receptacles in new installations. Each receptacle (duplex) is rated for 1.5 A. For 120 V: Each duplex 1.5×120 = 180W
17
Residential system sizing
Typically 3 wire 1 phase system 120/240 V Procedure defined by NEC article 220: Identify characteristic electrical loads Add lighting (3W/ft2) Add two 20 Amps circuits for kitchen Add one 20 Amps circuit for laundry Electricity for HVAC equipment based on requirement for heating or cooling
19
Summary of Power Sizing
Include enough capacity for heating and cooling Work through kitchen and then other rooms Include any items that are unusual Take first 10 kVA and then 40% of remaining load
20
Panel Sizing Find panel power usage and neutral usage
Size panel conductors and associated conduit and switches
21
Electric panel - 3 wire 1 phase 120/240
22
Homework 5 - problem 2 Sizing the residential electrical system
Defined by NEC article Similar to the example we worked out You need to collect the data for several characteristic consumers Includes conductor sizing
Similar presentations
© 2024 SlidePlayer.com. Inc.
All rights reserved.