1 2008 Code Drills Health Care Facilities
Smitty’s Speed Drills 2008 Code Drills Health Care Facilities (C) Copyright 2008 Ted "Smitty" Smith

2 (C) Copyright 2008 Ted "Smitty" Smith
Instructions Click on the slide show ICON in the lower left hand corner of this screen to start the slide show. A question will appear and stay on the screen for 2 minutes. The question will then be replaced with the correct answer and code reference. This process will repeat until you reach a slide with a stop sign. You can then click on the slides and the questions and answers will be repeated without the timer so you can look up the answers or take notes. Do not worry about writing down the answers until after the timed portion of the program. Concentrate on finding the answer and improving your speed using the NEC. This drill is focused on changes to the 2008 NEC. (C) Copyright 2008 Ted "Smitty" Smith

3 (C) Copyright 2008 Ted "Smitty" Smith
The life safety branch and critical branch of the emergency system shall be kept __________________ of all other wiring systems and equipment. (C) Copyright 2008 Ted "Smitty" Smith

4 (C) Copyright 2008 Ted "Smitty" Smith
Entirely independent (C)(1) (C) Copyright 2008 Ted "Smitty" Smith

5 (C) Copyright 2008 Ted "Smitty" Smith
All branch circuits serving patient care areas shall be provided with an _________________ by installation in a metal raceway system, or a cable having a metallic armor or sheath assembly. (C) Copyright 2008 Ted "Smitty" Smith

6 (C) Copyright 2008 Ted "Smitty" Smith
An effective ground-fault current path (A) (C) Copyright 2008 Ted "Smitty" Smith

7 (C) Copyright 2008 Ted "Smitty" Smith
The essential electrical system for these facilities shall comprise a system capable of supplying a ______________ of lighting and power service which is considered essential for life safety and orderly cessation of procedures during the time normal electrical service is interrupted for any reason. (C) Copyright 2008 Ted "Smitty" Smith

8 (C) Copyright 2008 Ted "Smitty" Smith
Limited amount (C) Copyright 2008 Ted "Smitty" Smith

9 (C) Copyright 2008 Ted "Smitty" Smith
Which of the following is not allowed as an alternate source of power for the essential electrical systems in a health care facility? Generator located on the premises Battery system A second external utility service, separate from the main external utility provided service An external utility service when the normal source of power consists of a generating unit located on premises. (C) Copyright 2008 Ted "Smitty" Smith

10 (C) Copyright 2008 Ted "Smitty" Smith
A second external utility service (A) An external utility service can only be used as an alternate source of power if the hospital is normally fed by a generating source on the premises. (C) Copyright 2008 Ted "Smitty" Smith

11 (C) Copyright 2008 Ted "Smitty" Smith
The disconnecting means for x-ray equipment shall be operable from a location readily accessible from the ______________. (C) Copyright 2008 Ted "Smitty" Smith

12 (C) Copyright 2008 Ted "Smitty" Smith
X-ray control 517.72(B) (C) Copyright 2008 Ted "Smitty" Smith

13 (C) Copyright 2008 Ted "Smitty" Smith
The task illumination for the medication preparation area of a patient care area shall be permitted to be connected the critical branch and shall be arranged for _______________ connection to the alternate power source. (C) Copyright 2008 Ted "Smitty" Smith

14 (C) Copyright 2008 Ted "Smitty" Smith
Delayed automatic (A) (C) Copyright 2008 Ted "Smitty" Smith

15 (C) Copyright 2008 Ted "Smitty" Smith
The ___________ system shall supply major electrical equipment necessary for patient care and basic hospital operation. (C) Copyright 2008 Ted "Smitty" Smith

16 (C) Copyright 2008 Ted "Smitty" Smith
Equipment (B)(3) (C) Copyright 2008 Ted "Smitty" Smith

17 (C) Copyright 2008 Ted "Smitty" Smith
Isolated power systems shall be permitted to be used for __________________ areas and if used the isolated power system equipment shall be listed as isolated power equipment. (C) Copyright 2008 Ted "Smitty" Smith

18 (C) Copyright 2008 Ted "Smitty" Smith
Critical care (F) (C) Copyright 2008 Ted "Smitty" Smith

19 (C) Copyright 2008 Ted "Smitty" Smith
The grounding terminals of all receptacles and all non-current carrying conductive surfaces of fixed electrical equipment likely to become energized that are subject to personal contact, operating at over ________ volts, shall be connected to an insulated copper grounding conductor. (C) Copyright 2008 Ted "Smitty" Smith

20 (C) Copyright 2008 Ted "Smitty" Smith
(B) (C) Copyright 2008 Ted "Smitty" Smith

21 (C) Copyright 2008 Ted "Smitty" Smith
In addition to the usual control and overcurrent protective devices, each isolated power system shall be provided with a continually operating _________________ that indicates total hazard current. (C) Copyright 2008 Ted "Smitty" Smith

22 (C) Copyright 2008 Ted "Smitty" Smith
Line isolation monitor (B) (C) Copyright 2008 Ted "Smitty" Smith

23 (C) Copyright 2008 Ted "Smitty" Smith
The disconnecting means for x-ray equipment shall be of adequate capacity for at least _______ percent of the input required for momentary rating or 100 percent of the input required for the long-time rating of the x-ray equipment, whichever is greater. (C) Copyright 2008 Ted "Smitty" Smith

24 (C) Copyright 2008 Ted "Smitty" Smith
50 percent (A) (C) Copyright 2008 Ted "Smitty" Smith

25 (C) Copyright 2008 Ted "Smitty" Smith
Illumination of means of egress, such as lighting required for corridors shall be supplied from the ____________ branch of the emergency system. (C) Copyright 2008 Ted "Smitty" Smith

26 (C) Copyright 2008 Ted "Smitty" Smith
Life safety (A) (C) Copyright 2008 Ted "Smitty" Smith

27 (C) Copyright 2008 Ted "Smitty" Smith
Nurse call systems shall be provided power from the __________ branch of the emergency system. (C) Copyright 2008 Ted "Smitty" Smith

28 (C) Copyright 2008 Ted "Smitty" Smith
Critical branch (A)(5) (C) Copyright 2008 Ted "Smitty" Smith

29 (C) Copyright 2008 Ted "Smitty" Smith
Each patient bed location shall be provided with a minimum of __________ receptacles. (C) Copyright 2008 Ted "Smitty" Smith

30 (C) Copyright 2008 Ted "Smitty" Smith
Four (B) (C) Copyright 2008 Ted "Smitty" Smith

31 (C) Copyright 2008 Ted "Smitty" Smith
The equipment grounding terminal buses of the normal and essential branch circuit panelboards serving the same individual patient care vicinity shall be connected together with an insulated continuous copper conductor not smaller than _________ AWG. (C) Copyright 2008 Ted "Smitty" Smith

32 (C) Copyright 2008 Ted "Smitty" Smith
(C) Copyright 2008 Ted "Smitty" Smith

33 (C) Copyright 2008 Ted "Smitty" Smith
End of Drill This is the end of the timed portion of the drill. You can now click on each slide and take your time reviewing the questions and answers. (C) Copyright 2008 Ted "Smitty" Smith

34 (C) Copyright 2008 Ted "Smitty" Smith
The life safety branch and critical branch of the emergency system shall be kept __________________ of all other wiring systems and equipment. (C) Copyright 2008 Ted "Smitty" Smith

35 (C) Copyright 2008 Ted "Smitty" Smith
Entirely independent (C)(1) (C) Copyright 2008 Ted "Smitty" Smith

36 (C) Copyright 2008 Ted "Smitty" Smith
All branch circuits serving patient care areas shall be provided with an _________________ by installation in a metal raceway system, or a cable having a metallic armor or sheath assembly. (C) Copyright 2008 Ted "Smitty" Smith

37 (C) Copyright 2008 Ted "Smitty" Smith
An effective ground-fault current path (A) (C) Copyright 2008 Ted "Smitty" Smith

38 (C) Copyright 2008 Ted "Smitty" Smith
The essential electrical system for these facilities shall comprise a system capable of supplying a ______________ of lighting and power service which is considered essential for life safety and orderly cessation of procedures during the time normal electrical service is interrupted for any reason. (C) Copyright 2008 Ted "Smitty" Smith

39 (C) Copyright 2008 Ted "Smitty" Smith
Limited amount (C) Copyright 2008 Ted "Smitty" Smith

40 (C) Copyright 2008 Ted "Smitty" Smith
Which of the following is not allowed as an alternate source of power for the essential electrical systems in a health care facility? Generator located on the premises Battery system A second external utility service, separate from the main external utility provided service An external utility service when the normal source of power consists of a generating unit located on premises. (C) Copyright 2008 Ted "Smitty" Smith

41 (C) Copyright 2008 Ted "Smitty" Smith
A second external utility service (A) An external utility service can only be used as an alternate source of power if the hospital is normally fed by a generating source on the premises. (C) Copyright 2008 Ted "Smitty" Smith

42 (C) Copyright 2008 Ted "Smitty" Smith
The disconnecting means for x-ray equipment shall be operable from a location readily accessible from the ______________. (C) Copyright 2008 Ted "Smitty" Smith

43 (C) Copyright 2008 Ted "Smitty" Smith
X-ray control 517.72(B) (C) Copyright 2008 Ted "Smitty" Smith

44 (C) Copyright 2008 Ted "Smitty" Smith
The task illumination for the medication preparation area of a patient care area shall be permitted to be connected the critical branch and shall be arranged for _______________ connection to the alternate power source. (C) Copyright 2008 Ted "Smitty" Smith

45 (C) Copyright 2008 Ted "Smitty" Smith
Delayed automatic (A) (C) Copyright 2008 Ted "Smitty" Smith

46 (C) Copyright 2008 Ted "Smitty" Smith
The ___________ system shall supply major electrical equipment necessary for patient care and basic hospital operation. (C) Copyright 2008 Ted "Smitty" Smith

47 (C) Copyright 2008 Ted "Smitty" Smith
Equipment (B)(3) (C) Copyright 2008 Ted "Smitty" Smith

48 (C) Copyright 2008 Ted "Smitty" Smith
Isolated power systems shall be permitted to be used for __________________ areas and if used the isolated power system equipment shall be listed as isolated power equipment. (C) Copyright 2008 Ted "Smitty" Smith

49 (C) Copyright 2008 Ted "Smitty" Smith
Critical care (F) (C) Copyright 2008 Ted "Smitty" Smith

50 (C) Copyright 2008 Ted "Smitty" Smith
The grounding terminals of all receptacles and all non-current carrying conductive surfaces of fixed electrical equipment likely to become energized that are subject to personal contact, operating at over ________ volts, shall be connected to an insulated copper grounding conductor. (C) Copyright 2008 Ted "Smitty" Smith

51 (C) Copyright 2008 Ted "Smitty" Smith
(B) (C) Copyright 2008 Ted "Smitty" Smith

52 (C) Copyright 2008 Ted "Smitty" Smith
In addition to the usual control and overcurrent protective devices, each isolated power system shall be provided with a continually operating _________________ that indicates total hazard current. (C) Copyright 2008 Ted "Smitty" Smith

53 (C) Copyright 2008 Ted "Smitty" Smith
Line isolation monitor (B) (C) Copyright 2008 Ted "Smitty" Smith

54 (C) Copyright 2008 Ted "Smitty" Smith
The disconnecting means for x-ray equipment shall be of adequate capacity for at least _______ percent of the input required for momentary rating or 100 percent of the input required for the long-time rating of the x-ray equipment, whichever is greater. (C) Copyright 2008 Ted "Smitty" Smith

55 (C) Copyright 2008 Ted "Smitty" Smith
50 percent (A) (C) Copyright 2008 Ted "Smitty" Smith

56 (C) Copyright 2008 Ted "Smitty" Smith
Illumination of means of egress, such as lighting required for corridors shall be supplied from the ____________ branch of the emergency system. (C) Copyright 2008 Ted "Smitty" Smith

57 (C) Copyright 2008 Ted "Smitty" Smith
Life safety (A) (C) Copyright 2008 Ted "Smitty" Smith

58 (C) Copyright 2008 Ted "Smitty" Smith
Nurse call systems shall be provided power from the __________ branch of the emergency system. (C) Copyright 2008 Ted "Smitty" Smith

59 (C) Copyright 2008 Ted "Smitty" Smith
Critical branch (A)(5) (C) Copyright 2008 Ted "Smitty" Smith

60 (C) Copyright 2008 Ted "Smitty" Smith
Each patient bed location shall be provided with a minimum of __________ receptacles. (C) Copyright 2008 Ted "Smitty" Smith

61 (C) Copyright 2008 Ted "Smitty" Smith
Four (B) (C) Copyright 2008 Ted "Smitty" Smith

62 (C) Copyright 2008 Ted "Smitty" Smith
The equipment grounding terminal buses of the normal and essential branch circuit panelboards serving the same individual patient care vicinity shall be connected together with an insulated continuous copper conductor not smaller than _________ AWG. (C) Copyright 2008 Ted "Smitty" Smith

63 (C) Copyright 2008 Ted "Smitty" Smith
(C) Copyright 2008 Ted "Smitty" Smith