Download presentation
Presentation is loading. Please wait.
Published byあかり みしま Modified over 5 years ago
1
Objective Revie the Cooling Cycle Learn about air distribution systems
Define Building Zones Solve part of HW3
2
Zones In building How to define the zone in building
Based on cooling/heating load requirement Based on ventilation requirement Based on use of buildings – different apartments deferent zones
3
Air Handling Units (AHU) Control of air Systems
Provide conditioned air Heating, cooling, humidification, dehumidification Ventilation Provide fresh air, remove contaminated air
4
Air Handling Unit (AHU)
Roof top AHU Gas/Electric Heater to building Fan air from building fresh air Evaporator filter mixing AHU schematic Exhaust From room Return fan flow control dampers Supply fan Compressor and Condenser Fresh air To room Outdoor air hot water cool water
5
Air Handling Units (AHS)
Equipment For AHU: Fans Cooling and heating coils Combustion heat exchangers Filtration Dampers, controls, mixing valves Humidification: steam/spray Dehumidification: cooling coil/desiccant Noise control
6
Control of air Systems Vary temperature, constant flow
Constant temperature, vary flow Vary temperature, vary flow
7
Constant Temperature, Variable Volume
On-off systems Residential and small commercial Vary volume by turning system on and off
8
Constant Air Volume Single zone constant air volume
Fan always runs Vary temperature of air in response to space thermostat Single zone constant air volume with reheat Often used for precise humidity control Multizone constant air volume with reheat Good humidity control, flexible Not very efficient
9
Multizone constant air volume with reheat
55°F 62°F Require less cooling
10
Variable Air Volume Single zone VAV Multizone VAV Can also use reheat
Varies air flow based on room thermostat Multizone VAV Central chilled air supply Zone thermostats control flow to each zone Can also use reheat Still need to provide adequate air flow for ventilation and for comfort Smaller energy penalty than CAV
11
VAV terminal
12
Multizone VAV 55°F Vary the flow
13
Reading Assignment Tao and Janis Chapter 3 Chapter 6 (from 6.1 to 6.7)
14
Homework Assignment 4 Table 1 Results of cooling load calculation and required amount of fresh air for ventilation Zone 1 Zone 2 Zone 3 Whole building Sensible cooling load for zone Time when the max cooling load appear 41000 Btu/h at 4 PM 45000 Btu/h at 6 PM 27000 Btu/h at 8 AM 92000 Btu/h Sensible cooling load for critical hour for whole building (6 PM) 37000 Btu/h 9000 Btu/h Latent cooling load (internal sources + infiltration) 5400 Btu/h 5200 Btu/h 16000 Btu/h Required amount of fresh air based on number of occupants 240 CFM (12 occupants) 520 CFM (26 occupants) 1000 CFM (50 occupants)
15
Homework Assignment 3 Supply air 55°F Recirculation air 76°F
Fresh air (Dallas, TX) DBT=102°F
Similar presentations
© 2025 SlidePlayer.com. Inc.
All rights reserved.