Presentation is loading. Please wait.

Presentation is loading. Please wait.

R200 and ATS100 Presentation 01/12/2013.

Similar presentations


Presentation on theme: "R200 and ATS100 Presentation 01/12/2013."— Presentation transcript:

1 R200 and ATS100 Presentation 01/12/2013

2 Easergy R200 and ATS100 Control and Monitoring distributed system
All the power and experience of Easergy range now inside Premset

3 The new generation of switchgear technology
Premset: a disruptive technological breakthrough opening to a new generation of switchgear - Efficiency Smart grid and advanced management solutions across the network Intelligent, smart grid-ready solutions: - Feeder automation - Load management - Asset management - Automatic Transfer System Architecture with distributed intelligence Premset The new generation of switchgear technology The new generation of switchgear technology also means embedding the smart devices directly inside the switchgear Schneider Electric UK Medium Voltage Activity 10/02 Product Marketing

4 R200 and ATS100 System

5 Premset Control & Monitoring

6 Embedded intelligence in switchgear
Local SCADA DMS LAN WAN Ethernet Modbus IP, IEC , DNP3 IP RTU, ATS Power Supply Modbus Serial and IP IEC /104 DNP3 Serial and IP PSTN RS232/485 Radio (FFSK) GSM / GPRS 3G R200 or ATS100 PS100 Modbus RS485 SC110 Flair 23DM PM800 VIP410 Energy Quality Monitoring Switch Controller FPI & Voltage presence Self powered Protection

7 System functional summary
Controls and monitors MV switchgears: SC1x0 (up to 29) Detects the passage of fault currents: Flair 2xD: All earthing systems Detects Voltage presence/absence: VD23: Highly configurable Measures: Current, voltage, power, energy, .... : PM Protection relays : VIP or SEPAM Automated network reconfiguration: ATS 100: ACO or BTA Supplied by a High availability Power Supply and battery: PS100 Configuration and Diagnostic tool through Web server Communicates to DMS and/or local SCADA Can integrate other Modbus slaves NEW!

8 Embedded intelligence in switchgear
Functional approach based on optional and independent modules to cover various combination and offer just enough architecture Remote Communication:R200 or Source transfer: ATS100 Modules fully integrated in functional unit Including sensors, switchgear interface, power supply, communication, HMI Pre- engineered, factory-tested, cost effective Easy integration based on : Field bus communication between modules Pre-cabling inside cublicle Other Modbus slave devices can be integrated: Sepam 80, PM, Ion meters, etc... Modbus Power supply : PS100 Fault passage indication : Flair 23DM Protection : VIP410, Sepam 20 or Sepam 40 Switchgear Control : SC110A or SC100E Voltage detection : VD 23 Power Monitoring : PM 800

9 Catalogue R200/ATS100 system Stand alone R200 ATS100 SC1x0 Flair 2xD
6 references, according to communication medium R200 Remote com. Remote com. + Source transfer 6 refs: ACO or Bus Tie, and no modem, GPRS or 3G ATS100 SC1x0 Local/remote control SC100A: Vdc SC100E: Vdc Vac SC110A: Vdc SC110E: Vdc Vac Flair 21D: Supercap Flair 22D: Li battery Flair 23D: Ext Vdc Flair 23DM: FPI + Voltage relay + Modbus communication Flair 2xD Fault passage indicator Voltage detection relay VD23 Voltage detection relay VD23 Flair 23DM: FPI + VIP410A VIP410E Self powered protection relay VIP400 VIP40/45 VIP 4 PS100 24VDC PS100 48VDC PS100 Power supply Sepam Auxilliary powered protection relay Sepam 20, 40, 60, 80 PM Energy Monitoring PM800

10 Easergy R200/ATS100 Common Functions

11 Substation Monitoring
Data acquisition from local devices Fault detection: Flair Protection relays trip indication Cubicles status Voltage presence: VD23 Measurement: Power Meter: I, U, power, energy, Concentrator of other Modbus slaves: Time stamping Clock synchronisation through DNP3 or IEC protocol or Ethernet Date stamping discrepancy: 20 ms Monitoring digital and analogue variables Managing alarms or simple recording: thresholds, dead band, ... Configurable recording settings Archival capacity: Event Log Alarm Log 2000 Measurement log 50000 System Log 6000

12 SCADA Communication NEW! Compatible with all SCADA Systems
Catalogue of protocols including the major standards with IP versions IEC and 104 DNP 3 level 3 serial and TCP/IP MODBUS serial and TCP/IP Compatible with all communication media A large catalogue of built-in modems: RS232/485, radio (FFSK), PSTN V32, Ethernet, GSM/GPRS/3G The RS232/RS485 interface can handle external modems SMS, Mail One “modem” port + one Ethernet port NEW!

13 Standby supplies high availability Guaranteed Switchgear Operation
An energy Battery and charger sized to supply Motor drive systems: 24 or 48 VDC Transmission equipment: 12VDC, 1A permanent, 7 A peak Substation equipments Total max power 90W permanent Guaranteed long battery life A regulated and temperature compensated charger Protection against total discharging Schematic with external relays proposed for long duration outages Guaranteed power supply availability Continuous power supply self-checking Typical autonomy: 16 hours with 10 O/C cycles Alarm returned if fault occurs Battery service life at 20°C: 10 years

14 A powerful configuration tool 2 major new features for better efficiency and productivity
Off-line configurator: Same Web pages can run locally on the PC or on the R200/ATS100 Modbus slaves auto discovery with predefined configuration files NEW! NEW!

15 Easy to setup Easy&Quick System Configuration
Scan 1 2 3 4 ON T/R ATS 100 1 2 NEW! Data In order to make commissioning an easy, straight forward, and therefore fast task, R200 and ATS100 are fitted with features new to the Easergy range: User can activate a scan of the Modbus slaves that will automatically detect all slaves connected and the associated default configuration and data (Of course, this applies only to Modbus slaves part of the system). User tasks is therefore finally limited to configuring each of the devices according to his application needs as well as configure R200 specific configuration parameters such as communication to SCADA Scan & Modbus slaves auto-discovering Display the single line diagram Display each device data Configure each device according to application and R200 (communication etc...)

16 Powerful diagnostic and alarm through Web pages simplicity
Powerfull diagnostic and alarm through Web pages Data view Single line System view Alarming

17 A whole system for control and monitoring
32 devices max Daisy chaining of smart modules Self configuration Automatic Modbus configuration Automatic module detection and configuration Sensors, HMI, devices integrated in cubicle One power supply for the whole switchboard See each product presentation (SC100, PS100, Flair 2xd, etc…) for more details)

18 Easergy ATS100 Specific Functions

19 ATS100 Features Module dedicated to source change over Main functions
Inherits from all R200 functions Own box + dedicated interface Only field bus interface with the switchgear Main functions Automatic source change over (lines, bus tie) Safe manual operation With or without // coupling Remote communication (Ethernet, 2G, 3G)

20 ATS100 Architecture Auxiliary supply provided by PS100
SC110 SC110 Auxiliary supply provided by PS100 ATS100 : 12V or 24 or 48V SC110, Flair 23DM, motorisation : 24 or 48V

21 ATS- ACO : 1/ lines

22 ATS-BTA : 2/3 - 2 lines + bus tie
Bus tie normally open

23 Dedicated HMI (2/3) Local /remote On / Off Automatic change over
Behaviour Auto return (no predefined normal source) No return (keep on back-up source after change over) Self return (back on normal source possible after change over) Manual operation Sequenced operation on switchgear

24 Dedicated HMI (3/3) Reset automation (Unlock)
LED and communication test (SCADA and system)


Download ppt "R200 and ATS100 Presentation 01/12/2013."