Presentation is loading. Please wait.

Presentation is loading. Please wait.

1. TURBOGENERATOR ROTOR WINDINGS

Similar presentations


Presentation on theme: "1. TURBOGENERATOR ROTOR WINDINGS"— Presentation transcript:

1 1. TURBOGENERATOR ROTOR WINDINGS
TESTING THE FIELD WINDINGS OF LARGE ELECTRICITY GENERATORS USING THE RSO METHOD. 1. TURBOGENERATOR ROTOR WINDINGS ROWTEST LTD.

2 LARGE GENERATOR ROTOR TYPES
The 2 main types of large generator rotors are: 1. Cylindrical rotors for use with high-speed turbo generators as shown above. The dimensions of a large rotor are typically 16m long, 2m diameter and weight 80 tonnes. The RSO test is primarily used for testing these rotor types. 2. Lower speed salient pole rotors, which are used in hydro-electric generators. Some examples of salient pole rotors are shown in the next figure. 

3 EXAMPLES OF SALIENT POLE ROTORS
Salient pole rotors in large hydro-electric generators rotate at lower speeds and have multiple sets of magnetic poles as shown above. The RSO test is generally not suitable for testing using these types of rotors.

4 ROTOR WINDING DETAILS The rotor is a cylindrical electromagnet which rotates at high-speed and is normally powered by a gas and/or steam turbine connected directly to the rotor shaft. For a typical large (600MW) generator, the magnetic field is produced by passing a direct current of around 3000 amps through turns of high-conductivity copper bar. The value of the magnetic field produced by the rotor winding is directly proportional to the product of the current and the number of turns in the winding.   The magnetic field, is at right-angles to the axis of rotation and the rotor has clearly-defined north and south poles. The rotating magnetic field induces voltages in the 3-phase stator winding (see next slide) of typically 25KV.

5 Principle of operation of a generator having a 2-pole rotor.
3-PHASE GENERATORS Principle of operation of a generator having a 2-pole rotor. A rotor can have 2 or more magnetic poles and these determine the relationship between the rotor speed of rotation and the supply frequency generated. For example, the frequency generated by a 2-pole rotor will equal the number of rotations per second, while for a 4-pole rotor, the frequency generated will be 2 x the number of rotations per second etc.

6 CONSTRUCTION OF CYLINDRICAL TURBO GENERATOR ROTORS
A typical turbo- generator field rotor (courtesy of GE Power Systems)  The rotor body is a solid steel forging containing radial slots for the coils which make up the electromagnets (rotor windings). The turns of the coils are normally rectangular copper bars insulated with an epoxy material. In a 2-pole rotor, there are typically 8 pairs of slots for each pole of the electromagnet, with each slot containing up to 20 conductor turns.

7 ROTOR WINDING DETAILS At the ends of the rotor body, the turns pass from the end of one slot to its equivalent slot on the other side of the magnetic pole and are held in place in the end regions by steel end (retaining) rings. Cylindrical rotor windings normally have either a single pair or 2 pairs of magnetic poles, and these are known as 2 or 4-pole rotors. An important characteristic of all cylindrical rotor windings is that they are symmetrical when viewed from either slip-ring. A 2-pole rotor contains 2 identical half-windings, one for the North pole and one for the South pole, as shown in the next slide.

8 MAGNETIC POLES The Figure shows a simplified representation of the magnetic field path, magnetic pole locations and conductor slots for a typical 2-pole cylindrical turbogenerator rotor. There is a single pair of magnetic poles, which are located along the centre line of each set of coils. There are also 2 identical half-windings, corresponding to the north and south magnetic poles (poles 1 and 2).

9 The Figure shows examples of 2 cylindrical rotors with the end rings removed to expose the copper bars in the end regions of the rotor winding.

10 DETAILS OF HALF-WINDINGS
A 2-pole rotor contains 2 identical half-windings, one for the North pole and one for the South pole, as shown below. Each half-winding is identical. Representation of a 2-pole rotor winding showing the identical North and South pole half-windings

11 A TYPICAL LARGE TURBO-GENERATOR ROTOR WITH THE RETAINING END-RINGS REMOVED.
The direct current through the rotor winding is usually produced by a DC (or rectified-AC) generator known as the exciter, mounted on the rotor shaft. Typical exciter voltages are around 300V DC, so the rotor windings have only relatively low-voltage insulation when compared with the high-voltage (25KV) insulation required for the stator windings.

12 CROSS-SECTION OF A RADIAL COIL SLOT
The figure shows a cross-section of a typical radial slot (in this case, containing 7 turns of insulated copper bar) The insulation between the turns is typically around 10 to 15 mils thick and is made from Nomex paper or resin impregnated epoxy glass laminate. One consequence of this form of construction is that the rotor winding approximates to a high-frequency transmission line (similar to a coaxial cable) as the conductors sit within enclosed conducting slots in the rotor forging. This property is used in the RSO test to identify and locate approximately any faults in the rotor winding. (GE Power Systems)

13 TYPICAL FIELD WINDING SHOWING BOTH THE MIDDLE AND END SECTIONS.
Some of the turns are shown lifted from the slots.

14 Coil construction

15

16 SECTION 2. ROTOR WINDING FAULTS

17 Examples of coil insulation breakdown
FAULTS IN ROTOR WINDINGS A 2-pole rotor rotates at 3000/3600 rpm to produce a 50Hz or 60Hz alternating voltage in the (3-phase) stator windings. The rotor windings experience large centrifugal forces, which can damage the insulation, resulting in 2 possible types of winding faults as shown in the figure : 1. Faults from the winding to the rotor body ('earth faults') 2. Faults between parts of the winding ('inter-winding or inter-turn faults') Examples of coil insulation breakdown (GE Power Systems)

18

19

20 EXAMPLE OF SHORTED TURNS IN END-REGION

21

22

23

24

25 DETECTING AND LOCATING WINDING FAULTS
An earth fault is detectable with a simple multimeter and it may be possible to operate a rotor having a single earth fault (preferably with some form of alarm system to detect the onset of a second earth fault). The existence of an inter-winding fault is not easily detected by simple electrical methods. However, a rotor winding with a serious inter-turn fault will frequently overheat, leading to more serious local damage, or may display excessive mechanical vibration and have to be taken out of service. As the DC current is large and the short circuits will have finite resistance, large quantities of heat can be generated at the fault location and this can cause damage to the remaining insulation, resulting in severe damage to the rotor windings. Short circuits can also cause magnetic imbalance, giving rise to increased vibration levels.

26 TEST METHODS FOR DETECTING FAULTS IN ROTOR WINDINGS
Generator rotors are routinely tested to detect these types of fault, both during construction and also before and after routine generator maintenance. One standard test method used is time-domain reflectometry. However, unlike the similar technique used for testing transmission lines, a custom test instrument (an RSO Reflectometer) is required, to overcome complications caused by the imperfect transmission line equivalence of the rotor winding.

27 Thank you for viewing this presentation.
If you have any questions, please send them to us at .com. We will try to respond to you as soon as we can.


Download ppt "1. TURBOGENERATOR ROTOR WINDINGS"

Similar presentations


Ads by Google