LOAD CONTROLLERS & LOADS
2
LOAD CONTROLLERS are devices that control power to loads
LOAD CONTROLLERS are devices that control power to loads. Basically, they are switches.
3
LOAD CONTROLLERS OHMMETER VOLTMETER AMMETER OPEN CLOSED
4
LOAD CONTROLLERS OHMMETER VOLTMETER AMMETER OPEN X Ω CLOSED
Disconnect power Isolate component Set ohmmeter on lowest scale Reading = Infinite ∞ O.L. CLOSED
5
LOAD CONTROLLERS OHMMETER VOLTMETER AMMETER OPEN X Ω CLOSED X Ω
Disconnect power Isolate component Set ohmmeter on lowest scale Reading = Infinite ∞ O.L. CLOSED X Ω Disconnect power Isolate component Set ohmmeter on lowest scale Reading = ‘0’
6
LOAD CONTROLLERS OHMMETER VOLTMETER AMMETER OPEN X Ω V CLOSED X Ω
Disconnect power Isolate component Set ohmmeter on lowest scale Reading = Infinite ∞ O.L. Reading = applied voltage CLOSED X Ω Disconnect power Isolate component Set ohmmeter on lowest scale Reading = ‘0’
7
LOAD CONTROLLERS OHMMETER VOLTMETER AMMETER OPEN X Ω V CLOSED X Ω V
Disconnect power Isolate component Set ohmmeter on lowest scale Reading = Infinite ∞ O.L. Reading = applied voltage CLOSED X Ω V Disconnect power Isolate component Set ohmmeter on lowest scale Reading = ‘0’ Reading = ‘0’ volts
8
LOAD CONTROLLERS OHMMETER VOLTMETER AMMETER OPEN X Ω V A CLOSED X Ω V
Disconnect power Isolate component Set ohmmeter on lowest scale Reading = Infinite ∞ O.L. Reading = applied voltage Reading = ‘0’ amps CLOSED X Ω V Disconnect power Isolate component Set ohmmeter on lowest scale Reading = ‘0’ Reading = ‘0’ volts
9
LOAD CONTROLLERS OHMMETER VOLTMETER AMMETER OPEN X Ω V A CLOSED X Ω V
Disconnect power Isolate component Set ohmmeter on lowest scale Reading = Infinite ∞ O.L. Reading = applied voltage Reading = ‘0’ amps CLOSED X Ω V A Disconnect power Isolate component Set ohmmeter on lowest scale Reading = ‘0’ Reading = ‘0’ volts Reading = ‘measureable’ amps
10
LOADS are devices that consume power and are basically ‘coils’ of wire.
11
LOADS = Coil OHMMETER VOLTMETER AMMETER Ω OPEN
Ohmmeter on lowest scale Reading = ∞ = O.L. SHORTED – an internal problem
12
LOADS = Coil OHMMETER VOLTMETER AMMETER Ω Ω OPEN
Ohmmeter on lowest scale Reading = ∞ = O.L. SHORTED – an internal problem Ω Ohmmeter on lowest scale Reading = ‘0’ or less than normal
13
LOADS = Coil OHMMETER VOLTMETER AMMETER Ω GROUNDED an external problem
Ohmmeter on highest scale Reading = any reading is NOT good GOOD
14
LOADS = Coil OHMMETER VOLTMETER AMMETER Ω GROUNDED an external problem
Ohmmeter on highest scale Reading = any reading is NOT good GOOD
15
LOADS = Coil OHMMETER VOLTMETER AMMETER Ω GROUNDED an external problem
GOOD Ω Ohmmeter on lowest scale Reading = any reading other than O.L. & ‘0’
16
LOADS = Coil OHMMETER VOLTMETER AMMETER V OPEN SHORTED –
Reading = applied voltage SHORTED – an internal problem
17
LOADS = Coil OHMMETER VOLTMETER AMMETER V V OPEN SHORTED –
Reading = applied voltage SHORTED – an internal problem V Short blew fuse: Reading = ‘0’ voltage
18
LOADS = Coil OHMMETER VOLTMETER AMMETER V GROUNDED an external problem
Grounded blew fuse: Reading = ‘0’ voltage GOOD
19
LOADS = Coil OHMMETER VOLTMETER AMMETER V V GROUNDED
an external problem V Grounded blew fuse: Reading = ‘0’ voltage GOOD V Reading = applied voltage
20
LOADS = Coil OHMMETER VOLTMETER AMMETER A OPEN SHORTED –
Reading = ‘0’ amps SHORTED – an internal problem
21
LOADS = Coil OHMMETER VOLTMETER AMMETER A A OPEN SHORTED –
Reading = ‘0’ amps SHORTED – an internal problem A Short blew fuse: Reading = ‘0’ amp
22
LOADS = Coil OHMMETER VOLTMETER AMMETER A GROUNDED an external problem
Ground blew fuse: Reading = ‘0’ amp GOOD
23
LOADS = Coil OHMMETER VOLTMETER AMMETER A A GROUNDED
an external problem A Ground blew fuse: Reading = ‘0’ amp GOOD A Reading = measureable amps
24
T H E E N D