Presentation is loading. Please wait.

Presentation is loading. Please wait.

Geothermal Alliance of Illinois

Similar presentations


Presentation on theme: "Geothermal Alliance of Illinois"— Presentation transcript:

1 Geothermal Alliance of Illinois
Variable Speed Pumping Control Strategies for ECM Pumps Geothermal Alliance of Illinois March 11, 2019 Tom Wyer, Geo-Flo Products Corporation

2 Overview This presentation will provide an overview of the control strategies used with modern ECM pumps in closed-loop geothermal systems, with a focus on installation and commissioning simplicity, and energy efficiency. Constant and proportional pressure control modes will be explained and compared. This information will be useful for contractors and engineers installing multiple geothermal heat pumps on a common ground loop heat exchanger.

3 Goals Review the benefits of variable speed pumping on geothermal systems Review PSC, VFD, and ECM pumps Review basic control strategies for modern ECM pumps Learn to read pump performance and power curves for ECM pumps Understand the two common differential pressure control modes including advantages/disadvantages of each mode

4 Review benefits of VS Pumping
Drivers for Geothermal Heat Pump System Efficiency Review benefits of VS Pumping Geothermal heat pump unit efficiency Duct design and installation Ground loop design and installation Pumping efficiency Main drives from a product standpoint Items 3 and 4 are closely related

5 Review benefits of VS Pumping
Variable Speed Pumping Advantages Review benefits of VS Pumping Increased system efficiency (next slides) Lower operating costs Added start-up/service benefits Some systems display one or more Pump speed (RPM) Power (W) Head (Feet or PSI) Flow rate (GPM) EWT/LWT HE/HR read-out

6 Review benefits of VS Pumping
Pumping Contribution to System Efficiency Review benefits of VS Pumping Manufacturers catalog data for COP/EER does not include pumping watts AHRI/ISO/ASHRAE certified data for COP/EER includes pump watts based on the following formula: Pump power correction (W) = (gpm x ) x (Press Drop x 2990) / 300 Where "Press Drop" is the pressure drop through the unit’s heat exchanger at rated water flow in feet of head Example: 4 ton system with 11 ft of gpm Pump power correction = 83 Watts This is incredibly low, and causes AHRI efficiency to be overstated in most cases (if using constant speed pumps) Repeat bullet 1 for emphasis Pressure drop is through the unit only; does not include loop

7 benefits of VS Pumping system efficiency
Pumping Contribution to System Efficiency benefits of VS Pumping system efficiency COP = [Heating Capacity/Power Input] ÷ 3.412 EER=[Total Cooling Capacity/Power Input] Pumping watts can be significant, and will affect system COP/EER Manufacture’s performance data: Full Load COP= [Heating Capacity/Power Input]÷3.412 Actual System COP=[Heating Capacity/(Power Input+ Pump watts)]÷3.412

8 benefits of VS Pumping system efficiency
Pumping Contribution to System Efficiency benefits of VS Pumping system efficiency For more information, see: New Technologies That Are Increasing Geothermal System Efficiencies-MNGHPA Jan 2013.pdf Variable speed pumps lead to greater system efficiency, and in some cases, are required. ASHREA 90.1 (2013)

9 PSC, VFD, AND ECM PUMPS Review ECM technology
PSC= Permanent Split Capacitor Motor that uses AC to generate a magnetic field in the stator to spin the pump’s rotor Typically single or multiple constant speed settings Advantages Simplest installation and setup Low first cost Disadvantages No control (over pumping) Highest operating costs Cannot be used on large systems (per ASHREA standards)

10 PSC, VFD, AND ECM PUMPS Review ECM technology
VFD=Variable Frequency Drive Controller that drives the pump motor by changing the frequency Advantages Lower operating costs than PSC Capable of scaling to very large systems (high head-high flow) Disadvantages Highest complexity installation and setup Higher installation cost Limited turn-down (20-30% of full speed) May require controls contractor, depending on system complexity

11 PSC, VFD, AND ECM PUMPS Review ECM technology
ECM=Electronically Commutated Motor Permanent magnet rotor Advantages Low complexity installation and setup Lowest operating cost Lower first cost than VFD Lower sound levels than VFD Disadvantages Higher first cost than PSC Limited capacity (head/flow) Must design loop for these pumps Limited voltage ranges ( V) Can be overcome with transformer

12 ECM CONTROL STRATEGIES OVERVIEW Control strategies
Modern ECM pumps have built-in controls that allow simple setup. ECM pump manufactures include: Grundfos (Magna3) Taco (00e Series) Wilo (Stratos) Bell & Gosset, Armstrong, others NOTE: This presentation is not intended to cover all control strategies or ECM pump options. See Magna3 Installation and Setup FEB.pdf for a discussion of control options offered by one pump manufacturer.

13 ECM CONTROL STRATEGIES OVERVIEW Control strategies
Constant/fixed speed ECM (i.e. no control ) Can be used in central, primary/secondary, and one-pipe systems Generally higher efficiency than PSC pumps due to ECM technology External control Can be used on any system type NOTE: See “New Technologies Increasing Geothermal System Efficiencies” (IGSHPA 2015) for detailed description of system types.

14 CONTROL STRATEGIES OVERVIEW Control strategies
Delta-T; Δ-T (Differential Temperature) Typically used on primary/secondary systems Must use external controller if more than on set point is required. Delta-P; Δ-P (Differential pressure) Constant pressure Proportional (variable) pressure More on next slides NOTE: Avoid “black box” automatic modes for geothermal systems

15 CONSTANT PRESSURE CONTROL Control strategies
Constant differential pressure (Δp-c) Pump maintains a constant differential pressure based on the programmed setpoint Output pressure of the pump is constant Pump adjusts speed (RPM) to maintain this differential pressure Power consumption can be determined from corresponding power curves

16 CONSTANT PRESSURE CONTROL Control strategies
Like constant speed pumps, the pump can only run at the intersection of the system curve, and the pump curve. Unlike constant speed pumps, ECM pumps have more than one curve. If system curve/duty point is beyond the max pump curve, the differential pressure will be less than desired.

17 CONSTANT PRESSURE CONTROL Control strategies
If system curve/duty point is below the constant pressure setpoint, the pump will run at the constant pressure setpoint. Result: Flow may be higher than required/desired, and/or additional pressure drop will be created by system devices (such as circuit setters or flow control valves)

18 PROPORTIONAL PRESSURE CONTROL Control strategies
Proportional (variable) pressure (Δp-v) Pump maintains a differential pressure between the setpoint, and ½ of the set point. Pump adjusts speed (RPM) to maintain this differential pressure. Output pressure varies linearly between setpoint and ½ setpoint Power consumption can be determined from corresponding power curves.

19 PROPORTIONAL PRESSURE CONTROL Control strategies
Like constant speed pumps, the pump can only run at the intersection of the system curve, and the pump curve. Unlike constant speed pumps, ECM pumps have more than one curve. If system curve/duty point is beyond the max pump curve/speed, the differential pressure will be less than desired.

20 PROPORTIONAL PRESSURE CONTROL Control strategies
If system curve/duty point is below the proportional pressure setpoint, the pump will run along the H to ½ H curve. Result: Flow may be higher than required, and/or additional pressure drop will be created by system devices (such as circuit setters or flow control valves)

21 COMPARING Δ-P MODES Control strategies Δp-c Δp-v Easy to understand ✔
Easy field troubleshooting Predictable flow when zone valves close Lower power consumption Lower noise ✔ = Advantage

22 COMPARING Δ-P MODES Control strategies
April 29, 2014 COMPARING Δ-P MODES Control strategies EXAMPLE SYSTEM: 3 heat pumps, customer wants VS & 100% redundancy 1 – 5 ton heat pump 1 – 3 ton heat pump 1 – 2 ton heat pump 10 tons total 20 % methanol See next slide for details 2” HDPE 410’ total ¾” loops, 650’ total

23 COMPARING Δ-P MODES Control strategies
April 29, 2014 COMPARING Δ-P MODES Control strategies COMPONENTS AND DIAGRAM FOR AN ECM PUMP SYSTEM WITH TWO PUMPS IN PARALLEL

24 COMPARING Δ-P MODES Control strategies EXAMPLE SYSTEM:
10 tons of equipment; 3 heat pumps (5, 3 and 2 ton packaged units) Unit 1= 5 ton + unit’s piping: 18.5 GPM Unit 2= 3 ton + unit’s piping: 10 GPM Unit 3= 2 ton + unit’s piping: 8.5 GPM Common loop pressure drop 25 GPM (all units running-max) 1st duty point: 43.5 GPM (all units running) 2nd duty point: 17.5 GPM (units 2 and 3 running) 3rd duty point: 10 GPM (unit 3 only) NOTE: See Understanding Pressure Drop Calculations and Pump Sizing For Large Residential-Light Commercial Geothermal Systems-Iowa Geo Conf 2015.pdf Assume 20% methanol 10X 650 ft of ¾” HDPE u-bends 410’ of 2” HDPE (plus two elbows)

25 COMPARING Δ-P MODES Control strategies
1st duty point: 43.5 GPM (all units running) Constant Proportional Side NOTE: at the duty point of each of these units, a two-pump flow center would be required. Each would consume around 320, 350, 390-watts (total of 1060 W) 539 W 539 W 53.9 W/ton 53.9 W/ton

26 COMPARING Δ-P MODES Control strategies
2nd duty point: 17.5 GPM (units 2 and 3 running) Constant Proportional Notice higher pressure than duty point on each. 419 W 289 W 84 W/ton 58 W/ton

27 COMPARING Δ-P MODES Control strategies
3rd duty point: 10 GPM (unit 3 only) Constant Proportional Notice higher pressure than duty point on each. 352 W 179 W 176 W/ton 89.5 W/ton

28 ? COMPARING Δ-P MODES Control strategies
Selecting the Δp control mode to use One manufacturer’s recommendation Notice higher pressure than duty point on each. ?

29 ? COMPARING Δ-P MODES Control strategies
Selecting the Δp control mode to use Another manufacturer’s recommendation ? Notice higher pressure than duty point on each.

30 COMPARING Δ-P MODES Control strategies
Simplified recommendation for selecting the control mode Design the system based on constant pressure mode Commission the system with proportional pressure mode If proportional pressure does not give you the flow you need at full load, switch to constant pressure Notice higher pressure than duty point on each.

31 Control strategies lessons
CONCLUSIONS Control strategies lessons ECM pumps integrate simple, yet powerful, pumping controls into a small, easy to install package Proportional/variable differential pressure results in decreased energy consumption at part load “H” setpoint has the biggest influence on pump energy consumption at full and part load Consider setpoint at manufacturer’s minimum recommended values at full load for maximum energy savings Use proportional pressure control whenever possible Assume 20% methanol 10X 650 ft of ¾” HDPE u-bends 410’ of 2” HDPE (plus two elbows)

32 Geothermal Alliance of Illinois
Questions? Geothermal Alliance of Illinois Tom Wyer, Geo-Flo Products Corporation


Download ppt "Geothermal Alliance of Illinois"

Similar presentations


Ads by Google