Earthed & Insulated Distribution Systems 2
3
NER Earthed Power Distribution System When Star point of three phase power generation system is Earthed onboard a ship it is called EARTHED Power distribution system. It must be done through a Neutral Earth Resistor (NER) to limit the fault current below the generator rated current to avoid the service interruption. 3
4
Insulated Power Distribution System When Star point of three phase power generation system is not connected to earth is call INSULATED power distribution system 4
5
NER Earth Fault in Earthed Power Distribution System Large Fault Current Ground Fault An earth fault occurs in earthed power distribution system, it creates a flow of high current. That current will be short circuited the circuit at that moment. A circuit breaker or a circuit protection device tripping mechanism works and disconnect the fault current and ensure the safety of persons and equipment. 5
6
Earth Fault in Insulated Power Distribution System No Fault Current An earth fault occurs in insulated power distribution system, it does not creates a flow of fault current. Therefore we won’t be able to see any power failure due to a one earth fault onboard ship. Ground Fault 6
7
Earth Fault in Insulated Power Distribution System 7 No Fault Current If a fault occur in same phase at two different locations on an insulated systems the system will not be disconnected or circuit breakers will not be operated
8
Earth Fault in Insulated Power Distribution System If an Earth fault occur in two different phases on an insulated systems the system be disconnected or circuit breakers will be operated 8
9
Purpose of Insulated Distribution Systems According to SOLAS regulations neutral insulated systems to be used in cargo area, pump rooms & tankers to avoid explosion hazards due to stray earth current. In a Neutral earthed system a single earth fault would have caused heavy earth current to flow and operate the tripping mechanisms Even with a single earth fault essential services onboard a ship will continue to operate 9
10