Presentation is loading. Please wait.

Presentation is loading. Please wait.

3AH5 Vacuum Circuit-Breaker For Standard Applications

Similar presentations


Presentation on theme: "3AH5 Vacuum Circuit-Breaker For Standard Applications"— Presentation transcript:

1 3AH5 Vacuum Circuit-Breaker For Standard Applications
Siemens Medium Voltage © Siemens AG 2009 Sector Energy, Business Unit Medium Voltage

2 3AH5 Vacuum Circuit-Breaker Directory
Technical Data Portfolio Product Features Details Applications September 2009

3 3AH5 Vacuum Circuit-Breaker 1. Technical Data
Rated voltage up to 36 kV Short-circuit breaking current up to 31,5 kA Operating current up to 2500 A Mechanical operating cycles 10,000 (M2) Electrical operating cycles 10,000 (E2, C2) September 2009

4 3AH5 Vacuum Circuit-Breaker 2. Portfolio
September 2009

5 3AH5 Vacuum Circuit-Breaker 3. Product Features
Main Data 12, 17,5, 24 & 36 kV 800 to 2500 A 13,1 to 31,5 kA Up to 10,000 mechanical operating cycles Type tested according to IEC Your Benefit Usage for all standard application in medium voltage Compact dimensions Maintenance free up to 10,000 operating cycles September 2009

6 3AH5 Vacuum Circuit-Breaker 3. Product Features
Column construction Vacuum interrupters are vertically arranged Free convection possible Solid insulation material is minimised as far as possible Your Benefit High mechanical stability Compact dimensions No forced-cooling up to 2500 A Very low fire load Easy access to all parts September 2009

7 3AH5 Vacuum Circuit-Breaker 4. Details
Hand crank coupling Push button “ON” Indicator „Closing spring charged“ Counter for “Operating cycles” Push button “OFF” Indicator „Closed/Open“ September 2009

8 3AH5 Vacuum Circuit-Breaker 4. Details
Operating unit Cooling element Auxiliary switch Gearbox Shunt release Opening magnet Closing spring September 2009

9 3AH5 Vacuum Circuit-Breaker 4. Details
Secondary equipment Basic equipped Fully equipped September 2009

10 Comparison: Use of Insulation and Plastics
3AH5 Vacuum Circuit-Breaker 4. Details Comparison: Use of Insulation and Plastics 3AH5 column construction SION shell construction Competition embedded pole 12 kV 4 kg 13 kg 17 kg 14 kg 23 kg 2500A Phase barrier drive 10 kg PMA 160 mm Phase barriers 17,5 kV 16 kg PMA 150/160 mm Phase barrier contact arms September 2009

11 Applications for 3AH5 5. Switching of Standard Applications
Requirements Switching of transformers, drives, capacitors, filter circuits, overhead lines and cables Synchronising of parallel networks Rapid load transfer of consumers to other incoming feeder Auto-reclosing in overhead lines to clear transient faults or short-circuits Switching of short-circuits Industry Application “Refinery” September 2009