1 PowerLogic PM5350 High-performance multifunction power meter
For entry-range metering applications

2 A high-performance multifunction power meter for the entry-range meter market
The PowerLogic PM5350 provides you with a superior entry-range power meter for demanding applications where accuracy is paramount. This user-friendly meter offers the perfect balance of price, features and performance.

3 Offer overview PM5350 meter to monitor and control main feeders:
PM800 series for incomers or critical feeders PM1000 series for basic feeders PM5350 meter to monitor and control main feeders: Accurate and complete measurements Alarming for key parameters Breaker status monitoring and control Embedded serial Modbus communication

4 Applications Panel instrumentation Energy management
Sub-billing and cost allocation Electrical installation remote monitoring Circuit breaker monitoring and control

5 Features Comprehensive measurement package
Energy and demand monitoring THD/TDD & Min/Max reading Pre-configured alarm functions for more than 30 conditions Time stamp & internal time clock 4 digital inputs for circuit breaker status indication 2 relay outputs for circuit breaker control Active Energy compliant with IEC class 0.5S Temperature range confirmed with IEC standard Modbus RS-485 communication port Sealable features (V,I)

6 Easy operation Intuitive navigation with self-guided, language selectable menus Language customization (English & simplified Chinese) Bright, anti-glare dot matrix display (backlit) Summary screens with multiple values Front panel LEDs provide at-a-glance information Orange LED (configurable) w/ 3 modes: Off, Alarm, Energy pulses Green LED w/ 2 modes: Off, Diagnostic Two meter reset levels (global, single parameter) Makes commissioning faster and easier

7 Easy installation Mounting clips (2) hold the meter in place
No other tools required Ultra compact (44mm depth) Save valuable space Connectable up to 480 V L-L without PTs For installations compliant with category III Wetted digital inputs No needs of external power supply Clear identification for all connections Electrical drawings on the meter itself Green connector for communications Avoid mistaking it for the power supply

8 Alarming 29 standard alarms to cover most common needs 4 unary alarms
Pickup magnitude and delays Dropout magnitude and time delays 4 unary alarms Power up, meter reset, self-diagnostic, phase reversal 4 digital input alarms Association alarm – D/O possible 4 levels of priority (None/Low/Med/High) 40 alarms saved in non volatile memory Alarm counter to measure occurrence Alarm time-stamped (1s)

9 Specifications & dimensions
15 pre-defined system configuration types for 4, 3 or 2 wires Data Update: 1 s nominal (50/60 cycles) Input Voltage: 20 to 690 V AC L-L 20 to 400 V AC L-N Input Current: Through CTs CT primary: 5A A CT secondary: 5 A nominal Burden: < VA at 9 A AC control power: V ac DC control power: V dc Temperature: Operating: -20 °C to +70 °C Storage: -40 °C to +85 °C

10 Measured parameters / accuracy ratings
Instantaneous measurements Accuracy Min/Max I1,I2,I3,In ± 0.24% from 0.5 to 9.0 A ü U1,U2,U3,V1,V2,V3 ± 0.30% from 65 to 347 V ac F ± 0.03% from 45 to 70 Hz PFtot, DPFtot, PF1, PF2, PF3, DPF1, DPF2, DPF3 ± 0.50%(Signed) Ptot, Qtot, Stot, P1, P2, P3, Q1, Q2, Q3, S1, S2, S3 ± 0.36%(P-Q Signed) THD / thd I1, I2, I3, In, THD / thd V1,V2,V3,U1,U2,U3 TDD ? Unbalance I, V, U

11 Measured parameters / accuracy ratings
Energy† Accuracy NV Memory Active IEC Class 0.5S ü Reactive IEC Class 2 Apparent ± 0.5% † Capacity of counting ~ 9,2 x 10 ^ 6 Twh or ~ 11 years at 480VL-L / 1000 A Demand Power Type‡ Peak D/T NV Memory Active Total ü Reactive Apparent Current Average ‡ Demand calculations are Sliding, Fixed and Rolling bloc; and Thermal for current only

12 Additional measurements
Load timer with adjustable settings With Low set up calculates total operating feeder time Beyond nominal current settings calculates the overload time Digital Input/Output timers Measurement in (s) for Time On

13 Standards compliance Accuracy
Class 0.5S for active energy according to IEC Class 2 for reactive energy according to IEC IEC PMD /S/K70/0.5 Safety CE as per IEC cULus as per UL61010 Mechanical characteristics according to IEC 60529 IP degree 51 for front of meter IP degree 30 for meter body

14 Standards compliance Electromagnetic compatibility
Electrostatic Discharge Level III (IEC ) Immunity to radiated fields Level III (IEC ) Immunity to fast transients Level III (IEC ) Immunity to impulse waves Level III (IEC ) Conducted immunity Level III (IEC ) Immunity to magnetic field Level III (IEC ) Immunity to voltage dips Level III (IEC ) Conducted and radiated emissions CE commercial environment / FCC part 15 EN55011 Class A Harmonics IEC Flicker emissions IEC

15 Environmental friendly
RoHS Compliant Low energy consumption Possibility to turn off Display and backlit Consumption typical 2 Watts ISO plant manufactured

16 For more detailed information on this product, or other products, services and solutions
Ask your Schneider Electric representative Visit


Download ppt "PowerLogic PM5350 High-performance multifunction power meter"

Similar presentations


Ads by Google