1 Shut 95SS2-235 (245)

2 IF draining to Recovery Header,
THEN check SHUT 95SS2-238 (248) AND

3 IF draining to Recovery Header,
THEN check SHUT 95SS2-238 (248) AND check OPEN 95SS2-237 (247)

4 IF draining to Drain Header ,
THEN check SHUT 95SS2-237 (247) AND

5 IF draining to Drain Header ,
THEN check SHUT 95SS2-237 (247) AND check OPEN 95SS2-238 (248)

6 Check OPEN 95SS2-234 (244) AND 95SS2-236 (246)

7 Check SHUT V1 (V2) on jumper

8 Insert jumper into test connections for A (B) Hotwell Conductivity cell.

9 Jumper Installation Sign Attachment 11 as installer.
Have a second person verify proper installation AND sign Attachment 11 as verifier.

10 Throttle OPEN V1 (V2) to obtain about 100 cc/min on 95FI-118 (120).

11 Hang tag on installed jumper identifying PC-02
Hang tag on installed jumper identifying PC as installation procedure